15.01.2015 Views

Operating Instructions MDK-ES-10 Multifunction Control Unit

Operating Instructions MDK-ES-10 Multifunction Control Unit

Operating Instructions MDK-ES-10 Multifunction Control Unit

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>Operating</strong> <strong>Instructions</strong><br />

<strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong><br />

<strong>Multifunction</strong> <strong>Control</strong> <strong>Unit</strong><br />

Art. No. 215.00.000<br />

E-Mail:verkauf@se-ag.ch<br />

Internet:www.se-ag.ch<br />

starkstrom-elektronik ag<br />

Schweiz Suisse Switzerland<br />

Güterstrasse 11, CH-8957 Spreitenbach<br />

Tel. +41 56 418 76 11, Fax +41 56 401 49 86<br />

11522e-A4<br />

BA-<strong>MDK</strong>-<strong>ES</strong>-V3-A4-en


2 <strong>Operating</strong> <strong>Instructions</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong><br />

Contents<br />

1 <strong>Multifunction</strong> <strong>Control</strong> <strong>Unit</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong> ............................................................................................. 3<br />

1.1 Introduction................................................................................................................................ 3<br />

1.2 Intended use.............................................................................................................................. 3<br />

1.3 Basic specifications ................................................................................................................... 3<br />

2 Safety rules ....................................................................................................................................... 3<br />

2.1 Responsibilities.......................................................................................................................... 3<br />

2.2 Safety symbols .......................................................................................................................... 4<br />

2.3 Residual dangers....................................................................................................................... 4<br />

2.4 Special rules to be observed ..................................................................................................... 4<br />

3 <strong>Control</strong> .............................................................................................................................................. 5<br />

3.1 Analogue control with ON/OFF key ........................................................................................... 6<br />

3.2 Analogue control without ON/OFF key ...................................................................................... 6<br />

3.3 Single-key control (ETS)............................................................................................................ 7<br />

3.4 Daylight-dependent control (TLR) ............................................................................................. 8<br />

3.5 Multikey control with 4 presets and program enable ................................................................. 9<br />

3.6 Multikey control with 4 presets without program enable.......................................................... <strong>10</strong><br />

3.7 Multikey control with 2 presets and program enable ............................................................... <strong>10</strong><br />

3.8 Multikey control with 2 presets without program enable.......................................................... 11<br />

3.9 Movement-dependent control.................................................................................................. 12<br />

3.<strong>10</strong> Central switch-on/off................................................................................................................ 13<br />

3.11 Switch-on or overdrive with analogue signal with key control.................................................. 14<br />

4 Load circuit ..................................................................................................................................... 15<br />

4.1 Fluorescent lamps (FL) with dimmable electronic ballasts (EVGs)........................................ 15<br />

4.2 Standard dimmers ................................................................................................................... 16<br />

4.3 Three-phase load with EVGs................................................................................................... 17<br />

5 Standard diagrams (standard applications).................................................................................... 18<br />

5.1 Several <strong>MDK</strong>s, paralleled control points (external supply) ...................................................... 18<br />

5.2 Daylight-dependent regulation with 2 circuits .......................................................................... 19<br />

5.3 Room interconnection in MTS mode ....................................................................................... 20<br />

6 Switch-on/off ramps........................................................................................................................ 21<br />

7 Switched output .............................................................................................................................. 21<br />

8 LED signalling on control unit ......................................................................................................... 21<br />

9 Service mode.................................................................................................................................. 22<br />

9.1 Setting time analogue.............................................................................................................. 22<br />

9.2 Setting time.............................................................................................................................. 22<br />

9.3 Fading time.............................................................................................................................. 22<br />

9.4 Minimum light value................................................................................................................. 23<br />

9.5 Maximum light value................................................................................................................ 23<br />

9.6 Preheat time ............................................................................................................................ 23<br />

9.7 General reset........................................................................................................................... 23<br />

<strong>10</strong> Installation and wiring ..................................................................................................................... 24<br />

<strong>10</strong>.1 Installing the <strong>MDK</strong>.................................................................................................................... 24<br />

<strong>10</strong>.2 Placing in electric's cubicle...................................................................................................... 25<br />

11 Technical data ................................................................................................................................ 26<br />

12 Trouble shooting ............................................................................................................................. 29<br />

13 Maintenance and disposal .............................................................................................................. 29<br />

14 Accessories to <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong> ............................................................................................................ 30<br />

11522e V3<br />

starkstrom-elektronik ag<br />

CH-8957 Spreitenbach


<strong>Operating</strong> <strong>Instructions</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong> 3<br />

1 <strong>Multifunction</strong> <strong>Control</strong> <strong>Unit</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong><br />

1.1 Introduction<br />

The <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong> is a multifunction control unit employing forward phase control technique. It can be controlled in<br />

various modes and can also regulate different loads:<br />

•= control via potentiometer<br />

•= control by a single key<br />

•= control by several keys<br />

•= control with switch-dim actuator<br />

•=<br />

•=<br />

regulating fluorescent lamps via dimmable electronic ballast<br />

regulating additional standard control units<br />

The <strong>MDK</strong> has both a an analogue output (0...<strong>10</strong>V) and a switched output (230V). Both outputs have an<br />

integrated switch-on/off function, so that installation of the usual contactor is superfluous.<br />

The <strong>MDK</strong> can be connected to several control points, and several <strong>MDK</strong>s may be paralleled to a central control<br />

panel.<br />

Moreover the <strong>MDK</strong> can control the load according to daylight or movement, or switch the load on and off<br />

centrally.<br />

1.2 Intended use<br />

A varitens multifunction control unit is intended solely for controlling light sources. It is suited for use in indoor<br />

switch panels, though the ambient conditions set out in Section 11 (Technical Data) must be assured for certain.<br />

The control unit may be put into operation and placed under voltage only after proper connection according to<br />

Section 3 to 5 "<strong>Control</strong>", "Load Circuit" and "Standard Diagrams" (Standard Applications).<br />

