1 / 16 - 1 / 8 DIN INDICATOR<br />

CONCISE PRODUCT MANUAL (59344-3)<br />

CAUTION: Installation should be only performed by<br />

technically competent personnel. Local Regulations<br />

regard<strong>in</strong>g electrical <strong>in</strong>stallation & safety must be observed.<br />

1. INSTALLATION<br />

The two <strong>in</strong>dica<strong>to</strong>rs covered by this <strong>manual</strong> have different DIN case sizes (refer <strong>to</strong><br />

section 9). Some <strong>in</strong>stallation details vary between <strong>the</strong>se models. These differences<br />

have been clearly shown.<br />

Note: The functions described <strong>in</strong> sections 2 <strong>to</strong> 8 are common <strong>to</strong> both models.<br />

Install<strong>in</strong>g Option Modules<br />

1 / 16 D<strong>in</strong> Size Instruments<br />

CPU PCB<br />

Option Module 1<br />

Option Module 2<br />

CPU PCB<br />

Option Module B<br />

(not used on<br />

Indica<strong>to</strong>r models)<br />

Option Module 2<br />

Option Module 1<br />

1 / 8 D<strong>in</strong> Size Instruments<br />

Mount<strong>in</strong>g Struts<br />

Option Module A<br />

Option Module 3<br />

PSU PCB<br />

Mount<strong>in</strong>g Struts<br />

Option Module A<br />

Option Module 3<br />

PSU PCB<br />

To access modules 1 or A, first detach <strong>the</strong> PSU and CPU boards from <strong>the</strong> front by<br />

lift<strong>in</strong>g first <strong>the</strong> upper, and <strong>the</strong>n lower mount<strong>in</strong>g struts. Gently separate <strong>the</strong> boards.<br />

a. Plug <strong>the</strong> required option modules <strong>in</strong><strong>to</strong> <strong>the</strong> correct connec<strong>to</strong>rs, as shown below.<br />

b. Locate <strong>the</strong> module <strong>to</strong>ngues <strong>in</strong> <strong>the</strong> correspond<strong>in</strong>g slot on <strong>the</strong> opposite board.<br />

c. Hold <strong>the</strong> ma<strong>in</strong> boards <strong>to</strong>ge<strong>the</strong>r while relocat<strong>in</strong>g back on <strong>the</strong> mount<strong>in</strong>g struts.<br />

d. Replace <strong>the</strong> <strong>in</strong>strument by align<strong>in</strong>g <strong>the</strong> CPU and PSU boards with <strong>the</strong>ir guides<br />

<strong>in</strong> <strong>the</strong> hous<strong>in</strong>g, <strong>the</strong>n slowly push <strong>the</strong> <strong>in</strong>strument back <strong>in</strong><strong>to</strong> position.<br />

Note: Option modules are au<strong>to</strong>matically detected at power up.<br />

Option Module Connec<strong>to</strong>rs<br />

1 / 16 D<strong>in</strong> Size Instruments<br />

Option Slot 1<br />

Connec<strong>to</strong>rs<br />

PL7 & PL8<br />

Option Slot 2<br />

Connec<strong>to</strong>r<br />

PL4A<br />

Option Slot B<br />

(not used on<br />

Indica<strong>to</strong>r<br />

models)<br />

Option Slot 2<br />

Connec<strong>to</strong>r<br />

PL4A<br />

Option Slot 1<br />

Connec<strong>to</strong>rs<br />

PL7 & PL8<br />

1 / 8 D<strong>in</strong> Size Instruments<br />

Option Slot A<br />

Connec<strong>to</strong>rs<br />

PL5 & PL6<br />

Option Slot 3<br />

Connec<strong>to</strong>r<br />

PL4B<br />

Option Slot A<br />

Connec<strong>to</strong>rs<br />

PL5 & PL6<br />

Option Slot 3<br />

Connec<strong>to</strong>r<br />

PL4B<br />

Panel-Mount<strong>in</strong>g<br />

The mount<strong>in</strong>g panel must be rigid, and may be up <strong>to</strong><br />

6.0mm (0.25<strong>in</strong>ch) thick. Cut-out sizes are:<br />

Cut-Out Dim A Cut-Out Dim B<br />

1 / 16 D<strong>in</strong> = 45mm 1 / 16 & 1 / 8 D<strong>in</strong> = 45mm<br />

