CECOROC WALL PANEL BASE<br />
DETAILS WITH<br />
HAT-CHANNELS<br />
SHT. NO.<br />
CRC1<br />
DATE<br />
REV.<br />
JUL. 04 00<br />
WALL PANEL<br />
INSULATION<br />
2 ST FASTENERS<br />
16" O.C.<br />
(IF<br />
REQUIRED)<br />
BASE<br />
CHANNEL<br />
3<br />
" TR FASTENER<br />
4<br />
16" O.C.<br />
HAT-CHANNEL<br />
(#CR109/#CR400)<br />
BASE TRIM<br />
(#CR105/#CR402)<br />
WHEN INSULATION PLACED<br />
BETWEEN PANEL AND GIRT<br />
HAT-CHANNEL IS PLACED<br />
BETWEEN PANEL AND<br />
INSULATION<br />
2 SS BLIND RIVETS<br />
PER BASE TRIM ENDLAP<br />
BASE DETAIL W/O NOTCH<br />
W/ BASE CHANNEL<br />
WALL PANEL<br />
2 ST FASTENERS<br />
16" O.C.<br />
3<br />
" TR FASTENER<br />
4<br />
16" O.C.<br />
BASE<br />
CHANNEL<br />
HAT-CHANNEL<br />
(#CR109/#CR400)<br />
BASE<br />
TRIM<br />
(#CR105/#CR402)<br />
2 SS BLIND RIVETS<br />
PER BASE TRIM ENDLAP<br />
BASE DETAIL W/NOTCH<br />
W/ BASE CHANNEL
CECOROC PANEL<br />
SHT. NO.<br />
CRC1A<br />
DATE<br />
REV.<br />
AUG. 02 00<br />
5<br />
" 8<br />
2 1 " 2<br />
3<br />
" 4<br />
5<br />
" 8<br />
FINISH<br />
THIS SIDE<br />
3<br />
" 4<br />
1'-4"
CECOROC WALL PANEL BASE<br />
DETAILS WITH<br />
HAT-CHANNELS<br />
SHT. NO.<br />
CRC2<br />
DATE<br />
REV.<br />
JUL. 04 00<br />
OPTIONAL<br />
WALL PANEL<br />
2 FASTENERS<br />
16" O.C.<br />
3<br />
" TR FASTENER<br />
4<br />
16" O.C.<br />
HAT-CHANNEL<br />
(#CR109/#CR400)<br />
INSULATION<br />
(IF REQUIRED)<br />
BASE ANGLE<br />
WHEN INSULATION PLACED<br />
BETWEEN PANEL AND GIRT<br />
HAT-CHANNEL IS PLACED<br />
BETWEEN PANEL AND<br />
INSULATION<br />
BASE<br />
TRIM<br />
(#CR105/#CR402)<br />
2 SS BLIND RIVETS<br />
PER BASE TRIM<br />
ENDLAP<br />
BASE DETAIL W/O NOTCH<br />
W/ BASE ANGLE<br />
OPTIONAL<br />
WALL PANEL<br />
2 ST FASTENERS<br />
16" O.C.<br />
INSULATION<br />
(IF<br />
REQUIRED)<br />
3<br />
" TR FASTENER<br />
4<br />
16" O.C.<br />
HAT-CHANNEL<br />
(#CR109/#CR400)<br />
BASE<br />
ANGLE<br />
BASE<br />
TRIM<br />
(#CR105/#CR402)<br />
2 SS BLIND RIVETS<br />
PER BASE TRIM ENDLAP<br />
BASE DETAIL W/NOTCH<br />
W/ BASE ANGLE
CECOROC WALL PANEL BASE<br />
DETAILS WITH<br />
HAT-CHANNEL<br />
SHT. NO.<br />
CRC3<br />
DATE<br />
REV.<br />
JUL. 04 00<br />
WALL PANEL<br />
ST<br />
FASTENERS<br />
16" O.C.<br />
3<br />
"<br />
4<br />
TR FASTENER<br />
16" O.C.<br />
INSULATION<br />
(IF<br />
REQUIRED)<br />
WHEN INSULATION PLACED<br />
BETWEEN PANEL AND GIRT<br />
HAT-CHANNEL IS PLACED<br />
BETWEEN PANEL AND<br />
INSULATION<br />
HAT-CHANNEL<br />
(#CR109/#CR400)<br />
BASE TRIM<br />
(#CR103/#CR401)<br />
2 SS BLIND RIVETS<br />
PER BASE<br />
TRIM ENDLAP<br />
DETAIL AT WALL<br />
OPEN FOR MASONRY<br />
WALL PANEL<br />
2 ST FASTENERS<br />
16" O.C.<br />
3<br />
" TR FASTENER<br />
4<br />
16" O.C.<br />
HAT-CHANNEL<br />
(#CR109/#CR400)<br />
INSULATION<br />
(IF<br />
REQUIRED)<br />
BASE TRIM<br />
(#CR103/#CR401)<br />
2 SS BLIND RIVETS<br />
PER BASE<br />
TRIM ENDLAP<br />
DETAIL AT WALL<br />
OPEN FOR ACCESS
CECOROC<br />
WALL PANEL<br />
WITH PARTIALLY OPEN WALL<br />
SHT. NO.<br />
CRC3A<br />
DATE<br />
REV.<br />
OCT. 03 00<br />
WHEN A WALL IS PARTIALLY OPEN, STRAPPING MUST BE ATTACHED TO THE FACE<br />
OF ALL COLD-FORMED MEMBERS (CHANNEL, ZEE, EAVE STRUT OR GABLE ANGLE)<br />
AT MIDPOINT OF BAY AND 5'-0" EACH SIDE OF COLUMN TO SUPPORT THE WALL<br />
PANELS.<br />
EAVE<br />
STRUT<br />
A<br />
WALL PANEL<br />
STRAPPING<br />
(SEE NOTE)<br />
*STRAPPING<br />
(AT MIDPOINT<br />
OF BAY AND 5'-0" EACH<br />
SIDE OF COLUMN<br />
CHANNEL<br />
A<br />
*1 1 4 " X 0.031 PRE-PUNCHED<br />
HIGH-TENSILE STEEL BANDING<br />
NOTE: IF SAG ANGLES ARE USED<br />
AND THE SAG ANGELS ARE<br />
INSTALLED BEFORE THE PANELS<br />
OPEN WALL CHANNEL<br />
SECTION<br />
A-A<br />
ARE ATTACHED, THE STRAPPING<br />
IS NOR REQUIERD.