Note:<br />

The manufacturer (or supplier of the <strong>MDK</strong>-AN06 as the case may be) declines all liability for any<br />

damage or injury to persons caused by improper use or failure to observe these instructions.<br />

1.3 Basic specifications<br />

The <strong>MDK</strong> is supplied complete as a snap-on unit for cap rail mounting, together with these operating instructions.<br />

All functions described in the instructions are implemented at all times.<br />

2 Safety rules<br />

2.1 Responsibilities<br />

Installation, commissioning or maintenance of the <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong> may be performed only if the following safety rules<br />

are observed as well as the safety-relevant instructions in the individual sections. In particular the person<br />

installing the control unit is responsible for the security of persons and for any material damage, also for<br />

providing the operator with the necessary information. He is furthermore responsible for satisfying the general<br />

work safety regulations in force and the safety rules for working on medium-voltage electrical equipment.<br />

starkstrom-elektronik ag<br />

CH-8957 Spreitenbach<br />

11522e V3


4 <strong>Operating</strong> <strong>Instructions</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong><br />

2.2 Safety symbols<br />

The following symbols draw attention to the various danger levels in the individual sections:<br />

Information, instructions or prohibitions to prevent serious damage or injury to persons.<br />

Special information, instructions or prohibitions for preventing lesser damage.<br />

Note:<br />

Special information for obtaining the best use from the equipment.<br />

2.3 Residual dangers<br />

If the <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong> is used as it should be, all relevant standards and regulations aimed at preventing injury to<br />

persons and damage will be fulfilled. Nevertheless residual dangers from live connections cannot be ruled out<br />

entirely. The principal parts with potential residual dangers are shown in Fig. 2-1 below:<br />

Fig. 2 - 1<br />

Potential residual danger by touching connections under medium voltage (230 Vac)<br />

2.4 Special rules to be observed<br />

The <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong> multifunction control unit may be installed and used only if it is in perfect<br />

condition and the operating instructions are complied with.<br />

The electrical connections (supply and control unit output etc.) may be connected and<br />

disconnected only when not under voltage (see also section 2.3: Residual Dangers).<br />

Working on live connections may lead to severe injury due to electric shock.<br />

The output LS is not isolated when the control unit is switched off. A separate automatic cutout<br />

must be fitted in the supply lead.<br />

11522e V3<br />

starkstrom-elektronik ag<br />

CH-8957 Spreitenbach


<strong>Operating</strong> <strong>Instructions</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong> 5<br />

3 <strong>Control</strong><br />

The <strong>MDK</strong> differentiates between 8 operating modes, which are adjusted on it from outside with 3 DIP switches.<br />

The 8 modes differ in the way the <strong>MDK</strong> is controlled:<br />

•= analogue control with ON/OFF key<br />

•= analogue control without ON/OFF key<br />

•= single-key control (ETS))<br />

•= daylight-dependent control (TLR)<br />

•= multikey control (MTS) with 4 presets with program enable<br />

•= multikey control (MTS) with 4 presets without program control<br />

•= multikey control (MTS) with 2 presets with program control<br />

•= ultikey control (MTS) with 2 presets without program co<br />

With a further DIP switch the control unit may be switched over into a service mode, and with another 2 DIP<br />

switches the kind of lamp may be selected.<br />

1 2 3 4 5 6 DIP Switch<br />

Analogue with ON/OFF (potentiometer, ext. setpoint)<br />

Analogue without ON/OFF (potentiometer, ext.<br />

Single-key control (ETS)<br />

Daylight-dependent control (TLR)<br />

MTS preset storage allowed, 4xP<br />

MTS preset storage blocked, 4xP<br />

MTS preset storage allowed, 2xP<br />

MTS preset storage blocked, 2xP<br />

Service mode<br />

el. ballast (EVG) not off at min. light<br />

el. ballast (EVG) off at min. light<br />

<br />

Dimmer<br />

Tab. 3 - 1 Functions of DIP switches 1-6 = ON, = OFF<br />

starkstrom-elektronik ag<br />

CH-8957 Spreitenbach<br />

11522e V3


6 <strong>Operating</strong> <strong>Instructions</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong><br />

3.1 Analogue control with ON/OFF key<br />

With a standard <strong>10</strong> k potentiometer the load is regulated from the adjustable minimum light value to the similarly<br />

adjustable maximum. Instead of the potentiometer a 0-<strong>10</strong>V control voltage or sink current source (e.g. EIB<br />

switching dimming actuator) may be used. With sink current control a jumper must be placed between IN:0-<strong>10</strong>V<br />

and 12V-<strong>10</strong>k . Using an ON/OFF key with back signalling (LED), the <strong>MDK</strong> is switched on and off. When the<br />

control unit is switched off the switched output is likewise inactive.<br />

In this operating mode the inputs for movement detector (Section 3.9) and central ON/OFF (Section 3.<strong>10</strong>) are<br />

usable.<br />

Switch settings:<br />

1 2 3 4 5 6<br />

•= Analogous with ON/OFF<br />

Fig. 3 - 1 Potentiometer and ON/OFF key with back signalling, e.g. PDP-H-ETE, Art. No. 313.<strong>10</strong>.014<br />

3.2 Analogue control without ON/OFF key<br />

A potentiometer, an external control voltage 0-<strong>10</strong>V or a sink current source (e.g. EIB switching dimming actuator)<br />

is to be connected. In this mode the control unit is switched on and off via the control voltage. A voltage below<br />

0.6V switches the control unit off, a voltage above 0.6V switches it on again. When the control unit is switched off<br />

the switched output for preheating is also inactive.<br />

In this operating mode the inputs for movement detectors (Section 3.9) and central ON/OFF (Section 3.<strong>10</strong>) are<br />

usable.<br />

1 2 3 4 5 6<br />

Switch settings:<br />

•=<br />

Analogous without ON/OFF<br />

Note: The connection diagram is as Fig, 3-1 without ON/OFF key.<br />

11522e V3<br />

starkstrom-elektronik ag<br />

CH-8957 Spreitenbach


<strong>Operating</strong> <strong>Instructions</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong> 7<br />

