15<br />

Technical information manual <strong>UTA</strong>-ECHOS<br />

REF. <strong>UTA</strong>-ECHOS-/<strong>UTA</strong>_ECHOS_2011.DOC<br />

CORRECTION FACTORS<br />

The above indicated bends of the correction factor of the total, sensitive and load loss yield depending on the variation of the air<br />

capacity, refer only to the UTW units, at the following functioning conditions:<br />

• Input air temp.: 26 °C BS 19 °C BU<br />

• Input/output water temp.: 7/12 °C<br />

EXAMPLE:<br />

Let us suppose to want to obtain the total, sensitive cooling yield and load loss of unit UTW 36 with an air capacity of 0.455 m3/s.<br />

From the table on page 4 the following values can be read: total yield: 10.4 kW, sensitive yield 7.6 kW, load loss 18 kPa.<br />

The nominal air capacity: 0.542 m3/s. Requested capacity value expressed in % respect to the nominal capacity<br />

value: (0.455/0.542) x 100 = 84 %. From the above indicated bends the values of the corrective coefficients<br />

corresponding to the new capacity value are obtained:<br />

84% ~> pc tot yield = 0.90; pc sen yield = 0.88<br />

~> pc load loss = 0.82<br />

The new values will be:<br />

total yield = 10.4 x 0.90 = 9.4 kW<br />

sensitive yield = 7.6 x 0.88 = 6.7 kW<br />

load loss = 18 x 0.82 = 14.8 kPa<br />

___________________________________________________________________________________________<br />

<strong>Western</strong> <strong>Airconditioning</strong> B.V. Hoevelaken Tel. (033) 247 78 00 E-mail: sales@western.nl www.western.nl