CECOROC WALL PANEL<br />
WITH PARTIALLY OPEN WALL<br />
WITH HAT-CHANNEL<br />
SHT. NO.<br />
CRC3B<br />
DATE<br />
REV.<br />
OCT. 03 00<br />
WHEN A WALL IS PARTIALLY OPEN, STRAPPING MUST BE ATTACHED TO THE FACE<br />
OF ALL COLD-FORMED MEMBERS (CHANNEL, ZEE, EAVE STRUT OR GABLE ANGLE)<br />
AT MIDPOINT OF BAY AND 5'-0" EACH SIDE OF COLUMN TO SUPPORT THE WALL<br />
PANELS.<br />
EAVE<br />
STRUT<br />
A<br />
WALL PANEL<br />
STRAPPING<br />
(SEE NOTE)<br />
*STRAPPING (AT<br />
MIDPOINT OF BAY<br />
AND 5'-0"<br />
EACH<br />
SIDE OF COLUMN<br />
HAT-CHANNEL<br />
CHANNEL<br />
A<br />
INSULATION<br />
(IF REQUIRED)<br />
WHEN INSULATION PLACED<br />
*1 1 4 " X O.O31 PRE-PUNCHED<br />
HIGH-TENSILE STEEL BANDING<br />
BETWEEN PANEL AND GIRT<br />
HAT-CHANNEL IS PLACED<br />
BETWEEN PANEL AND<br />
INSULATION<br />
NOTE: IF SAG ANGLES ARE USED<br />
AND THE SAG ANGELS ARE<br />
INSTALLED BEFORE THE PANELS<br />
ARE ATTACHED, THE STRAPPING<br />
IS NOR REQUIERD.<br />
OPEN<br />
WALL CHANNEL<br />
SECTION<br />
A-A
CECOROC WALL PANEL BASE<br />
DETAILS WITH<br />
HAT-CHANNELS<br />
SHT. NO.<br />
CRC4<br />
DATE<br />
REV.<br />
JUL. 04 00<br />
2 FASTENERS<br />
16" O.C.<br />
3<br />
" TR FASTENER<br />
4<br />
16" O.C.<br />
HAT-CHANNEL<br />
(#CR109/#CR400)<br />
INSULATION<br />
(IF<br />
REQUIRED)<br />
WHEN INSULATION PLACED<br />
BETWEEN PANEL AND GIRT<br />
HAT-CHANNEL IS PLACED<br />
BETWEEN PANEL AND<br />
INSULATION<br />
BASE<br />
FLASHING<br />
(#CR107)<br />
6 SS BLIND RIVETS<br />
PER BF25<br />
ENDLAP<br />
DETAIL AT WALL<br />
OPEN FOR MASONRY
CECOROC WALL PANEL CORNER<br />
DETAILS WITH HAT-CHANNELS<br />
SHT. NO.<br />
CRC5<br />
DATE<br />
REV.<br />
JUL. 04 00<br />
WHEN INSULATION<br />
PLACED BETWEEN<br />
PANEL AND GIRT<br />
HAT-CHANNEL<br />
IS<br />
PLACED BETWEEN<br />
PANEL AND<br />
INSULATION<br />
HAT-CHANNEL<br />
(#CR109/#CR400)<br />
3<br />
" TR FASTENER<br />
4<br />
16" O.C.<br />
ENDWALL PANEL<br />
SS BLIND RIVETS<br />
2'-0"<br />
O.C.<br />
PANEL SUPPORT<br />
FLASHING<br />
(ML47)<br />
3<br />
" TR FASTENER<br />
4<br />
CL292<br />
CL206R<br />
GIRT<br />
4 SS BLIND RIVETS<br />
PER CORNER TRIM ENDLAP<br />
2 SS BLIND RIVETS<br />
PER PANEL SUPPORT<br />
FLASHING ENDLAP<br />
CL205<br />
GIRT<br />
CL292<br />
CORNER TRIM<br />
WHEN INSULATION<br />
PLACED BETWEEN<br />
PANEL AND GIRT<br />
HAT-CHANNEL<br />
IS<br />
PLACED BETWEEN<br />
PANEL AND<br />
(#164OC)<br />
SS BLIND<br />
RIVETS<br />
2'-0" O.C.<br />
INSULATION<br />
HAT-CHANNEL<br />
(#CR109/#CR400)<br />
3<br />
" TR FASTENER<br />
4<br />
16" O.C.<br />
SIDEWALL PANEL<br />
2 ST FASTENERS<br />
HAT-CHANNEL<br />
(#CR109/#CR400)<br />
16" O.C.<br />
OUTSIDE CORNER FLUSH<br />
4 SS BLIND RIVETS<br />
GIRT<br />
PER CORNER TRIM ENDLAP<br />
2 SS BLIND RIVETS<br />