3.3 Single-key control (ETS)<br />

In this mode only the ON/OFF key with back signalling is active. A short actuating pulse (50...300 ms) switches<br />

the control unit on or off. A long pulse (exceeding 300 ms) dims. The sense of action is reversed by releasing the<br />

key and then pressing it again longer than 300 ms. The control unit runs from one limit to the other. When it is at<br />

minimum (service parameter "minimum light") the heat conductor remains switched on.<br />

The heat conductor and the phase angle are switched off by the ON/OFF function.<br />

When the control unit is switched off and the ON/OFF key is pressed and not released, the control unit runs from<br />

0% to <strong>10</strong>0% brightness after 300 ms (dimming function).<br />

If the light is dimmed to 0% brightness, depending on the control the output LS switches off after 1s (see Section<br />

4).<br />

When the control unit is switched on by briefly pressing the key, the value active before switching-off is assumed.<br />

If this was less than 5% of the maximum, the switch-on light value is assumed. (The switch-on value is stored<br />

with the ON/OFF key in the MTS mode).<br />

In this operating mode the inputs for movement detectors (Section 3.9) and central ON/OFF (Section 3.<strong>10</strong>) are<br />

usable.<br />

Switch settings:<br />

1 2 3 4 5 6<br />

•= Single-key control (ETS)<br />

Fig. 3 - 2 Single-key control by ON/OFF key with back signalling, e.g. DPL-H-ETE, Art. No. 312.<strong>10</strong>.014<br />

starkstrom-elektronik ag<br />

CH-8957 Spreitenbach<br />

11522e V3


8 <strong>Operating</strong> <strong>Instructions</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong><br />

3.4 Daylight-dependent control (TLR)<br />

By connecting a mixed light sensor (LFM) with an ON/OFF key and "lighter" and "darker" keys, daylightdependent<br />

control can be obtained. For the ON/OFF key a back signalling LED may be controlled. With the<br />

lighter and darker keys the setpoint can be altered. With the ON/OFF key the adjusted light setpoint can be<br />

stored (press till the back signal of the ON/OFF key flashes). When the control unit is switched on, the stored<br />

value is regulated (basic value 5V). If the daylight changes, the <strong>MDK</strong> regulates the artificial light till the adjusted<br />

setpoint is reached. If artificial light is no longer necessary, it is switched off. When daylight fades (e.g. in the<br />

evening) the artificial light is switched on again.<br />

In this operating mode the inputs for movement detectors (Section 3.9) and central ON/OFF (Section 3.<strong>10</strong>) are<br />

usable.<br />

Switch settings:<br />

1 2 3 4 5 6<br />

•= Daylight-dependent control (TLR)<br />

Note: To avoid storing an altered setpoint the connection T3 can be laid to 0V.<br />

By connecting T2 to 0V, switching-on again depending on daylight can be prevented (see Fig. 3-3).<br />

* SWITCHING ON AGAIN DEPENDING ON DAYLIGHT BLOCKED WITH<br />

CONNECTION BETWEEN 0V (GND) AND T2<br />

** STORAGE BLOCKED<br />

*<br />

Fig. 3 - 3<br />

Daylight-dependent control with mixed light sensor Art. No. 223.20.901, ON/OFF key, "lighter" and "darker" keys<br />

and back signalling LED (e.g. DPL-3KETE, Art. No. 312.11.234)<br />

11522e V3<br />

starkstrom-elektronik ag<br />

CH-8957 Spreitenbach


<strong>Operating</strong> <strong>Instructions</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong> 9<br />

3.5 Multikey control with 4 presets and program enable<br />

In this mode the following keys may be connected:<br />

•= ON/OFF with back signalling<br />

•= lighter<br />

•= darker<br />

•= preset 1..4 with back signalling<br />

The control unit is switched on with the ON/OFF key. The switch-on light value is assumed. By pressing one of<br />

the preset keys (50 ms ... 3 s) the control unit can be switched on also. A preselected light value is then<br />

assumed. With the "lighter"/"darker" keys the value may be altered and stored as new setpoint by prolonged<br />

pressure (over 3 s) on the corresponding preset key. By prolonged pressure (over 3 s) on the ON/OFF key the<br />

switch-on light value can be stored. Light values cannot be stored while the control unit is switched off.<br />

If the light is dimmed to 0% brightness, depending on the control the output LS switches off after 1s (see Section<br />

4).<br />

In this operating mode the signals from the movement detector, central ON / OFF are not available.<br />

Switch settings:<br />

•= Multikey control (MTS) with 4 presets<br />

Storage allowed<br />

1 2 3 4 5 6<br />

Fig. 3 - 4<br />

Multikey control with ON/OFF key, "lighter" and "darker" keys, 4 preset keys and back signals, e.g. DPL-7K-ETE<br />

(4 presets), Art. No. 312.11.274<br />

starkstrom-elektronik ag<br />

CH-8957 Spreitenbach<br />

11522e V3


<strong>10</strong> <strong>Operating</strong> <strong>Instructions</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong><br />

3.6 Multikey control with 4 presets without program enable<br />

The following keys are connected in this mode:<br />

•= ON/OFF with back signalling<br />

•= lighter<br />

•= darker<br />

•= preset 1..4 with back signalling<br />

The control unit is switched on with the ON/OFF key. The switch-on light value is assumed.<br />

By pressing one of the preset keys (50 ms - 3 s) the control unit can be switched on too. A preselected setting is<br />

then assumed. This value may be altered with the "lighter"/"darker" keys.<br />

Light values cannot be stored in this operating mode.<br />

If the light is dimmed to 0% brightness, depending on the control the output LS switches off after 1s (see Section<br />

4).<br />

In this operating mode the signals from the movement detector, central ON / OFF are not available.<br />

Switch settings:<br />

•= Multikey control (MTS) with 4 presets<br />

Storage blocked<br />

1 2 3 4 5 6<br />

Note: The connection diagram is as Fig. 3 - 4.<br />

3.7 Multikey control with 2 presets and program enable<br />

The following keys are connected in this mode:<br />

•= ON/OFF with back signalling<br />

•= lighter<br />

•= darker<br />

•= presets 1 and 2 with back signalling<br />

The control unit is switched on with the ON/OFF key. The switch-on light value is assumed. By pressing one of<br />

the preset keys (50 ms - 3 s) the control unit can be switched on too. A preselected light value is then assumed.<br />

