20.01.2015 Views

Climate control

Climate control

Climate control

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>Climate</strong> <strong>control</strong> – 19" fan racks<br />

19" fan dimensions<br />

V (m 3 /h)<br />

19" blower unit<br />

19" fan unit<br />

For local heat dissipation, the airflow volume required to extract<br />

the (energy loss) heat is calculated.<br />

P v (W)<br />

A41771<br />

Note<br />

The cabinet ventilation is not taken into account here.<br />

The required airflow volume is calculated as follows:<br />

V= (f x P v ) / T<br />

The air constant f = 3.3 mm 3 K/Wh.<br />

T is the difference between the ambient temperature and the<br />

internal temperature.<br />

Example<br />

- Pv = 600 W<br />

- internal temperature = 25 °C<br />

- ambient temperature = 30 °C<br />

1. T = T i – T a = 30 °C – 25 °C = 5 K<br />

2. From P v = 600 W for curve for T =5 K<br />

3. From the point of intersection down to the airflow volume<br />

V = 400 m 3 /h<br />

19" fan racks<br />

For further information ... www.schroff.biz<br />