CL207<br />
PER PANEL SUPPORT<br />
FLASHING ENDLAP<br />
CL205<br />
GIRT<br />
CL206R<br />
ENDWALL PANEL<br />
SS BLIND RIVETS<br />
2'-0" O.C.<br />
PANEL SUPPORT<br />
FLASHING (ML47)<br />
CL207<br />
3<br />
" TR FASTENER<br />
4<br />
CORNER<br />
TRIM<br />
(#164OC)<br />
SS BLIND RIVETS<br />
2'-0"<br />
O.C.<br />
SIDEWALL PANEL<br />
2 ST FASTENERS<br />
16" O.C.<br />
OUTSIDE CORNER INSET<br />
HAT-CHANNEL<br />
(#CR109/#CR400)
CECOROC WALL PANEL CORNER<br />
DETAILS WITH HAT-CHANNELS<br />
SHT. NO.<br />
CRC6<br />
DATE<br />
REV.<br />
JUL. 04 00<br />
3<br />
" TR FASTENER<br />
4<br />
16" O.C.<br />
4 SS BLIND RIVETS PER<br />
CORNER TRIM ENDLAP<br />
2 SS BLIND RIVETS PER<br />
PANEL SUPPORT FLASHING<br />
ENDLAP<br />
HAT-CHANNEL<br />
(#CR109/#CR400)<br />
ENDWALL PANEL<br />
SS BLIND RIVETS<br />
2'-0" O.C.<br />
PANEL SUPPORT<br />
FLASHING<br />
(ML47)<br />
CORNER TRIM<br />
(#164OC)<br />
SS BLIND RIVETS<br />
2'-0" O.C.<br />
SIDEWALL PANEL<br />
2 ST FASTENERS<br />
HAT-CHANNEL<br />
(#CR109/#CR400)<br />
16" O.C.<br />
OUTSIDE CORNER<br />
BYPASS GIRTS<br />
WHEN INSULATION PLACED<br />
BETWEEN PANEL AND GIRT<br />
HAT-CHANNEL IS PLACED<br />
BETWEEN PANEL AND<br />
INSULATION<br />
HAT-CHANNEL<br />
(#CR109/#CR400)<br />
INSIDE CORNER<br />
TRIM<br />
(#165IC)<br />
PANEL<br />
SS BLIND RIVETS<br />
2'-0"<br />
FLASHING<br />
O.C.<br />
SUPPORT<br />
(ML47)<br />
SS BLIND RIVETS<br />
2'-0"<br />
O.C.<br />
HAT-CHANNEL<br />
(#CR109/#CR400)<br />
3<br />
" TR FASTENER<br />
4<br />
16" O.C.<br />
4 SS BLIND RIVETS PER<br />
CORNER TRIM ENDLAP<br />
2 SS BLIND RIVETS PER<br />
PANEL<br />
2 ST FASTENERS<br />
16" O.C.<br />
ENDLAP<br />
SUPPORT FLASHING<br />
INSIDE<br />
CORNER
DETAIL AT GUTTERED<br />
EAVE<br />
WITH CECOROC WALL PANEL<br />
SHT. NO.<br />
CRC7<br />
DATE<br />
REV.<br />
May 08 00<br />
EAVE<br />
STRUT<br />
NOTE:<br />
SEE DETAILED INSTRUCTIONS<br />
FOR "SEALING LOW EAVES"<br />
EAVE GUTTER<br />
4" ROOF SHEET<br />
OVERHANG<br />
(WITH #CR109)<br />
5 1 2 " ROOF SHEET<br />
OVERHANG<br />
(WITH #CR400)<br />
WALL<br />
PANEL<br />
A A<br />
4"<br />
ROOF SHEET<br />
OVERHANG<br />
3<br />
" TR FASTENERS<br />
4<br />
16" O.C.<br />
EAVE<br />
GUTTER<br />
CECOROC<br />
(WITH<br />
WALL<br />
PANEL<br />
WHEN<br />
1<br />
" 2<br />
SECTION<br />
A-A<br />
EAVE<br />
HAT-CHANNELS)<br />
INSULATION PLACED<br />
BETWEEN PANEL AND GIRT<br />
HAT-CHANNEL IS PLACED<br />
SIDEWALL<br />
FLASHING<br />
TR<br />
BETWEEN PANEL AND INSULATION<br />
FASTENER<br />
(16" O.C.)<br />
HAT-CHANNEL<br />
STRUT<br />
(SF54)<br />
(#CR109/#CR400)<br />
TR<br />
FASTENER<br />
(16" O.C)<br />
CECOROC<br />
WALL<br />
PANEL<br />
(WITHOUT<br />
1<br />
" 2<br />
SECTION<br />
A-A<br />
ST<br />
HAT-CHANNELS)<br />
FASTENER<br />
16" O.C.