With the "lighter"/"darker" keys the brightness may be altered, and by prolonged pressure on the corresponding<br />

preset key (over 3 s) a new light setpoint can be stored. The switch-on light value may be stored by prolonged<br />

pressing (over 3 s) on the ON/OFF key. Light values cannot be stored while the control unit is switched off.<br />

If the light is dimmed to 0% brightness, depending on the control the output LS switches off after 1s (see Section<br />

4).<br />

In this mode the inputs for movement detectors (Section 3.9) and central ON/OFF (Section 1 2 3 4 3.<strong>10</strong>) 5 6 are<br />

usable.<br />

Switch settings:<br />

•=<br />

Multiswitch control (MTS) with 2 presets<br />

Storage allowed<br />

Note: The connection diagram is as Fig. 3 - 4.<br />

The keys at T3 and T4 (presets 3 and 4) and the LEDs on R3 and R4 (back signalling from presets 3<br />

and 4) are not used.<br />

11522e V3<br />

starkstrom-elektronik ag<br />

CH-8957 Spreitenbach


<strong>Operating</strong> <strong>Instructions</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong> 11<br />

3.8 Multikey control with 2 presets without program enable<br />

The following keys are connected in this operating mode:<br />

•= ON/OFF with back signalling<br />

•= lighter<br />

•= darker<br />

•= presets 1 and 2 with back signalling<br />

The control unit is switched on with the ON/OFF key. The switch-on light value is assumed. By pressing one of<br />

the preset keys (50 ms - 3 s) the control unit can be switched on too. A preselected setting is then assumed. This<br />

value may be altered with the "lighter"/"darker" keys.<br />

Light values cannot be stored in this operating mode.<br />

If the light is dimmed to 0% brightness, depending on the control the output LS switches off after 1s (see Section<br />

4).<br />

1 2 3 4 5 6<br />

The inputs for movement detectors (Section 3.9) and central ON and OFF (Section 3.<strong>10</strong>) are possible in<br />

this mode.<br />

Switch settings:<br />

1 2 3 4 5 6<br />

•= Multikey control (MTS) with 2 presets<br />

Storage blocked<br />

Note: The connection diagram is as Fig. 3 - 4.<br />

The keys on T3 and T4 (presets 3 and 4) and the LEDs on R3 and R4 (back signalling from presets<br />

3 and 4) are not used.<br />

starkstrom-elektronik ag<br />

CH-8957 Spreitenbach<br />

11522e V3


12 <strong>Operating</strong> <strong>Instructions</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong><br />

3.9 Movement-dependent control<br />

A movement detector connected to the <strong>MDK</strong> with potential-free contacts (or open collector output) switches on<br />

the lighting when the room is entered and switches it off again when it is left. This operating mode may be<br />

combined with others, though with multikey control there may be only 2 presets still available.<br />

Note:<br />

The movement detector is connected at terminal T4, consequently this operating mode cannot be<br />

combined with multikey control with 4 presets and program enable or multikey control with 4 presets<br />

without program enable.<br />

Fig. 3 - 5 Movement-dependent control with movement sensor, e.g. BWM-ECO-IR 360A, Art. No. 223.20.915<br />

11522e V3<br />

starkstrom-elektronik ag<br />

CH-8957 Spreitenbach


<strong>Operating</strong> <strong>Instructions</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong> 13<br />

3.<strong>10</strong> Central switch-on/off<br />

By connecting an ON and an OFF key, one or more <strong>MDK</strong>s may be switched on and off centrally from a single<br />

point.<br />

Note:<br />

The central ON and OFF keys are connected at the terminals R3 and R4. Consequently this<br />

operating mode cannot be combined with multikey control with 4 presets and program enable or<br />

multikey control with 4 presets without program enable.<br />

* TO OTHER EQUIPMENT<br />

Fig. 3 - 6 Central switch-on/off with I and O keys, e.g. DP-2K-ETE, Art. No. 312.11.124.<br />

starkstrom-elektronik ag<br />

CH-8957 Spreitenbach<br />

11522e V3


14 <strong>Operating</strong> <strong>Instructions</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong><br />

3.11 Switch-on or overdrive with analogue signal with key control<br />

By applying a voltage at the analogue input (IN 0-<strong>10</strong>V) the control unit is switched on or overdriven. In this way<br />

an emergency circuit may be obtained. There are two possibilities for this:<br />

•= With a potential-free contact the <strong>10</strong>V output of the control unit is switched onto the analogue input.<br />

Fig. 3 - 7<br />

Overdrive with potential-free contact<br />

•=<br />

An external voltage (below <strong>10</strong>V) may be switched onto the analogue input.<br />

Fig. 3 - 8<br />

Overdrive with external voltage source<br />

11522e V3<br />

starkstrom-elektronik ag<br />

CH-8957 Spreitenbach


<strong>Operating</strong> <strong>Instructions</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong> 15<br />

4 Load circuit<br />

With the multifunction control unit, dimmable electronic ballasts (EVGs) or dimmers are operated. Besides the<br />

analog output (0...<strong>10</strong>V) the unit has a solid-state relay with which loads up to a current of <strong>10</strong>A are switched on<br />

and off.<br />

With the DIP switches 1 and 2 the load to be controlled can be selected. When an EVG is selected, the switched<br />

output has a preheat time of 0.45/1.5s compared with the analogue output (see Section 7 for preheat time of<br />

