Actuators and<br />
Leakage Data<br />
Actuators<br />
<strong>Greenheck</strong> has a variety of actuators available for the HTD series. The common models are:<br />
RCS Sure series<br />
• 120V or 230V, 50/60 Hz<br />
• Spring Return, modulating or power<br />
open/close<br />
• NEMA-4, 4X and 7<br />
RCS MAR series<br />
• 24V, 120V, or 230V, 50/60 Hz<br />
• NEMA-4 , 4X and 7<br />
• Modulating or power open/close<br />
Siemens 331-2856<br />
• Pneumatic<br />
• Two position, modulating<br />
• Maximum 25 psi supply<br />
Hytork XL681SRHT<br />
• Pneumatic<br />
• Two position, modulating<br />
• Minimum 80 psi supply<br />
RCS Sure 100<br />
RCS MAR 90<br />
Siemens<br />
331-2856<br />
Hytork XL681SRHT<br />
Proximity Switch<br />
A proximity brand switch is mounted to the damper axle to indicate blade position on the<br />
damper. O-rings are used to seal the switch compartment for hazard, corrosion, and leakage<br />
protection. This proximity switch is NEMA-4, 4X, and 7 rated and has been tested to a<br />
temperature of 250°C for 2 hours of operation.<br />
Leakage Data<br />
Damper leakage (with blades fully closed) varies based on the type of low leakage seals applied. Leakage<br />
testing was conducted in accordance with AMCA Standard 500-D and is expressed as CFM per sq. ft. of<br />
damper face area. All data has been corrected to represent standard air at a density of .075 lb./ft 3 (1.2 kg/m 3 ).<br />
HTD-630<br />
Leakage (English version)<br />
42 in. x 42 in. (1067mm x 1067mm) damper<br />
HTD-630<br />
Leakage (Metric version)<br />
1067mm x 1067mm (42 in. x 42 in.) damper<br />
4