CECOROC WALL PANEL EAVE<br />
DETAILS WITH<br />
HAT-CHANNELS<br />
SHT. NO.<br />
CRC8<br />
DATE<br />
REV.<br />
JUL. 04 00<br />
GUTTER<br />
INSULATION<br />
(IF REQUIRED)<br />
2 ST FASTENER<br />
16" O.C.<br />
HAT-CHANNEL<br />
(#CR109/#CR400)<br />
WALL PANEL<br />
EAVE<br />
3<br />
" TR FASTENER<br />
4<br />
16" O.C.<br />
STRUT<br />
DETAIL AT GUTTERED EAVE<br />
WITH CECOROC WALL PANEL<br />
WHEN INSULATION PLACED<br />
BETWEEN PANEL AND GIRT<br />
HAT-CHANNEL IS PLACED<br />
BETWEEN PANEL AND<br />
INSULATION<br />
EAVE<br />
TRIM<br />
INSULATION<br />
(IF<br />
REQUIRED)<br />
HAT-CHANNEL<br />
(#CR109/#CR400)<br />
2 ST FASTENER<br />
16" O.C.<br />
3<br />
" TR FASTENER<br />
4<br />
16" O.C.<br />
WALL PANEL<br />
EAVE STRUT<br />
DETAIL AT PLAIN EAVE<br />
WITH CECOROC WALL PANEL
CECOROC WALL PANEL<br />
FALSE<br />
GUTTER DETAIL WITH HAT-CHANNELS<br />
SHT. NO.<br />
CRC9<br />
DATE<br />
REV.<br />
JUL. 04 00<br />
WHEN INSULATION PLACED<br />
BETWEEN PANEL AND GIRT<br />
HAT-CHANNEL IS PLACED<br />
BETWEEN PANEL AND<br />
INSULATION<br />
FALSE GUTTER<br />
HAT-CHANNEL<br />
(#CR109/#CR400)<br />
WALL PANEL<br />
INSULATION<br />
(IF<br />
REQUIRED)<br />
2 ST FASTENER<br />
16" O.C.<br />
3<br />
" TR FASTENER<br />
4<br />
16" O.C.<br />
EAVE STRUT<br />
DETAIL AT EAVE WITH FALSE GUTTER<br />
WITH CECOROC WALL PANEL
RAKE DETAIL WITH CECOROC<br />
WALL PANELS<br />
WITH HAT-CHANNELS<br />
SHT. NO.<br />
CRC10<br />
DATE<br />
REV.<br />
JUL. 04 00<br />
A<br />
RAKE<br />
TRIM<br />
ENDWALL<br />
PANEL<br />
A<br />
GABLE<br />
ANGLE<br />
HAT-CHANNEL<br />
(#CR109/#CR400)<br />
RAKE TRIM<br />
EXPANSION<br />
FLASHING<br />
NOTE:<br />
SEE DETAILED INSTRUCTIONS<br />
FOR "SEALING RAKE"<br />
5"<br />
NOTE:<br />
FOR INSTRUCTIONS<br />
ANGLE INSTALLATION<br />
OR<br />
WITHOUT THERMAL<br />
BLOCKS) AND<br />
ADAPTER<br />
FLASHING SEE "SEALING<br />
RAKE" DETAILS<br />
ON RAKE<br />
(WITH<br />
2 ST FASTENER<br />
16" O.C.<br />
GABLE ANGLE<br />
HAT-CHANNEL<br />
(#CR109/#CR400)<br />
RAKE TRIM<br />
PURLIN<br />
INSULATION<br />
3<br />
" TR FASTENER<br />
4<br />
16" O.C.<br />
(IF REQUIRED)<br />
CECOROC WALL PANEL<br />
SECTION<br />
A-A<br />
SHOWN WITHOUT THERMAL BLOCK<br />
WHEN INSULATION PLACED BETWEEN<br />
PANEL AND GIRT HAT-CHANNEL IS<br />
PLACED BETWEEN PANEL AND INSULATION
CECOROC WALL PANEL RAKE<br />
DETAIL<br />
WITH HAT-CHANNELS<br />
SHT. NO.<br />
CRC11<br />
DATE<br />
REV.<br />
JUL. 04 00<br />
HAT-CHANNEL<br />
(#CR109/<br />
#CR400)<br />
2 ST FASTENER<br />
16" O.C.<br />
RAKE TRIM<br />
GABLE<br />
ANGLE<br />
3<br />
" TR FASTENER<br />
4<br />
16" O.C.<br />
ML14<br />
WALL PANEL<br />
WHEN INSULATION PLACED<br />
BETWEEN PANEL AND GIRT<br />
HAT-CHANNEL IS PLACED<br />
BETWEEN PANEL AND INSULATION<br />
INSULATION<br />
(IF REQUIRED)<br />
PURLIN<br />
DETAIL AT RAKE<br />
WITH CECOROC WALL PANEL
CECOROC WALL PANEL PLAZA<br />
ENDWALL DETAIL<br />
WITH HAT-CHANNELS<br />