EVG). With dimmers the preheat time is 50ms.<br />

If the light is dimmed to 0% brightness with key control in the 2nd switch setting (EVG is cut out at min. light), the<br />

output LS cuts out as soon as the minimum light has been controlled during 1 s. With the other two switch<br />

settings the output LS remains switched on.<br />

Switch settings:<br />

1 2 3 4 5 6<br />

•=<br />

•=<br />

•=<br />

el. ballast (EVG) not off at min. light<br />

el. ballast (EVG) off at min. light<br />

dimmer<br />

4.1 Fluorescent lamps (FL) with dimmable electronic ballasts (EVGs)<br />

When using dimmable electronic ballasts the switched voltage of the <strong>MDK</strong> is taken as supply voltage and the<br />

analogue output as control signal. The analogue output may be loaded up to +6,-<strong>10</strong>0mA (equivalent to 650<br />

setronic(R) EVGs). The switched output LS can be loaded with <strong>10</strong>A. If a heavier current is needed, a contactor<br />

may be controlled with this output (see Section 4.3).<br />

If the light is dimmed to 0% brightness in the 2nd switch setting (EVG cuts out at minimum light) the output LS<br />

cuts out as soon as the minimum light has been controlled during 1s. In the other switch setting the output LS<br />

remains switched on.<br />

Switch settings:<br />

1 2 3 4 5 6<br />

•=<br />

•=<br />

el. ballast (EVG) not off at min. light<br />

el. ballast (EVG) off at min. light<br />

Fig. 4 - 1<br />

Fluorescent lamps with EVGs.<br />

starkstrom-elektronik ag<br />

CH-8957 Spreitenbach<br />

11522e V3


16 <strong>Operating</strong> <strong>Instructions</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong><br />

4.2 Standard dimmers<br />

When using dimmers (phase angle or phase interval) the switched voltage of the <strong>MDK</strong> is utilized as supply<br />

voltage and the analogue output as control signal. The analogue output may be loaded up to +6,-<strong>10</strong>0mA. The<br />

switched output LS can be loaded with <strong>10</strong>A. If a heavier current is needed, a contactor may be controlled with<br />

this output (se Section 4.3).<br />

•=<br />

dimmer<br />

1 2 3 4 5 6<br />

Fig. 4 - 2<br />

Standard dimmer<br />

11522e V3<br />

starkstrom-elektronik ag<br />

CH-8957 Spreitenbach


<strong>Operating</strong> <strong>Instructions</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong> 17<br />

4.3 Three-phase load with EVGs<br />

With dimmable electronic ballasts (EVGs) a three-phase distribution of the load is possible too. The output can<br />

be loaded with up to +6,-<strong>10</strong>0mA. These additional EVGs may be isolated from the network with a load relay<br />

controlled by the switched output of the <strong>MDK</strong>.<br />

* DISTRIBUTED BETWEEN THE 3 PHAS<strong>ES</strong><br />

Fig. 4 - 3<br />

Fluorescent lamps with dimmable EVGs, load distributed between 3 phases<br />

starkstrom-elektronik ag<br />

CH-8957 Spreitenbach<br />

11522e V3


18 <strong>Operating</strong> <strong>Instructions</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong><br />

5 Standard diagrams (standard applications)<br />

5.1 Several <strong>MDK</strong>s, paralleled control points (external supply)<br />

Any number of <strong>MDK</strong>s operating in parallel for different lighting circuits can be controlled from a central panel and<br />

with distributed secondary operating points. Together with the preset keys it is possible to store 4 genuine<br />

lighting moods.<br />

Each circuit has separate "lighter" and "darker" keys, allowing a different light value to be programmed for each<br />

circuit. All circuits together have a common ON/OFF key, common "lighter" and "darker" keys and up to 4 preset<br />

keys. The common "lighter" and "darker" keys must be connected through diodes.<br />

As digital control unit the <strong>MDK</strong> can be actuated from any number of parallel control points. The integrated power<br />

supply allows acknowledgement diodes up to 40 mA to be paralleled. If more acknowledgement diodes are<br />

needed, an external voltage source must be connected. The <strong>MDK</strong> can switch acknowledgement diodes up to a<br />

maximum current of 700 mA.<br />

1) WITH PARALLELED ACKNOWLEDGEMENT ABOVE 40mA<br />

AN EXTERNAL VOLTAGE SOURCE MUST BE CONNECTED<br />

* PARALLEL CONTROL POSSIBLE<br />

** ACKNOWLEDGMENT PARALLELED UP TO 40 mA<br />

Fig. 5 - 1<br />

2 <strong>MDK</strong>s with common control point<br />

Note:<br />

If the control units happen to be asynchronous, they can be synchronized again by pressing a preset<br />

key.<br />

11522e V3<br />

starkstrom-elektronik ag<br />

CH-8957 Spreitenbach


<strong>Operating</strong> <strong>Instructions</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong> 19<br />

5.2 Daylight-dependent regulation with 2 circuits<br />

Daylight-dependent regulation of 2 lighting circuits is to be provided in a room with different light levels in 2<br />

zones. The lighting on the window side and on the opposite side for instance is to be controlled by separate<br />

circuits. To adjust the setpoint of circuit 1, circuit 2 is switched off with ON/OFF key 2. The light value for circuit 1<br />

is selected with the "lighter" and "darker" keys and stored with ON/OFF key 1. Circuit 2 is adjusted similarly.<br />

* STORAGE BLOCKED<br />

Fig. 5 - 2<br />

Daylight-dependent regulation with 2 circuits<br />

starkstrom-elektronik ag<br />

CH-8957 Spreitenbach<br />

11522e V3


20 <strong>Operating</strong> <strong>Instructions</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong><br />

5.3 Room interconnection in MTS mode<br />

A room is separated by a removable partition. In both parts the lighting is regulated with an <strong>MDK</strong>. When the<br />

partition is removed it must be possible to adjust the entire room lighting from either control point. By pressing<br />

the "COMMON" key, the keys of the control consoles are interconnected, enabling genuine light moods to be<br />

obtained.<br />

Fig. 5 - 3<br />

Interconnection of two combinable rooms<br />

Note:<br />

If the control units happen to be asynchronous, they can be synchronized again by pressing a preset<br />

key.<br />

11522e V3<br />

starkstrom-elektronik ag<br />

CH-8957 Spreitenbach


<strong>Operating</strong> <strong>Instructions</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong> 21<br />