1 / 8 D<strong>in</strong> = 92mm<br />

For n multiple <strong>in</strong>struments mounted side-by-side, cut-out<br />

A is 48n-4mm ( 1 / 16 D<strong>in</strong>) or 96n-4mm ( 1 / 8 D<strong>in</strong>)<br />

Mount<strong>in</strong>g Panel<br />

Instrument<br />

Hous<strong>in</strong>g<br />

Ratchets<br />

Gasket<br />

A<br />

Tolerance +0.5, -0.0mm<br />

Slide mount<strong>in</strong>g clamp<br />

over <strong>the</strong> <strong>in</strong>strument<br />

hous<strong>in</strong>g <strong>to</strong>wards rear face<br />

of mount<strong>in</strong>g panel until<br />

<strong>the</strong> <strong>to</strong>ngues engage <strong>in</strong><br />

ratchets and <strong>in</strong>strument is<br />

clamped <strong>in</strong> position.<br />

Hold <strong>in</strong>strument firmly <strong>in</strong><br />

position (apply pressure<br />

<strong>to</strong> bezel only)<br />

CAUTION: Do not remove <strong>the</strong> panel gasket; it is a seal aga<strong>in</strong>st dust and<br />

moisture.<br />

Rear Term<strong>in</strong>al Wir<strong>in</strong>g<br />

USE COPPER CONDUCTORS (EXCEPT FOR T/C INPUT)<br />

S<strong>in</strong>gle Strand wire gauge: Max 1.2mm (18SWG)<br />

1 / 16 D<strong>in</strong> Size Instruments<br />

1 / 8 D<strong>in</strong> Size Instruments<br />

These diagrams show all possible option comb<strong>in</strong>ations. The actual<br />

connections required depend on <strong>the</strong> model and options fitted.<br />

CAUTION: Check <strong>in</strong><strong>format</strong>ion label on hous<strong>in</strong>g for correct operat<strong>in</strong>g<br />

voltage before connect<strong>in</strong>g supply <strong>to</strong> Power Input<br />

Fuse: 100 – 240V ac – 1amp anti-surge<br />

24/48V ac/dc – 315mA anti-surge<br />

Note: At first power-up <strong>the</strong> message is displayed, as described <strong>in</strong><br />

section 5 of this <strong>manual</strong>. Access <strong>to</strong> o<strong>the</strong>r menus is denied until configuration<br />

mode is completed<br />

B<br />

2. SELECT MODE<br />

Select mode is used <strong>to</strong> access <strong>the</strong> configuration and operation menu functions.<br />

It can be accessed at any time by hold<strong>in</strong>g down and press<strong>in</strong>g . The <br />

legend is shown for 1 second, followed by <strong>the</strong> legend for <strong>the</strong> current mode.<br />

Press or <strong>to</strong> choose <strong>the</strong> required mode, <strong>the</strong>n press <strong>to</strong> enter.<br />

An unlock code is required <strong>to</strong> prevent unauthorised entry <strong>to</strong> Configuration, & Setup<br />

modes. Press or <strong>to</strong> enter <strong>the</strong> unlock code, <strong>the</strong>n press <strong>to</strong> proceed.<br />

Mode Legend Set<br />

Description Default Units<br />

for 1 sec Value<br />

Unlock Display<br />

followed<br />

by<br />

Codes ( 1 /8 D<strong>in</strong><br />

Only )<br />

Opera<strong>to</strong>r Normal operation None<br />

Set Up<br />

Tailor sett<strong>in</strong>gs for application <br />

<br />

<br />

Configuration<br />

Configure <strong>in</strong>strument for use <br />

Product Info<br />

Instrument <strong>in</strong><strong>format</strong>ion None<br />

Note: Au<strong>to</strong>matic return <strong>to</strong> Opera<strong>to</strong>r Mode after 2 m<strong>in</strong>utes without key activity.<br />

3. CONFIGURATION MODE<br />

First select Configuration mode from Select mode (refer <strong>to</strong> section 2).<br />

Press <strong>to</strong> scroll through <strong>the</strong> parameters. While this key is pressed, and up <strong>to</strong> 1<br />

second after, <strong>the</strong> parameter legend is shown, followed by <strong>the</strong> current value.<br />

Press or <strong>to</strong> set <strong>the</strong> required value. Press <strong>to</strong> display <br />

, press<br />

accept <strong>the</strong> change, o<strong>the</strong>rwise parameter will revert <strong>to</strong> previous value. To exit from<br />