SHT. NO.<br />
CRC11A<br />
DATE<br />
REV.<br />
JUL. 04 00<br />
5 SS BLIND RIVETS<br />
PER TRIM FLASHING ENDLAP<br />
STITCH<br />
FASTENERS<br />
(2 PER FOOT)<br />
TRIM<br />
FLASHING<br />
(#CR143)<br />
BASE<br />
FLASHING<br />
WALL PANEL<br />
HAT-CHANNEL<br />
(#CR109/#CR400)<br />
3<br />
" TR FASTENER<br />
4<br />
16" O.C.<br />
GABLE ANGLE<br />
2 ST FASTENER<br />
16" O.C.<br />
INSULATION<br />
PURLIN<br />
(IF REQUIRED)<br />
WHEN INSULATION PLACED<br />
BETWEEN PANEL AND GIRT<br />
HAT-CHANNEL IS PLACED<br />
BETWEEN PANEL AND INSULATION<br />
DETAIL AT PLAZA ENDWALL<br />
WITH CECOROC WALL PANEL
LOW SIDEWALL WITH PLAZA ENDWALL<br />
WITH CECOROC WALL PANEL<br />
SHT. NO.<br />
CRC11B<br />
DATE<br />
REV.<br />
JUL. 04 00<br />
BASE<br />
FLASHING<br />
A<br />
TRIM<br />
(#CR143)<br />
FLASHING<br />
A<br />
CECOROC<br />
WALL<br />
PANEL<br />
GUTTER<br />
J-TRIM<br />
FLASHING<br />
(#200CH,<br />
#403CH<br />
OR #250CH)<br />
CORNER<br />
FLASHING<br />
GUTTER END FLASHING<br />
DETAIL AT LOW SIDEWALL<br />
PLAZA<br />
ENDWALL<br />
WITH<br />
CECOROC<br />
PANEL<br />
BASE<br />
FLASHING<br />
CORNER<br />
(#164OC)<br />
TRIM<br />
TRIM<br />
TO BOTTOM<br />
OF ROOF PANELS<br />
J-TRIM (#200CH,<br />
#403CH OR #250CH)<br />
SECTION<br />
A-A
DETAIL AT CECOROC<br />
WALL PANEL SPLICE WITH HAT-CHANNEL<br />
SHT. NO.<br />
CRC12<br />
DATE<br />
REV.<br />
JUL. 04 00<br />
WALL PANEL<br />
DETAIL<br />
"A"<br />
ST<br />
FASTENER<br />
16" O.C.<br />
SUPPORT<br />
PANEL<br />
SPLICE<br />
(#CR209/#CR409)<br />
GIRT<br />
3<br />
" TR FASTENER<br />
4<br />
16" O.C. INSULATION<br />
(IF REQUIRED)<br />
SECTION THRU WALL<br />
PANEL<br />
ENDLAP<br />
WHEN INSULATION PLACED<br />
BETWEEN PANEL AND GIRT<br />
PANEL SPLICE IS PLACED<br />
BETWEEN PANEL AND<br />
INSULATION<br />
STARTING<br />
SIDE "A" SIDE "B" SIDE "A"<br />
SIDE "B"<br />
SHEETING<br />
DIRECTION<br />
LAPPING<br />
"B"<br />
SIDE B<br />
RIGHT SIDE<br />
OF PANEL<br />
"B"<br />
DETAIL "A"<br />
SECTION<br />
B-B
DETAILS AT FRAMED<br />
OPENING WITH HAT-CHANNELS<br />
SHT. NO.<br />
CRC13<br />
DATE<br />
REV.<br />
JUL. 04 00<br />
WALL PANEL<br />
2 ST FASTENER<br />
16" O.C.<br />
HAT-CHANNEL<br />
(#CR109/#CR400)<br />
INSULATION<br />
(IF REQUIRED)<br />
3<br />
" TR FASTENER<br />
4<br />
16" O.C.<br />
WINDOW & DOOR CAP<br />
(#CR180/#CR404)<br />
3 SS BLIND RIVETS PER<br />
WINDOW AND DOOR CAP ENDLAP<br />
NOTE: IF SAG ANGLES ARE<br />
USED AND THE SAG ANGLES<br />
HEADER<br />
ARE INSTALLED BEFORE THE<br />
PANELS ARE ATTACHED, THE<br />
STRAPPING IS NOT REQUIRED.<br />
SECTION THRU FRAMED<br />
OPENING HEADER<br />
WINDOW/DOOR J-TRIM<br />
(#200CH)<br />
SILL<br />
SS BLIND RIVETS 2'-0"<br />
ON CENTER AT<br />
WINDOW/DOOR J-TRIM<br />
HAT-CHANNEL<br />
(#CR109/#CR400)<br />
WALL PANEL<br />
INSULATION<br />
(IF<br />
REQUIRED)<br />
NOTE: IF SAG ANGLES ARE<br />
USED AND THE SAG ANGLES<br />
ARE INSTALLED BEFORE THE<br />