6 Switch-on/off ramps<br />

When switching on and off the control unit is always run up and down a ramp of 500 ms. As a result, any<br />

transformer connected does not get saturated when switching on: there is no current peak.<br />

Fig. 6 - 1<br />

Switch-on and switch-off ramps<br />

7 Switched output<br />

The switched output LS is activated before the switch-on ramp of the analogue output begins. This enables the<br />

electrodes of fluorescent lamps to warm up to the requisite temperature, which makes for longer lamp life.<br />

Depending on the load (EVG or dimmer) being used, different values are taken. The preheat time used with<br />

EVGs can be fixed in the service mode between 0.45 s and 1.5 s (see Section 9.6 "Preheat Time").<br />

Switching on LS:<br />

EVG:<br />

dimmer:<br />

Switch off LS:<br />

all loads:<br />

0.45 or 1.5 s before analogue output<br />

50 ms before analogue output<br />

50ms after analogue output<br />

Fig. 7 - 1<br />

Preheat time<br />

8 LED signalling on control unit<br />

There are three LEDs on the control unit:<br />

•= red LED 230 V supply (power)<br />

•= yellow LED control unit working (run)<br />

•= green LED status display (status)<br />

The red LED indicates the presence of the supply voltage.<br />

hen the yellow LED flashes at 1-second intervals the control unit is working properly.<br />

The green LED lights while the control unit is switched on and is dark when it is switched off. The green LED also<br />

signals overheating inside the <strong>MDK</strong>. This is tripped around 70°C (green LED flashes). The control unit then<br />

automatically reduces the analogue output to 50%. If the temperature continues to rise, the switched output LS is<br />

cut out completely.<br />

1s<br />

Fig. 8-1 Green LED display (status) at overheating<br />

starkstrom-elektronik ag<br />

CH-8957 Spreitenbach<br />

11522e V3


22 <strong>Operating</strong> <strong>Instructions</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong><br />

9 Service mode<br />

By setting DIP switch 3 to position ON the <strong>MDK</strong> is switched over to the service mode.<br />

Switch setting:<br />

1 2 3 4 5 6<br />

•= Service mode<br />

When returning to the operating mode (DIP switch 3 to OFF) the changed parameters are taken over.<br />

9.1 Setting time analogue<br />

"Setting time analogue" denotes the time taken by the control unit in the analogue operating mode to effect a<br />

change from one setpoint to another. This way continuous fading is obtained despite abrupt setpoint change. The<br />

value can be altered in 0.5 s steps between 0.5 s and 20 s.<br />

If the control unit is in the analogue mode, after changing DIP switch 3 the "setting time analogue" parameter is<br />

selected. The light now runs endlessly up and down between minimum and maximum.<br />

t = Setting time analogue<br />

Fig. 9-1 Analogue output with parameter adjustment "setting time analogue"<br />

The back signalling of the ON/OFF key lights. By briefly pressing the ON/OFF key (50ms...300ms) the time is<br />

lengthened by 0.5 seconds. Prolonged pressing of the ON/OFF key (over 300 ms) shortens the time by 0.5<br />

seconds.<br />

Note:<br />

If a variant with only one potentiometer (without ON/OFF key) is selected, an ON/OFF key must be<br />

connected temporarily to the corresponding terminals to adjust the "setting time analogue.<br />

9.2 Setting time<br />

The setting time is the time needed by the control unit in a digital operating mode (ETS or MTS) to change the<br />

setpoint from 0% to <strong>10</strong>0% with the "lighter" key. The value may be altered in 0.5 s steps between 0.5 s and 20 s.<br />

If the control unit is in the ETS or MTS mode, after changing DIP switch 3 the setting time parameter is selected<br />

automatically. The light now runs up and down endlessly between minimum and maximum.<br />

t = Setting time<br />

Fig. 9-2 Analogue output with setting time parameter adjustment<br />

ETS:<br />

MTS:<br />

The back signal of the ON/OFF key lights. By briefly pressing the ON/OFF key (50ms...300ms) the<br />

time is lengthened by 0.5 seconds. By prolonged pressing of the same key (over 300 ms) the time is<br />

shortened by 0.5 seconds.<br />

With the preset 1 key the setting time is selected. The back signal of preset 1 key lights. By operating<br />

the "lighter" and "darker" keys the parameter may be increased or reduced in 0.5s steps.<br />

9.3 Fading time<br />

The fading time is the time taken by the control unit in the MTS mode to change from one preset value to<br />

another. It may be altered in 0.5 s increments between 0.5 and 20 seconds<br />

If the control unit is in the MTS mode, after changing DIP switch 3 the setting time parameter is selected<br />

automatically. The light now runs up and down endlessly between minimum and maximum.<br />

t = Fading time<br />

Fig. 9-3 Analogue output with fading time parameter adjustment<br />

MTS:<br />

The fading time is selected with the preset 2 key. By operating the "lighter" and "darker" keys the<br />

parameter may be increased or reduced in 0.5s increments.<br />

11522e V3<br />

starkstrom-elektronik ag<br />

CH-8957 Spreitenbach


<strong>Operating</strong> <strong>Instructions</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong> 23<br />

9.4 Minimum light value<br />

The minimum light value is the minimum control unit output that can be modulated. It can be varied between 0%<br />

and 50%.<br />

TLR:<br />

After changing the DIP switch 3 the minimum light value parameter is selected automatically. It can be<br />

raised or lowered with the "lighter" and "darker" keys. (Pressing the ON/OFF key changes from the<br />

maximum light value to the minimum light value parameter)<br />

If the minimum light value is greater than 0, the control unit does not cut out although there is<br />

sufficient light.<br />

MTS:<br />

With the preset 3 key the minimum light value is selected. The back signal lights on the preset 3 key.<br />

After selecting the parameter the adjusted value is modulated. It can be increased or reduced with<br />

the "lighter" or "darker" key.<br />

9.5 Maximum light value<br />

The maximum light value is the maximum control unit output that can be modulated. It may be altered between<br />