Configuration mode, hold down and press , <strong>to</strong> return <strong>to</strong> Select mode.<br />

Note: Parameters displayed depends on how <strong>in</strong>strument has been configured.<br />

Refer <strong>to</strong> user guide (available from your supplier) for fur<strong>the</strong>r details.<br />

Parameters marked * are repeated <strong>in</strong> Setup Mode.<br />

Parameter Legend Set Adjustment Range & Default Units<br />

for 1 sec Value Description Value Display<br />

followed<br />

( 1 /8 D<strong>in</strong><br />

by<br />

Only )<br />

Input<br />

Range/Type<br />

See follow<strong>in</strong>g table for possible codes <br />

<br />

Code Input Type &<br />

Range<br />

bC bF CC C: 0 - 2320 ºC NC<br />

CF C: 32 - 4208 ºF NF<br />

JC J: –200 - 1200 ºC<br />

JF J: –328 - 2192 ºF<br />

j.C J: –128.8 - 537.7 ºC<br />

j.F J: –199.9 - 999.9 ºF<br />

KC K: –240 - 1373 ºC tC<br />

KF K: –400 - 2503 ºF<br />

Code<br />

Input Type &<br />

Range<br />

B: 100 - 1824 ºC L.C L: 0.0 - 537.7 ºC<br />

B: 211 - 3315 ºF L.F L: 32.0 - 999.9 ºF<br />

Code Input Type &<br />

Range<br />

PtRh20% vs 40%:<br />

P24F 32 - 3362 ºF<br />

NC N: 0 - 1399 ºC PTC Pt100: –199 - 800 ºC<br />

NF N: 32 - 2551 ºF PtF Pt100: –328 - 1472 ºF<br />

rC R: 0 - 1759 ºC Pt.C Pt100: –128.8 - 537.7 ºC<br />

rF R: 32 - 3198 ºF Pt.F Pt100: –199.9 - 999.9 ºF<br />

SC S: 0 - 1762 ºC<br />

0 - 20 mA DC<br />

SF S: 32 - 3204 ºF<br />

4 - 20 mA DC<br />

tC T: –240 - 400 ºC<br />

0 - 50 mV DC<br />

tF T: –400 - 752 ºF<br />

.<br />

10 - 50 mV DC<br />

k.C K: –128.8 - 537.7 ºC t.C T: –128.8 - 400.0 ºC 0 - 5 V DC<br />

K.F K: –199.9 - 999.9 ºF t.F T: –199.9 - 752.0 ºF 1 - 5 V DC<br />

LC L: 0 - 762 ºC<br />

PtRh20% vs. 40%:<br />

0 - 10 V DC<br />

P24C LF L: 32 - 1403 ºF<br />

0 - 1850 ºC<br />

2 - 10 V DC<br />

Note: Decimal po<strong>in</strong>t shown <strong>in</strong> table <strong>in</strong>dicates temperature resolution of 0.1°<br />

Parameter Legend Set Adjustment Range & Default Units<br />

for 1 sec Value Description Value Display<br />

followed<br />

( 1 /8 D<strong>in</strong><br />

by<br />

Only )<br />

Scale Range<br />

Upper Limit<br />

Scale Range<br />

Lower Limit<br />

Decimal po<strong>in</strong>t<br />

position<br />

L<strong>in</strong>ear Range<br />

Eng<strong>in</strong>eer<strong>in</strong>g<br />

Units Display<br />

Multi-Po<strong>in</strong>t<br />

Scal<strong>in</strong>g<br />

Alarm 1Type<br />

High Alarm 1*<br />

Low Alarm 1*<br />

Alarm 1<br />

Hysteresis*<br />

Alarm 2Type<br />

High Alarm 2*<br />

Low Alarm 2*<br />

Al 2 Hysteresis*<br />

Alarm 3Type<br />

High Alarm 3*<br />

Low Alarm 3*<br />

Al 3 Hysteresis*<br />

Alarm 4Type<br />

<br />

Scale Range Lower Limit +100 Max (L<strong>in</strong><br />

<strong>to</strong> Range Maximum = 1000)<br />

<br />

<br />

Range M<strong>in</strong>imum <strong>to</strong> M<strong>in</strong> (L<strong>in</strong><br />

