Vantage Modulating - Roberts Gordon
Vantage Modulating - Roberts Gordon
Vantage Modulating - Roberts Gordon
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
SECTION 6: HEATER INSTALLATION<br />
FIGURE 16: Linear Heater Layout Overview<br />
LEGEND<br />
Burner<br />
g<br />
b<br />
c<br />
d<br />
e<br />
Reflector<br />
f<br />
Tube<br />
20' (6 m) Tube Length<br />
Tube/Reflector<br />
Hanger<br />
Coupling<br />
Assembly<br />
g<br />
b<br />
c<br />
d e e<br />
Vent Adapter<br />
f<br />
a = 14" (36 cm)<br />
reflector width (not shown)<br />
b = 2" (5 cm)<br />
end cap to burner<br />
g<br />
b<br />
c<br />
30' (9 m) Tube Length<br />
d e e e<br />
c = 2" (5 cm)<br />
end cap to hanger<br />
f<br />
d = 7'6" (229 cm)<br />
distance first hanger<br />
e = 10' (305 cm)<br />
distance between hangers<br />
g<br />
b<br />
c<br />
40' (12 m) Tube Length<br />
d e e e e<br />
f = 9.5" (24 cm)<br />
burner height<br />
g = 17.5" (44 cm)<br />
burner length<br />
f<br />
50' (15 m) Tube Length<br />
g<br />
b<br />
c<br />
d e e e e e<br />
g<br />
f<br />
b<br />
c<br />
b<br />
60' (18 m) Tube Length<br />
d e e e e e e<br />
f<br />
70' (21 m) Tube Length<br />
g<br />
b<br />
c<br />
d e e e e e e<br />
e<br />
b<br />
f<br />
80' (24 m) Tube Length<br />
15 of 71