<strong>Climate</strong> <strong>control</strong> – 19" fan racks<br />
19" fan dimensions<br />
V (m 3 /h)<br />
19" blower unit<br />
19" fan unit<br />
For local heat dissipation, the airflow volume required to extract<br />
the (energy loss) heat is calculated.<br />
P v (W)<br />
A41771<br />
Note<br />
The cabinet ventilation is not taken into account here.<br />
The required airflow volume is calculated as follows:<br />
V= (f x P v ) / T<br />
The air constant f = 3.3 mm 3 K/Wh.<br />
T is the difference between the ambient temperature and the<br />
internal temperature.<br />
Example<br />
- Pv = 600 W<br />
- internal temperature = 25 °C<br />
- ambient temperature = 30 °C<br />
1. T = T i – T a = 30 °C – 25 °C = 5 K<br />
2. From P v = 600 W for curve for T =5 K<br />
3. From the point of intersection down to the airflow volume<br />
V = 400 m 3 /h<br />