PANELS ARE ATTACHED, THE<br />
STRAPPING IS NOT REQUIRED.<br />
SECTION THRU FRAMED<br />
OPENING<br />
SILL
DETAILS AT FRAMED<br />
OPENING WITH HAT-CHANNELS<br />
SHT. NO.<br />
CRC14<br />
DATE<br />
REV.<br />
JUL. 04 00<br />
GIRT<br />
JAMB<br />
2 ST FASTENER<br />
16" O.C.<br />
3<br />
" TR FASTENER<br />
4<br />
16" O.C.<br />
HAT-CHANNEL<br />
(#CR109/#CR400)<br />
WALL PANEL<br />
SS BLIND RIVETS<br />
2'-0" O.C.<br />
PANEL SUPPORT FLASHING<br />
(ML47)<br />
WINDOW/DOOR J-TRIM<br />
(#200CH/#403CH)<br />
SECTION THRU FRAMED<br />
OPENING<br />
JAMB<br />
WHEN INSULATION PLACED<br />
BETWEEN PANEL AND GIRT<br />
HAT-CHANNEL IS PLACED<br />
BETWEEN PANEL AND INSULATION<br />
GIRT<br />
JAMB<br />
2 ST FASTENER<br />
16" O.C.<br />
3<br />
"<br />
4<br />
TR FASTENER<br />
16" O.C.<br />
9 SS BLIND RIVETS<br />
PER JAMB TRIM ENDLAP<br />
PANEL SUPPORT FLASHING<br />
(ML47)<br />
HAT-CHANNEL<br />
(#CR109/#CR400)<br />
WALL<br />
PANEL<br />
JAMB TRIM<br />
(#CR100)<br />
SS BLIND RIVETS<br />
2'-0" O.C.<br />
SECTION THRU FRAMED<br />
OPENING JAMB
CECOROC WALL PANEL BASE<br />
DETAILS (WITHOUT HAT-CHANNELS)<br />
SHT. NO.<br />
CRC15<br />
DATE<br />
REV.<br />
SEP. 01 00<br />
WALL PANEL<br />
ST<br />
FASTENER<br />
16" O.C.<br />
BASE<br />
CHANNEL<br />
BASE<br />
TRIM<br />
(#CR106)<br />
2 SS BLIND RIVETS PER<br />
BASE TRIM ENDLAP<br />
BASE DETAIL W/O NOTCH<br />
W/ BASE CHANNEL<br />
WALL PANEL<br />
ST<br />
FASTENER<br />
16" O.C.<br />
BASE CHANNEL<br />
2 SS BLIND RIVETS PER<br />
BASE TRIM ENDLAP<br />
BASE TRIM<br />
(#CR105)<br />
BASE DETAIL W/NOTCH<br />
W/ BASE CHANNEL
CECOROC WALL PANEL BASE<br />
DETAILS (WITHOUT HAT-CHANNELS)<br />
SHT. NO.<br />
CRC16<br />
DATE<br />
REV.<br />
SEP. 01 00<br />
OPTIONAL<br />
WALL PANEL<br />
ST FASTENER<br />
16" O.C.<br />
BASE<br />
ANGLE<br />
BASE TRIM<br />
(#CR106)<br />
2 SS BLIND RIVETS PER<br />
BASE TRIM ENDLAP<br />
BASE DETAIL W/O NOTCH<br />
W/ BASE ANGLE<br />
OPTIONAL<br />
WALL PANEL<br />
ST FASTENER<br />
16" O.C.<br />
BASE TRIM<br />
(#CR105)<br />
BASE<br />
ANGLE<br />
2 SS BLIND RIVETS PER<br />
BASE TRIM ENDLAP<br />
BASE DETAIL W/ NOTCH<br />
W/ BASE ANGLE
CECOROC WALL PANEL BASE<br />
DETAILS (WITHOUT HAT-CHANNELS)<br />
SHT. NO.<br />
CRC17<br />
DATE<br />
REV.<br />
SEP. 01 00<br />
WALL PANEL<br />
ST FASTENER<br />
16" O.C.<br />
BASE TRIM<br />
(#CR104)<br />
2 SS BLIND RIVETS PER<br />
BASE TRIM ENDLAP<br />
DETAIL AT WALL<br />
OPEN FOR MASONRY<br />
WALL PANEL<br />
ST FASTENER<br />
16" O.C.<br />
BASE TRIM<br />
(#CR104)<br />
2 SS BLIND RIVETS PER<br />
BASE TRIM ENDLAP<br />
DETAIL AT WALL<br />
OPEN FOR ACCESS
CECOROC WALL PANEL BASE<br />
DETAIL (WITHOUT HAT-CHANNELS)<br />
SHT. NO.<br />
CRC18<br />
DATE<br />
REV.<br />
SEP. 01 00<br />
WALL PANEL<br />
ST FASTENER<br />
16" O.C.<br />
BASE FLASHING<br />
(#CR107)<br />
6 SS BLIND RIVETS<br />
PER BASE FLASHING<br />
ENDLAP<br />
DETAIL AT WALL<br />
OPEN FOR<br />
MASONRY