50% and <strong>10</strong>0%.<br />

TLR:<br />

After changing DIP switch 3 the maximum light value parameter is selected automatically. By pressing<br />

the ON/OFF key the maximum light value parameter is selected. It may be increased or reduced with<br />

the "lighter" or "darker" key.<br />

MTS:<br />

With the preset 4 key the maximum light value is selected. The back signal of the preset 4 key lights.<br />

After selecting the parameter the adjusted value is modulated. It may be increased or reduced with<br />

the "lighter" or "darker" key.<br />

9.6 Preheat time<br />

The "preheat time" is the time by which the switched output of fluorescent lamps is switched on before the ramp<br />

of the dimmed output. It may be changed between 0.45 s and 1.5 s.<br />

MTS:<br />

By prolonged simultaneous pressing of preset keys 1 and 2 (more than 3s) the preheat time is<br />

changed between 0.45s and 1.5s. The change is indicated by the ON/OFF key flashing.<br />

9.7 General reset<br />

If the control unit is in its service mode, a general reset can be obtained by pressing the ON/OFF key at least <strong>10</strong><br />

seconds. After releasing it the acknowledgement flashes, indicating that the general reset has been carried out.<br />

Pressing any key returns the control unit to the normal service mode; parameters may be altered again. The<br />

basic adjustments are:<br />

•= setting time in MTS, ETS 8s<br />

•= fading time 5s<br />

•= minimum light value 0%<br />

•= maximum light value <strong>10</strong>0%<br />

•= preheat time 5s<br />

•= switch-on light maximum light value<br />

•= setting time analogue 500ms<br />

•= daylight control regulating value 5V<br />

•= preset 1 33%<br />

•= preset 2 50%<br />

•= preset 3 67%<br />

•= preset 4 <strong>10</strong>0%<br />

starkstrom-elektronik ag<br />

CH-8957 Spreitenbach<br />

11522e V3


24 <strong>Operating</strong> <strong>Instructions</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong><br />

<strong>10</strong> Installation and wiring<br />

To install the multifunction control unit the supply voltage must be cut off on the input side.<br />

<strong>10</strong>.1 Installing the <strong>MDK</strong><br />

The <strong>MDK</strong> is mounted on a cap rail by placing in onto the rail from below and then engaging it onto the front with<br />

a light pressure.<br />

<br />

<br />

<br />

Fig. <strong>10</strong> - 1 Dimensions of the <strong>MDK</strong><br />

11522e V3<br />

starkstrom-elektronik ag<br />

CH-8957 Spreitenbach


<strong>Operating</strong> <strong>Instructions</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong> 25<br />

<strong>10</strong>.2 Placing in electric's cubicle<br />

A number of <strong>MDK</strong>s may be accommodated in an electric's cubicle. A distance of 8 mm must be assured between<br />

the control units themselves and between the associated cable channels. A distance of 25 mm must be<br />

maintained between groups. The control units may also be installed staggered against a common cable channel.<br />

Each individual <strong>MDK</strong> generates a 15W power loss under nominal load. When installing several control units in<br />

the cubicle therefore, it must be ensured that the temperatures of the individual controllers do not exceed 70øC.<br />

With unventilated cubicles the power loss of all equipment installed must not exceed 270 W/mm3. Accordingly in<br />

a cubicle measuring 1800x800x600 mm about 15 <strong>MDK</strong>s could be installed.<br />

If ventilation is provided in addition, or the control units do not operate under nominal load simultaneously, the<br />

number of control units may be increased.<br />

8mm 8mm 8mm<br />

25mm<br />

Cable channel<br />

8mm<br />

Cable channel<br />

Cable channel<br />

25mm<br />

Cable channel<br />

Cable channel<br />

Cable channel<br />

Fig. <strong>10</strong> - 2 <strong>MDK</strong>s side by side, staggered with common cable channel, or with separate cable channel<br />

25mm<br />

8mm<br />

Cable channel<br />

Fig. <strong>10</strong> - 3 <strong>MDK</strong>s one above the other, vertical<br />

starkstrom-elektronik ag<br />

CH-8957 Spreitenbach<br />

11522e V3


26 <strong>Operating</strong> <strong>Instructions</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong><br />

11 Technical data<br />

Type<br />

<strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong><br />

Mechanical data:<br />

Housing:<br />

Steel sheet with aluminium heat sink<br />

Dimensions: Width: <strong>10</strong>5 mm<br />

Height:<br />

90 mm<br />

Depth: 49 mm (44mm from cap rail)<br />

Weight:<br />

460 grams<br />

Installation:<br />

On DIN cap rails 35 mm<br />

Power connection: Screw terminals 2.5 mm² max.<br />

Load connection: Screw terminals 2.5 mm² max.<br />

<strong>Control</strong> connection: Screw terminals 1.5 mm² max.<br />

Ambient conditions:<br />

Ambient temperature: ta 0-40 °C max. Air throughput at heat sink must be unimpeded.<br />

Storage temperature: 70 °C max.<br />

Air humidity:<br />

<strong>10</strong>%...80% relative air humidity, no condensation<br />

Housing temperature: tc 70 °C max.<br />

IP protection:<br />

IP20<br />

Electrical data:<br />

Supply voltage: 230 V ±<strong>10</strong>%<br />

Supply frequency: 50 Hz (optional 60Hz)<br />

Switching output Switched Triac (solid-state relay)<br />

technology:<br />

Maximum switching <strong>10</strong>A<br />

output load:<br />

Switching output lead: 50 ms with dimmers,<br />

1.5s with EVGs (switchable to 0.45 s)<br />

Switching output lag: 50 ms<br />

Power loss under 15 W<br />

nominal load:<br />

Power loss standing by: 2.5 W<br />

Cooling:<br />

Natural air circulation<br />

No-load voltage:


<strong>Operating</strong> <strong>Instructions</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong> 27<br />