Scale Range Upper Limit -100 = 0)<br />

<br />

=XXXX, =XXX.X, (non-temperature<br />

=XX.XX, =X.XXX ranges only)<br />

<br />

<br />

None (Blank), °C or °F<br />

<br />

<br />

<br />

1 / 8 D<strong>in</strong> units only where l<strong>in</strong>ear<br />

<br />

°<br />

<br />

<br />

<strong>in</strong>puts represent temperature<br />

°<br />

<br />

<br />

Enables or disables <strong>the</strong> <strong>in</strong>put<br />

Mm<br />

<br />

multi-po<strong>in</strong>t scal<strong>in</strong>g feature<br />

<br />

<br />

<br />

Process High Alarm<br />

<br />

<br />

Process Low Alarm<br />

<br />

<br />

<br />

No alarm<br />

<br />

Alarm 1 value, adjustable with<strong>in</strong> scaled Max (Alm1<br />

<br />

range, <strong>in</strong> display units M<strong>in</strong> only = )<br />

1 LSD <strong>to</strong> full span <strong>in</strong> display units on<br />

safe side of alarm<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

Max<br />

Options as for alarm 1<br />

<br />

M<strong>in</strong><br />

<br />

<br />

!<br />

<br />

<br />

<br />

<br />

Max<br />

Options as for alarm 1<br />

<br />

M<strong>in</strong><br />

<br />

<br />

*<br />

Options as for alarm 1 <br />

<br />

Parameter<br />

Legend<br />

for 1 sec<br />

followed<br />

by<br />

Set<br />

Value<br />

Adjustment Range &<br />

Description<br />

Default<br />

Value<br />

Units<br />

Display<br />

( 1 /8 D<strong>in</strong><br />

Only )<br />

High Alarm 4* <br />

Max<br />

Low Alarm 4*<br />

Options as for alarm 1 M<strong>in</strong> <br />

Al 4 Hysteresis*<br />

<br />

<br />

Alarm 5 Type<br />

<br />

<br />

<br />

High Alarm 5*<br />

<br />

Max<br />

Options as for alarm 1<br />

Low Alarm 5*<br />

<br />

M<strong>in</strong><br />

<br />

Al 5 Hysteresis*<br />

<br />

<br />

" Alarm 1, direct, non-latch<strong>in</strong>g<br />

Alarm 1, reverse, non-latch<strong>in</strong>g<br />

"<br />

Alarm 1, direct, latch<strong>in</strong>g<br />

<br />

Alarm 1, reverse, latch<strong>in</strong>g<br />

Alarm 2, direct, non-latch<strong>in</strong>g<br />

Alarm 2, reverse, non-latch<strong>in</strong>g<br />

<br />

Alarm 2, direct, latch<strong>in</strong>g<br />

<br />

Alarm 2, reverse, latch<strong>in</strong>g<br />

Alarm 3, direct, non-latch<strong>in</strong>g<br />

Alarm 3, reverse, non-latch<strong>in</strong>g<br />

<br />

Alarm 3, direct, latch<strong>in</strong>g<br />

<br />

Alarm 3, reverse, latch<strong>in</strong>g<br />

Alarm 4, direct, non-latch<strong>in</strong>g<br />

Alarm 4, reverse, non-latch<strong>in</strong>g for<br />

l<strong>in</strong>ear<br />

<br />

Alarm 4, direct, latch<strong>in</strong>g<br />

outputs,<br />

Output 1 Usage<br />

<br />

<br />

Alarm 4, reverse, latch<strong>in</strong>g<br />

<br />

Alarm 5, direct, non-latch<strong>in</strong>g "<br />

Alarm 5, reverse, non-latch<strong>in</strong>g for o<strong>the</strong>rs<br />