CECOROC WALL PANEL<br />
CORNER DETAILS<br />
SHT. NO.<br />
CRC19<br />
DATE<br />
REV.<br />
FEB. 03 00<br />
CL292<br />
GIRT<br />
4 SS BLIND RIVETS PER<br />
CORNER TRIM ENDLAP<br />
2 SS BLIND RIVETS PER<br />
PANEL SUPPORT FLASHING<br />
ENDLAP<br />
ENDWALL PANEL<br />
CL206R<br />
CL205<br />
GIRT<br />
ST FASTENER<br />
SS BLIND RIVETS<br />
2'-0"<br />
O.C.<br />
CL292<br />
PANEL SUPPORT<br />
FLASHING<br />
(ML47)<br />
CORNER TRIM<br />
(#164OC)<br />
SS BLIND RIVETS<br />
2'-0" O.C.<br />
SIDEWALL<br />
PANEL<br />
4" X 2 5 8 " X .058<br />
ANGLE (W/ ST FASTENER)<br />
OUTSIDE CORNER FLUSH<br />
2 ST FASTENER<br />
16" O.C.<br />
4 SS BLIND RIVETS PER<br />
GIRT<br />
CORNER TRIM<br />
ENDLAP<br />
ST<br />
FASTENER<br />
16" O.C.<br />
CL207<br />
2 SS BLIND RIVETS PER<br />
PANEL SUPPORT FLASHING<br />
ENDLAP<br />
ENDWALL PANEL<br />
CL206R<br />
CL205<br />
GIRT<br />
ST<br />
FASTENER<br />
SS BLIND RIVETS<br />
2'-0" O.C.<br />
CL207<br />
PANEL SUPPORT<br />
FLASHING (ML47)<br />
CORNER TRIM<br />
(#164OC)<br />
SS BLIND RIVETS<br />
2'-0" O.C.<br />
SIDEWALL PANEL 2 ST FASTENER<br />
16" O.C.<br />
4" X 2 5 8 " X .058<br />
ANGLE (W/ ST FASTENER)<br />
OUTSIDE CORNER INSET
CECOROC WALL PANEL CORNER<br />
DETAILS (WITHOUT HAT-CHANNELS)<br />
SHT. NO.<br />
CRC20<br />
DATE<br />
REV.<br />
FEB. 03 00<br />
ST FASTENER<br />
16" O.C.<br />
4 SS BLIND RIVETS PER<br />
CORNER TRIM<br />
ENDLAP<br />
ENDWALL PANEL<br />
SS BLIND RIVETS<br />
2'-0"<br />
O.C.<br />
PANEL SUPPORT<br />
FLASHING (ML47)<br />
CORNER TRIM<br />
(#164OC)<br />
SS BLIND RIVETS<br />
2'-0" O.C.<br />
SIDEWALL<br />
OUTSIDE CORNER<br />
BYPASS GIRTS<br />
PANEL<br />
ST<br />
FASTENER<br />
16" O.C.<br />
SS BLIND RIVETS<br />
2'-0" O.C.<br />
SS BLIND RIVETS<br />
2'-0" O.C.<br />
INSIDE CORNER TRIM<br />
(#165IC)<br />
PANEL SUPPORT<br />
FLASHING (ML47)<br />
4 SS BLIND RIVETS PER<br />
CORNER TRIM ENDLAP<br />
INSIDE<br />
CORNER
CECOROC WALL PANEL EAVE<br />
DETAILS (WITHOUT HAT-CHANNELS)<br />
SHT. NO.<br />
CRC21<br />
DATE<br />
REV.<br />
SEP. 01 00<br />
GUTTER<br />
ST<br />
FASTENER<br />
16" O.C.<br />
WALL<br />
PANEL<br />
EAVE<br />
STRUT<br />
DETAIL AT GUTTERED EAVE<br />
WITH CECOROC WALL PANEL<br />
EAVE<br />
TRIM<br />
ST<br />
FASTENER<br />
16" O.C.<br />
WALL<br />
PANEL<br />
EAVE<br />
STRUT<br />
DETAIL AT PLAIN EAVE<br />
WITH CECOROC WALL PANEL
CECOROC WALL PANEL FALSE GUTTER<br />
DETAIL (WITHOUT HAT-CHANNELS)<br />
SHT. NO.<br />
CRC22<br />
DATE<br />
REV.<br />
SEP. 01 00<br />
FALSE GUTTER<br />
ST<br />
FASTENER<br />
16" O.C.<br />
WALL PANEL<br />
EAVE STRUT<br />
DETAIL AT EAVE WITH FALSE GUTTER<br />
WITH CECOROC WALL PANEL
RAKE DETAIL WITH CECOROC<br />
PANEL WITHOUT HAT-CHANNEL<br />
WALL<br />
SHT. NO.<br />
CRC23<br />
DATE<br />
REV.<br />
SEP. 01 00<br />
A A<br />
RAKE<br />
TRIM<br />
ENDWALL<br />
PANEL<br />
GABLE ANGLE<br />
RAKE TRIM<br />
EXPANSION<br />
FLASHING<br />
NOTE:<br />