Analogue output:<br />

Output control voltage.<br />

Output current:<br />

CE standards:<br />

EN 60669-2-1<br />

EN 55<strong>10</strong>4<br />

EN 6<strong>10</strong>00-3-2<br />

EN 6<strong>10</strong>00-3-3<br />

EN 55014<br />

0...<strong>10</strong> V<br />

± 6 mA<br />

according to 89/336/EWG and 73/23/EWG<br />

Safety requirements<br />

Disturbance immunity<br />

Attenuation of harmonics<br />

Voltage fluctuations (flicker)<br />

Radio interference<br />

starkstrom-elektronik ag<br />

CH-8957 Spreitenbach<br />

11522e V3


28 <strong>Operating</strong> <strong>Instructions</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong><br />

Fig. 11 - 1 Declaration of Conformity<br />

11522e V3<br />

starkstrom-elektronik ag<br />

CH-8957 Spreitenbach


<strong>Operating</strong> <strong>Instructions</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong> 29<br />

12 Trouble shooting<br />

Fault<br />

Remedy<br />

Lamp does not light up •= Check supply voltage on <strong>MDK</strong> (red LED must light).<br />

•= Check control voltage in analogue operating mode.<br />

•= With key control check connections and key panel.<br />

•= 0V possibly not wired.<br />

Light switched on but cannot be •= Select proper operating mode.<br />

altered with keys<br />

•= Analogue input is under voltage.<br />

Lamp can only be switched on and off •= Analogue output not connected (0V, OUT:0-<strong>10</strong>V).<br />

•= Setting time too long (can be altered in service mode).<br />

•= Analogue output of <strong>MDK</strong> defective. <strong>MDK</strong> must be exchanged.<br />

Lamps cannot be darkened completely •= Select proper operating mode.<br />

•= Minimum light value not 0% (can be altered in service mode).<br />

Light values cannot be stored in MTS •= Select proper operating mode (MTS: storage possible).<br />

mode<br />

Potentiometer control range too •= Adjust minimum and maximum light values properly (service mode).<br />

narrow<br />

Light not switched off in daylight mode •= Minimum light value not 0% (can be altered in service mode).<br />

<strong>Control</strong> unit cannot be regulated up to •= Select proper operating mode.<br />

<strong>10</strong>0%<br />

•= Maximum light value not <strong>10</strong>0% (can be altered in service mode).<br />

Adjusting time too slow or too fast •= Setting time too long or too short (can be altered in service mode).<br />

Light runs ramp in 1-20s cycle •= Select proper operating mode (control unit is in service mode).<br />

Light flashes in <strong>10</strong>-60s cycle (is<br />

reduced or switched off).<br />

•= <strong>Control</strong> unit overloaded. Reduce load, maybe heat sink should be<br />

cooled better.<br />

13 Maintenance and disposal<br />

Maintenance<br />

There are no parts needing maintenance inside the <strong>MDK</strong>. It must be replaced if it is defective. Excessive dust<br />

should be cleaned from the outside of the <strong>MDK</strong> from time to time. (The power electronics inside it set up heat,<br />

which can be dissipated only if there is adequate air circulation. Excessive dust will obstruct the air circulation).<br />

Disposal<br />

If the <strong>MDK</strong> has to be disposed of it must be treated as electrical scrap. There are no parts in it demanding<br />

treatment as special waste.<br />

starkstrom-elektronik ag<br />

CH-8957 Spreitenbach<br />

11522e V3


30 <strong>Operating</strong> <strong>Instructions</strong> <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong><br />

14 Accessories to <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong><br />

The following accessories are suitable for use with the multifunction control unit <strong>MDK</strong>-<strong>ES</strong>-<strong>10</strong>:<br />

Article designation Types Article<br />

Forward phase control unit 3000 VA SDK-AN-13 215.0001.00<br />

Reverse phase control unit 2300 W SDK-AB-<strong>10</strong> 215.0002.00<br />

Forward phase control unit 1400 VA LEK-01-06 213.06.<strong>10</strong>0<br />

Reverse phase control unit 1200 W ADK-01-05 213.05.500<br />

Mixed light sensor (Edizio) LFM 223.20.901<br />

Standard movement detector ECO BWM-ECO-IR 360A 223 20.915<br />

Switching power supply 24 VDC / 1.3A GSN-24-1.3A 444.<strong>10</strong>.202<br />

Switching power supply 24 VDC / 0.6A GSN-24-0.6A 444.<strong>10</strong>.201<br />

setronic ® EVG dimmable for FL T26 36 W EVD-01-36 T/OX 232.<strong>10</strong>.<strong>10</strong>0<br />

setronic ® EVG dimmable for FL T26 58 W / TC-L 55W EVD-01-58 T/OX 232.<strong>10</strong>.<strong>10</strong>1<br />

setronic ® EVG dimmable for FL TC-L/F 36 W EVD-01-36 C/OX 232.<strong>10</strong>.<strong>10</strong>2<br />

Signal converter for EVGs (PD/OCU/LCU) SUK-01-<strong>10</strong>V 221.90.<strong>10</strong>0<br />

<strong>Control</strong> panel with 1 electronic key, EDIZIO white for ON/OFF<br />

function<br />

DPL-H-ETE 312.<strong>10</strong>.014<br />

<strong>Control</strong> panel with 2 electronic keys, EDIZIO white for ON and<br />

OFF function<br />

<strong>Control</strong> panel with 3 electronic keys, EDIZIO white for<br />

ON/OFF/ /<br />

<strong>Control</strong> panel with 4 electronic keys, EDIZIO white for<br />

ON/OFF// /DIA function<br />

<strong>Control</strong> panel with 7 electronic keys, EDIZIO white for<br />

ON/OFF// /DIA-1-4 function<br />

<strong>Control</strong> panel with potentiometer + 1 electronic key, EDIZIO<br />

white for ON/OFF + potentiometer function<br />

DP-2M-ETE 312.11.125<br />

DPL-3K-ETE 312.11.234<br />

DPL-4K-ETE 312.11.244<br />

DPL-7K-ETE 312.11.274<br />

PDP-H-ETE 313.<strong>10</strong>.014<br />

Note:<br />

Further information may be found in Internet under:<br />

www.se-ag.ch<br />

Please address enquiries to:<br />

verkauf@se-ag.ch<br />

11522e V3<br />

starkstrom-elektronik ag<br />

CH-8957 Spreitenbach

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!