<br />

Alarm 5, direct, latch<strong>in</strong>g<br />

<br />

Alarm 5, reverse, latch<strong>in</strong>g<br />

Logical Alarm 1 OR 2, direct<br />

Logical Alarm 1 OR 2, reverse<br />

Logical Alarm 1 OR 3, direct<br />

Logical Alarm 1 OR 3, reverse<br />

Logical Alarm 2 OR 3, direct<br />

Logical Alarm 2 OR 3, reverse<br />

<br />

Any active alarm, direct<br />

<br />

Any active alarm, reverse<br />

<br />

Retransmit PV Output<br />

#<br />

0 <strong>to</strong> 10VDC (adjustable)<br />

transmitter power supply*<br />

<br />

0 <strong>to</strong> 5 V DC output<br />

<br />

0 <strong>to</strong> 10 V DC output<br />

Output 1 PV<br />

<br />

2 <strong>to</strong> 10 V DC output<br />

Retransmit Type <br />

<br />

0 <strong>to</strong> 20 mA DC output<br />

<br />

<br />

<br />

4 <strong>to</strong> 20 mA DC output<br />

Retransmit OP 1 Display value between, -1999 & 9999 Range<br />

Scale maximum<br />

at which Output 1 will be at maximum max<br />

<br />

Retransmit OP 1 Display value between, -1999 & 9999 Range<br />

Scale m<strong>in</strong>imum<br />

at which Output 1 will be at m<strong>in</strong>imum m<strong>in</strong><br />

<br />

TxPSU 1 level Output 1 Power Supply (0 <strong>to</strong> 10VDC)*<br />

.<br />

<br />

Output 2 Usage<br />

As for Output 1 Usage <br />

<br />

Output 2 PV<br />

Retransmit Type<br />

As for Output 1 PV Retransmit Type <br />

Retransmit OP2<br />

Scale Maximum<br />

As for Retransmit Output 1 Scale Maximum <br />

Retransmit OP2<br />

Scale M<strong>in</strong>imum<br />

As for Retransmit Output 1 Scale M<strong>in</strong>imum <br />

TxPSU 2 level Output 2 Power Supply (0 <strong>to</strong> 10VDC)*<br />

.<br />

<br />

Output 3 Usage<br />

As for Output 1 Usage <br />

<br />

Output 3 PV<br />

Retransmit Type<br />

As for Output 1 PV Retransmit Type <br />

Retransmit OP3<br />

Scale maximum<br />

As for Retransmit Output 1 Scale Maximum <br />

Retransmit OP3<br />

Scale m<strong>in</strong>imum<br />

As for Retransmit Output 1 Scale M<strong>in</strong>imum <br />

TxPSU 3 level Output 3 Power Supply (0 <strong>to</strong> 10VDC)*<br />

.<br />

<br />

Output 4 Usage<br />

<br />

Alarm output options as for <br />

<br />

Output 5 Usage<br />

<br />

Output 1 Usage<br />

<br />

<br />

Display Strategy $ , , , , or % (refer <strong>to</strong> section 6) <br />

<br />

Permanent Red<br />

Display Colour<br />

<br />

<br />

Permanent Green<br />

&<br />

Red <strong>to</strong> Green on any alarm<br />

& #<br />

&<br />

Green <strong>to</strong> Red on any alarm<br />

'<br />

ASCII<br />

Serial<br />

Mm<br />

<br />

Modbus with no parity<br />

Communication<br />

<br />

Mm<br />

<br />

<br />

Pro<strong>to</strong>col Mm<br />

<br />

Modbus with Even Parity<br />

Mm<br />

<br />

Modbus with Odd Parity<br />

Comms Bit Rate ., ., .(, ).% or ). kbps .( <br />

Comms Address <br />

<strong>to</strong> (Modbus), <strong>to</strong> )) (ASCII) <br />

Cont<strong>in</strong>ued on next page…


Parameter<br />

Comms Write<br />

Digital Input<br />

Usage<br />

Config Lock<br />

Legend<br />

for 1 sec<br />

followed<br />

by<br />

4. SETUP MODE<br />

Set<br />

Value<br />

Adjustment Range &<br />

Description<br />

Default<br />

Value<br />

Ww<br />

Ww<br />

Read/Write<br />

<br />

<br />

Read only<br />

Ww<br />

Ww<br />

<br />

Reset latched relay(s)<br />

Initiate Tare (zero display)<br />

<br />

<br />

Reset m<strong>in</strong>/max PV values<br />

<br />

Reset Alarm 1 elapsed time<br />

<br />

Reset Alarm 1 elapsed time<br />

& m<strong>in</strong>/max PV values<br />

# Config Mode lock code, <strong>to</strong> )))) <br />

Units<br />

Display<br />

( 1 /8 D<strong>in</strong><br />

Only )<br />

Note: Configuration must be completed before adjust<strong>in</strong>g Setup parameters.<br />

First select Setup mode from Select mode (refer <strong>to</strong> section 2). Press <strong>to</strong> scroll<br />

through <strong>the</strong> parameters (while this key is pressed, and for 1 sec after, <strong>the</strong> parameter<br />

legend is shown, <strong>the</strong>n <strong>the</strong> current value). Press or <strong>to</strong> change <strong>the</strong> value.<br />