SEE DETAILED INSTRUCTIONS<br />
FOR "SEALING RAKE"<br />
5"<br />
NOTE:<br />
FOR INSTRUCTIONS ON RAKE<br />
ANGLE INSTALLATION (WITH<br />
OR WITHOUT THERMAL<br />
BLOCKS) AND ADAPTER<br />
FLASHING SEE "SEALING<br />
RAKE" DETAILS<br />
GABLE ANGLE<br />
RAKE<br />
TRIM<br />
PURLIN<br />
ST<br />
FASTENER<br />
16" O.C.<br />
CECOROC WALL PANEL<br />
SECTION A-A<br />
SHOWN WITHOUT THERMAL BLOCK
CECOROC WALL PANEL RAKE<br />
DETAIL WITHOUT HAT-CHANNEL<br />
SHT. NO.<br />
CRC24<br />
DATE<br />
REV.<br />
FEB. 02 00<br />
RAKE TRIM<br />
GABLE ANGLE<br />
ST<br />
FASTENER<br />
16" O.C.<br />
ML14<br />
3<br />
" TR FASTENER<br />
4<br />
16" O.C.<br />
WALL PANEL<br />
PURLIN<br />
DETAIL AT<br />
RAKE<br />
WITH CECOROC WALL PANEL
CECOROC WALL PANEL PLAZA ENDWALL<br />
DETAIL WITHOUT HAT-CHANNEL<br />
SHT. NO.<br />
CRC24A<br />
DATE<br />
REV.<br />
FEB. 02 00<br />
5 SS BLIND RIVETS PER<br />
TRIM FLASHING ENDLAP<br />
STITCH<br />
FASTENERS<br />
(2 PER FOOT)<br />
TRIM FLASHING<br />
(#CR143)<br />
BASE<br />
FLASHING<br />
WALL PANEL<br />
ST<br />
FASTENER<br />
16" O.C.<br />
GABLE<br />
ANGLE<br />
PURLIN<br />
DETAIL AT PLAZA ENDWALL<br />
WITH CECOROC WALL PANEL
DETAIL AT CECOROC WALL PANEL<br />
SPLICE<br />
WITHOUT HAT-CHANNEL<br />
SHT. NO.<br />
CRC25<br />
DATE<br />
REV.<br />
SEP. 01 00<br />
WALL PANEL<br />
DETAIL<br />
"A"<br />
ST FASTENER<br />
16" O.C.<br />
ST FASTENER<br />
16" O.C.<br />
ST FASTENER<br />
12" O.C.<br />
GIRT<br />
4" X 2 5 " X .058<br />
8<br />
ANGLE<br />
SECTION THRU WALL<br />
PANEL ENDLAP<br />
STARTING<br />
SIDE "A" SIDE "B" SIDE "A"<br />
SIDE "B"<br />
SHEETING<br />
DIRECTION<br />
LAPPING<br />
"B"<br />
SIDE B (RIGHT<br />
SIDE OF PANEL)<br />
"B"<br />
DETAIL "A"<br />
SECTION<br />
B-B
DETAILS AT FRAMED OPENING<br />
WITHOUT HAT-CHANNEL<br />
SHT. NO.<br />
CRC26<br />
DATE<br />
REV.<br />
JUL. 04 00<br />
WALL PANEL<br />
ST FASTENER<br />
16" O.C.<br />
WINDOW & DOOR CAP<br />
(#CR180-2)<br />
HEADER<br />
3 SS BLIND RIVETS PER<br />
WINDOW AND DOOR CAP ENDLAP<br />
SECTION THRU FRAMED<br />
OPENING<br />
HEADER<br />
WINDOW/DOOR J-TRIM<br />
(#250CH)<br />
SILL<br />
SS BLIND RIVETS 2'-0"<br />
ON CENTER AT<br />
WINDOW/DOOR J-TRIM<br />
ST<br />
FASTENER<br />
16" O.C.<br />
WALL PANEL<br />
SECTION THRU FRAMED<br />
OPENING<br />
SILL
DETAILS AT FRAMED OPENINGS<br />
WITHOUT HAT-CHANNEL<br />
SHT. NO.<br />
CRC27<br />
DATE<br />
REV.<br />
FEB. 03 00<br />
GIRT<br />
JAMB<br />
2 SS BLIND RIVETS PER<br />
WINDOW/DOOR J-TRIM ENDLAP<br />
WINDOW/DOOR<br />
(#250CH)<br />
J-TRIM<br />
WALL PANEL<br />
PANEL SUPPORT FLASHING<br />
(ML47)<br />
SS BLIND RIVETS<br />
2'-0" O.C.<br />
SECTION THRU FRAMED<br />
OPENING<br />
JAMB<br />
GIRT<br />
JAMB<br />
9 SS BLIND RIVETS PER<br />
JAMB TRIM ENDLAP<br />
JAMB TRIM<br />
(#CR100)<br />
WALL PANEL<br />
PANEL SUPPORT FLASHING<br />
(ML47)<br />
SS BLIND RIVETS<br />
2'-0" O.C.<br />
SECTION THRU FRAMED<br />
OPENING JAMB