Metartec’s <strong>CENTI</strong> UPS Series<br />

Low THDi and Advanced Power Factor Control<br />

The <strong>CENTI</strong> UPS uses a new input IGBT Rectifier and<br />

an advanced PFC (Power Factor Control) capable<br />

of keeping input current Total Harmonic Distortion<br />

(THDi) at a low level (0.99)<br />

Key benefits are that the UPS is compatible with<br />

the upstream source, the mains or any kind of<br />

generator. The transfer of power between the load<br />

and the source is more efficient. This results in a<br />

saving in terms of sources – cables and protective<br />

devices.<br />

ECO UPS High Efficiency – Reducing overall cost of<br />

ownership<br />

The <strong>CENTI</strong> Series operates at a high efficiency of<br />

up to 95% in on-line mode. This reduces utility costs.<br />

Moreover higher system efficiency reduces facility<br />

air-conditioning costs and increases reliability.<br />

Because of the technology used – no additional<br />

losses are generated to get low input harmonics or<br />

increased input power factor.<br />

Double Conversion Topology<br />

True Online Double conversion topology (VFI –<br />

Voltage and Frequency Independent).<br />

The <strong>CENTI</strong> is designed to maintain very tight control<br />

over the output voltage and will comfortably handle<br />

100% load shifts. Unbalanced non-linear loads or IT<br />

Systems with a leading power factor will not require<br />

that the unit is upgraded.<br />

Advanced Technology<br />

The <strong>CENTI</strong> is a flexible and reliable UPS System<br />

offering advanced state-of-the-art total digital control.<br />

The design ensures that auxiliary power supplies<br />

and processors are no longer single points of failure<br />

that would compromise high availability of clean<br />

power to the load.<br />

The status of the most critical components is<br />

constantly monitored allowing for predictive<br />

maintenance, avoiding unexpected breakdowns.<br />

Parallel System for Redundancy or increase in<br />

Capacity<br />

The parallel UPS configuration is provided with<br />

control for operation of both redundant and<br />

capacity increase. The parallel control is fully<br />

digital and acts on both active and reactive power<br />

on each phase, allowing for accurate load current<br />

sharing among the active UPS systems in the parallel<br />

configuration. The parallel control is extremely<br />

simple and interconnections make installations and<br />

in the field upgrading simple.<br />

Further details on the<br />

<strong>CENTI</strong> UPS Series and information<br />

on Metartec’s complete range<br />

of critical power products and<br />

services can be viewed at<br />

www.metartec.com,<br />

alternatively call us on<br />

0845 50 40 444 or<br />

email info@metartec.com


POWER (kVA) 10 15 20 30 40<br />

UPS type<br />

ONLINE – Double Conversion<br />

Nominal output power (Cos φ 0,8) kVA 10 15 20 30 40<br />

Nominal output power (Cos φ 1,0) kW 8 12 16 24 32<br />

Efficiency (AC ÷AC)<br />

ON LINE – Double Conversion<br />

@25% load<br />

@50% load<br />

@75% load<br />

@100% load<br />

> 86%<br />

> 88%<br />

> 90%<br />

> 92%<br />

Efficiency (AC ÷AC) (Eco Mode) > 98%<br />

Heat dissipation at nominal load and<br />

voltage<br />

W<br />

Kcal/h<br />

695<br />

598<br />

1040<br />

894<br />

1390<br />

1195<br />

2080<br />

1788<br />

2780<br />

2390<br />

UPS ambient temperature (°C) 0 ÷ 40<br />

BATTERY ambient temperature (°C) 0 ÷ +25<br />

UPS storage temperature (°C) -10 ÷ +70<br />

BATTERY storage temperature (°C) -10 ÷ +60<br />

Relative humidity (non condensing) From 20% to 80% < 95%<br />

Altitude<br />

< 1000m (above sea level)<br />

Power derating for altitude > 1000 m<br />

According to “IEC62040-3”, 1% power derating every 100m above 1000m, up to max 2000m<br />

Ventilation<br />

Forced<br />

Requested cooling air volume (m3/h) 500 500 600 800 900<br />

Audible noise level (according EN 50091) < 50dB < 60dB<br />

Standard battery type lead acid (n° cells) 2 x 180<br />

Protection degree IP 20<br />

Electromagnetic compatibility EMI According to “EN50091-2” (CE marking) According to “IEC EN 62040-2” (CE marking)<br />

Safety IEC EN 62040-1<br />

Test and performances IEC EN 62040-3<br />

Paint RAL 7035<br />

Accessibility<br />

Front and top access for service<br />

Installation<br />

10cm from the wall<br />

Dimensions (mm) W x D x H 450 x 650 x 1200<br />

Weights (without battery – with battery) kgs 90-250 100-260 100-260 141<br />

Static load (without battery – with battery) kg/m2 310-854 340-890 340-890 483<br />