To exit from Setup mode, hold down and press <strong>to</strong> return <strong>to</strong> Select mode.<br />

Note: Parameters displayed depends on how <strong>in</strong>strument has been configured.<br />

Parameter Legend Set Adjustment Range & Default Units<br />

for 1 sec Value Description Value Display<br />

followed<br />

( 1 /8 D<strong>in</strong><br />

by<br />

Only )<br />

Input Filter Time<br />

Constant<br />

OFF or 0.5 <strong>to</strong> 100.0 secs . <br />

Process Variable<br />

Offset<br />

±Span of controller . <br />

Raw PV value<br />

L<strong>in</strong>ear <strong>in</strong>put value, un-scaled (mA, mV or VDC)blank<br />

High Alarm 1<br />

<br />

Alarm 1 value, adjustable with<strong>in</strong> scaled Max (Alm1<br />

Low Alarm 1<br />

<br />

range, <strong>in</strong> display units M<strong>in</strong> only = )<br />

Alarm 1<br />

1 LSD <strong>to</strong> full span <strong>in</strong> display units on<br />

Hysteresis<br />

safe side of alarm<br />

<br />

<br />

<br />

High Alarm 2<br />

<br />

Max<br />

Low Alarm 2<br />

<br />

Options as for alarm 1 M<strong>in</strong><br />

<br />

Al 2 Hysteresis<br />

<br />

!<br />

High Alarm 3<br />

<br />

Max<br />

Low Alarm 3<br />

<br />

Options as for alarm 1 M<strong>in</strong><br />

<br />

Al 3 Hysteresis<br />

<br />

*<br />

High Alarm 4<br />

<br />

Max<br />

Low Alarm 4<br />

<br />

Options as for alarm 1 M<strong>in</strong><br />

<br />

Al 4 Hysteresis<br />

<br />

<br />

High Alarm 5<br />

<br />

Max<br />

Low Alarm 5<br />

<br />

Options as for alarm 1 M<strong>in</strong><br />

<br />

Al 5 Hysteresis<br />

<br />

5<br />

Scal<strong>in</strong>g<br />

Multi-po<strong>in</strong>t scal<strong>in</strong>g breakpo<strong>in</strong>t 1 value,<br />

Breakpo<strong>in</strong>t 1<br />

# <br />

adjustable from <strong>to</strong><br />

<strong>in</strong> % of span<br />

Value <strong>to</strong> be displayed at multi-po<strong>in</strong>t Range<br />

Display Value 1<br />

scal<strong>in</strong>g breakpo<strong>in</strong>t 1, <strong>in</strong> display units Max<br />

<br />

Scal<strong>in</strong>g<br />

Multi-po<strong>in</strong>t scal<strong>in</strong>g breakpo<strong>in</strong>t 2, adjustable up <strong>to</strong><br />

Breakpo<strong>in</strong>t 2<br />

# 100% of span. Must be >#<br />

value<br />

Value <strong>to</strong> be displayed at Multi-po<strong>in</strong>t scal<strong>in</strong>g<br />

Display Value 2<br />

<br />

breakpo<strong>in</strong>t 2, <strong>in</strong> display units<br />

<br />

Scal<strong>in</strong>g<br />

Multi-po<strong>in</strong>t scal<strong>in</strong>g breakpo<strong>in</strong>t 3, adjustable up <strong>to</strong><br />

Breakpo<strong>in</strong>t 3<br />

#<br />

# 100% of span. Must be >#<br />

value<br />

Value <strong>to</strong> be displayed at Multi-po<strong>in</strong>t scal<strong>in</strong>g<br />

Display Value 3<br />

<br />

breakpo<strong>in</strong>t 3, <strong>in</strong> display units<br />

<br />

Scal<strong>in</strong>g<br />

Multi-po<strong>in</strong>t scal<strong>in</strong>g breakpo<strong>in</strong>t 4, adjustable up <strong>to</strong><br />

Breakpo<strong>in</strong>t 4<br />

# 100% of span. Must be >#<br />

value<br />

Value <strong>to</strong> be displayed at Multi-po<strong>in</strong>t scal<strong>in</strong>g<br />

Display Value 4<br />

<br />

breakpo<strong>in</strong>t 4, <strong>in</strong> display units<br />

<br />

Scal<strong>in</strong>g<br />

Multi-po<strong>in</strong>t scal<strong>in</strong>g breakpo<strong>in</strong>t 5, adjustable up <strong>to</strong><br />

