INTRODUCTION<br />

The <strong>Amerex</strong> Model 570/B570 <strong>30</strong> <strong>lb</strong>. (13.6 KG) Stored Pressure <strong>Class</strong> D fire extinguisher contains<br />

Sodium Chloride dry powder which has been tested and approved by Factory Mutual Systems (FM) <strong>for</strong><br />

use on the combustible metals listed in the table below. The heavy duty cylinder, valve assembly and<br />

hose/extension wand has been designed with innovative and dependable fire fighting capabilities as<br />

well as long life and ease of service. The unique soft flow extension applicator allows a continuous,<br />

even distribution of the dry powder agent while the operator stands a safe distance from the burning<br />

material. Easy to read instruction labels provide a quick and convenient guide to proper uses. This<br />

manual should be used as a guide <strong>for</strong> installing, operating and servicing this extinguisher. The best<br />

place to have your extinguisher serviced and recharged is your authorized <strong>Amerex</strong> distributor who has<br />

the professional experience and equipment to do it properly.<br />

USE MODEL 570/B570 EXTINGUISHER ON CLASS D BURNING METALS ONLY<br />

Extinguishing Capacity of Model 570/B570<br />

Approximate Hazard Size<br />

HAZARD AREA QUANTITY<br />

(ft²) (m²) (<strong>lb</strong>s) (kg)<br />

Magnesium Chips 4 .37 6 2.72<br />

Sodium Spill 5 .46 5 2.26<br />

(depth over ½ inch [1.3 cm]) 3 .27 6 2.72<br />

Potassium Spill 5 .46 5 2.26<br />

(depth over ½ inch [1.3 cm]) 3 .27 6 2.72<br />

Sodium Potassium Alloy Spill 3 .27 2 .90<br />

The model 570/B570 <strong>extinguishers</strong> have been manufactured and tested in accordance with the<br />

applicable standards of Factory Mutual to ANSI/UL 711 and ANSI/UL 299. It also complies with<br />

industry standards as presented in the National Fire Protection Association Standard No. 10 "Standard<br />

<strong>for</strong> Portable Fire Extinguishers."<br />

AMEREX CORPORATION DOES NOT SERVICE, MAINTAIN OR RECHARGE FIRE<br />

EXTINGUISHERS. THIS MANUAL IS PUBLISHED AS A GUIDE TO ASSIST<br />

QUALIFIED SERVICE PERSONNEL IN THE INSPECTION, MAINTENANCE AND<br />

RECHARGE OF AMEREX FIRE EXTINGUISHERS ONLY. NO INSTRUCTION<br />

MANUAL CAN ANTICIPATE ALL POSSIBLE MALFUNCTIONS THAT MAY BE<br />

ENCOUNTERED IN THE SERVICE OF FIRE EXTINGUISHERS. DUE TO THE<br />

POSSIBILITY THAT PRIOR SERVICE PERFORMED ON THIS EQUIPMENT MAY<br />

HAVE BEEN IMPROPERLY DONE, IT IS EXTREMELY IMPORTANT THAT ALL<br />

WARNINGS, CAUTIONS AND NOTES IN THIS MANUAL BE CAREFULLY<br />

OBSERVED. FAILURE TO HEED THESE INSTRUCTIONS COULD RESULT IN<br />

SERIOUS INJURY. AMEREX ASSUMES NO LIABILITY FOR SERVICE,<br />

MAINTENANCE OR RECHARGE OF FIRE EXTINGUISHERS BY PUBLISHING THIS<br />

MANUAL.<br />