Input/Output cable connection Bottom/rear side Bottom/front side<br />

Transport<br />

By wheels<br />

Transport mechanical stress According to “IEC EN 62040-3”<br />

Design standard According to “EN50091” “IEC 62040” “IEC EN 62040” “ISO 9001:2008”<br />

Free contact interface<br />

On Request<br />

Serial communication interface<br />

Standard: RS232<br />

Standard: RS232 – USB Optional: RS485 (Mod-<br />

Bus protocol)<br />

Parallel configuration (optional)<br />

Up to 3+1 (redundant parallel) Up to 4 (power parallel)<br />

POWER (kVA) 60 80 100 125 160 200 250 300<br />

UPS type<br />

ONLINE – Double Conversion<br />

Nominal output power (Cos φ 0,8) kVA 60 80 100 125 160 200 250 300<br />

Nominal output power (Cos φ 1,0) kW 48 64 80 100 128 160 200 240<br />

Efficiency (AC ÷AC)<br />

ON LINE – Double Conversion<br />

@25% load<br />

@50% load<br />

@75% load<br />

@100% load<br />

> 88%<br />

> 90%<br />

> 92%<br />

> 93%<br />

Efficiency (AC ÷AC) (Eco Mode) > 98%<br />

Heat dissipation at nominal load and<br />

voltage<br />

kW<br />

Kcal/h<br />

3,8<br />

3,3<br />

4,8<br />

4,2<br />

6,0<br />

5,2<br />

7,5<br />

6,5<br />

UPS ambient temperature (°C) 0 ÷ 40<br />

BATTERY ambient temperature (°C) 0 ÷ +25<br />

UPS storage temperature (°C) -10 ÷ +70<br />

BATTERY storage temperature (°C) -10 ÷ +60<br />

Relative humidity (non condensing) < 95%<br />

Altitude<br />

< 1000m (above sea level)<br />

Power derating for altitude > 1000 m<br />

According to “IEC62040-3”, 1% power derating every 100m above 1000m, up to max 2000m<br />

Ventilation<br />

Forced<br />

Requested cooling air volume (m3/h) 1600 1800 2100 2300 2500 3500 4100 4500<br />

Audible noise level (according EN 50091) < 60dB < 62dB<br />

Standard battery type lead acid (n° cells)<br />

300 – 312 adjustable<br />

Protection degree IP 20<br />

Electromagnetic compatibility EMI<br />

According to “IEC EN 62040-2” (CE marking)<br />

Safety IEC EN 62040-1<br />

Test and performances IEC EN 62040-3<br />

Paint RAL 7016<br />

Accessibility<br />

Front and top access for service<br />

Installation<br />

Also against wall and/or side-by-side<br />

Dimensions (mm) W x D x H 815 x 865 x 1705 1200 x 895 x 1905<br />

Weights (without battery) kgs 570 600 630 662 720 870 1020 1200<br />

Static load (without battery) kg/m2 948 998 1048 1101 1198 925 1085 1277<br />

Input/Output cable connection<br />

Bottom Side (Top Side on Request)<br />

Transport<br />

Base provided for forklift handling<br />

Transport mechanical stress According to “IEC EN 62040-3”<br />

Design standard “IEC EN 62040” “ISO 9001:2008”<br />

Free contact interface<br />

Standard remote contacts are available: EPO – MBCB – BCB – DIESEL MODE<br />

Serial communication interface Standard: RS232 – USB Optional: RS485 (Mod-Bus protocol)<br />

Parallel configuration (optional) Up to 5+1 (redundant parallel) Up to 6 (power parallel)<br />

Battery Technical Specification<br />

POWER (kVA) 10 15 20 30 40 60 80 100 125 160 200 250 300<br />

Type (standard) other on request<br />

Lead Sealed – maintenance free<br />

Number of Cells 2x180, 2x186 (for output 415V) 300 – 312 adjustable<br />

Floating voltage at 25°C 2x406, 2x418 (for output 415V) 680 for 300 cells, 707 for 312 cells (adjustable)<br />

Minimum discharge voltage 2x310 496 for 300 cells, 516 for 312 cells (adjustable)<br />

Power requested by inverter (At nominal Load)<br />

KW<br />

8,5 12,7 17 25.4 34 50 68 84 105 135 168 210 252<br />

Current required from inverter<br />

(at nominal load-minimum Vdc) (A)<br />

12 18 24 36 48 102 136 170 212 272 340 425 510<br />

Battery Protection (external to the UPS) Fuses Wall mounted fused switch box on request<br />

Battery Test<br />

Included as standard<br />

BS.DOC.052 Issue 1<br />

9,6<br />

8,3<br />

11,2<br />

9,6<br />

14,0<br />

12,0<br />

16,8<br />

14,4<br />

UK: Elm Park House, Elm Park Court, Pinner, Middlesex, HA5 3NN. Tel: 0845 64 39 772<br />

NI: Solutions House, 13 Harbour View, Heron Road, Belfast, BT3 9LE. Tel: 0845 50 40 444<br />

Email: info@metartec.com Visit: www.metartec.com