Breakpo<strong>in</strong>t 5<br />

# 100% of span. Must be >#<br />

value<br />

Value <strong>to</strong> be displayed at Multi-po<strong>in</strong>t scal<strong>in</strong>g<br />

Display Value 5<br />

<br />

breakpo<strong>in</strong>t 5, <strong>in</strong> display units<br />

<br />

Scal<strong>in</strong>g<br />

Multi-po<strong>in</strong>t scal<strong>in</strong>g breakpo<strong>in</strong>t 6, adjustable up <strong>to</strong><br />

Breakpo<strong>in</strong>t 6<br />

#% 100% of span. Must be >#<br />

value<br />

Value <strong>to</strong> be displayed at Multi-po<strong>in</strong>t scal<strong>in</strong>g<br />

Display Value 6<br />

%<br />

breakpo<strong>in</strong>t 6, <strong>in</strong> display units<br />

%<br />

Scal<strong>in</strong>g<br />

Multi-po<strong>in</strong>t scal<strong>in</strong>g breakpo<strong>in</strong>t 7, adjustable up <strong>to</strong><br />

Breakpo<strong>in</strong>t 7<br />

#* 100% of span. Must be >#%<br />

value<br />

Value <strong>to</strong> be displayed at Multi-po<strong>in</strong>t scal<strong>in</strong>g<br />

Display Value 7<br />

*<br />

breakpo<strong>in</strong>t 7, <strong>in</strong> display units<br />

*<br />

Scal<strong>in</strong>g<br />

Multi-po<strong>in</strong>t scal<strong>in</strong>g breakpo<strong>in</strong>t 8, adjustable up <strong>to</strong><br />

Breakpo<strong>in</strong>t 8<br />

#( 100% of span. Must be >#*<br />

value<br />

Value <strong>to</strong> be displayed at Multi-po<strong>in</strong>t scal<strong>in</strong>g<br />

Display Value 8<br />

(<br />

breakpo<strong>in</strong>t 8, <strong>in</strong> display units<br />

(<br />

Scal<strong>in</strong>g<br />

Multi-po<strong>in</strong>t scal<strong>in</strong>g breakpo<strong>in</strong>t 9, adjustable up <strong>to</strong><br />

Breakpo<strong>in</strong>t 9<br />

#) 100% of span. Must be >#(<br />

value<br />

Value <strong>to</strong> be displayed at Multi-po<strong>in</strong>t scal<strong>in</strong>g<br />

Display Value 9<br />

)<br />

breakpo<strong>in</strong>t 9, <strong>in</strong> display units<br />

)<br />

Tare Feature<br />

<br />

Enables or disables <strong>the</strong> <strong>in</strong>put<br />

<br />

au<strong>to</strong>-zero Tare feature<br />

<br />

<br />

Setup Lock Code # <strong>to</strong> )))) <br />

<br />

Note: Opera<strong>to</strong>r mode screens follow, without exit<strong>in</strong>g from Setup mode.<br />

<br />

<br />

<br />

5. MESSAGES & ERROR INDICATIONS<br />

These messages <strong>in</strong>dicate that <strong>the</strong> <strong>in</strong>strument may require attention, or <strong>the</strong>re is a<br />

problem with <strong>the</strong> signal <strong>in</strong>put connection. The message legend is shown for 1<br />

second, followed by its value.<br />

Caution: Do not cont<strong>in</strong>ue with <strong>the</strong> process until <strong>the</strong> issue is resolved.<br />

Parameter<br />

Instrument<br />

parameters are <strong>in</strong><br />

default conditions<br />

Input Over Range<br />

Input Under Range<br />

Legend<br />

for 1 sec<br />

followed<br />

by<br />

<br />

Input Sensor Break -<br />

Option 1 Error<br />

..<br />

Option 2 Error<br />

Option 3 Error<br />

Option A Error<br />

.. Option A module fault <br />

Option B Error<br />

..<br />

Shown if any module is fitted<br />

(option B not used on Indica<strong>to</strong>rs)<br />

<br />

Note: +,, +<br />

, or - may also be displayed if an <strong>in</strong>correct <strong>in</strong>put type is<br />

selected.<br />

Value Description<br />

Units<br />

Display<br />

( 1 /8 D<strong>in</strong><br />

Only )<br />

Configuration & Setup is required.<br />

This screen is seen at first turn on,<br />

or if hardware configuration is<br />

<br />

changed. Press <strong>to</strong> enter <br />

Configuration Mode, next press<br />

or <strong>to</strong> enter <strong>the</strong> unlock code,<br />

<strong>the</strong>n press <strong>to</strong> proceed<br />

+<br />

,<br />

Input signal is > 5% over-range<br />

Input signal is > 5% under-range<br />

+<br />

,<br />

(>10% under-range for 4 <strong>to</strong> 20mA,<br />

1 <strong>to</strong> 5V and 2 <strong>to</strong> 10V ranges)<br />

<br />

-<br />

Break detected <strong>in</strong> <strong>in</strong>put signal<br />

sensor or wir<strong>in</strong>g<br />

.. Option 1 module fault <br />

.. Option 2 module fault <br />

.. Option 3 module fault <br />

6. OPERATOR MODE<br />

This mode is entered at power on, or accessed from Select mode (see section 2).<br />

Note: All Configuration mode and Setup mode parameters must be set as<br />

required before start<strong>in</strong>g normal operations.<br />

Press <strong>to</strong> scroll through <strong>the</strong> parameters (while this key is pressed, and for 1 sec<br />

after, <strong>the</strong> parameter legend is shown, followed by <strong>the</strong> current value).<br />

Note: All Opera<strong>to</strong>r Mode parameters <strong>in</strong> Display strategy 6 are read only (see<br />

<strong>in</strong> configuration mode), <strong>the</strong>y can only be adjusted via Setup mode.<br />

Legend<br />

for 1 sec<br />

followed<br />

by<br />

#<br />

Value<br />

PV<br />

Value*<br />

Display Strategy and<br />

When Visible<br />

Always<br />

Max PV<br />

Mm Value<br />

Strategies , , , , & %<br />

M<strong>in</strong> PV<br />

Mm<br />

Value<br />

Strategies , , , , & %<br />

Elapsed<br />

Time<br />

Alarm 1<br />

Value<br />

Alarm 2<br />

Value<br />

Alarm 3<br />

Value<br />

Alarm 4<br />

Value<br />

Alarm 5<br />

Value<br />

Active<br />

<br />

Alarm<br />

Status* <br />

Strategies , & %<br />

if alarm 1 configured.<br />

Format mm.ss <strong>to</strong> 99.59<br />

<strong>the</strong>n mmm.s<br />

(10 sec <strong>in</strong>crements)<br />

Shows +<br />

, if >999.9<br />

Strategies , , & %<br />

if alarm 1 configured<br />

Strategies , , & %<br />

if alarm 2 configured<br />

Strategies , , & %<br />

if alarm 3 configured<br />

Strategies , , & %<br />

if alarm 4 configured<br />

Strategies , , & %<br />

if alarm 5 configured<br />

When one or more<br />

alarms are active<br />

Description<br />

Process Variable value<br />

Read only<br />

Latched outputs can be reset<br />

Maximum displayed value<br />

(<strong>in</strong>c +, or -)<br />

s<strong>in</strong>ce Mm last reset.<br />

To reset, press or for<br />

3 seconds,<br />

display = &&&& when reset<br />

M<strong>in</strong>imum displayed value<br />

(<strong>in</strong>c +<br />

, or -)<br />

s<strong>in</strong>ce Mm<br />

last reset.<br />

To reset, press or for<br />

3 seconds,<br />

display = &&&& when reset<br />

Accumulated alarm 1 active<br />

time s<strong>in</strong>ce last reset.<br />

To reset, press or for<br />

3 seconds,<br />

display = &&&& when reset<br />

Alarm 1 value, adjustable<br />

except <strong>in</strong> Strategy 6<br />

Alarm 2 value, adjustable<br />

except <strong>in</strong> Strategy 6<br />

Alarm 3 value, adjustable<br />

except <strong>in</strong> Strategy 6<br />

Alarm 4 value, adjustable<br />

except <strong>in</strong> Strategy 6<br />

Alarm 5 value, adjustable<br />

except <strong>in</strong> Strategy 6<br />

L Alarm 4 active<br />

Alarm 2 active<br />

Alarm 3 active<br />

Alarm 5 active<br />

Latched outputs can be reset<br />

Units<br />

Display<br />

( 1 /8 D<strong>in</strong><br />

Only )<br />

° ° , or<br />

blank<br />

° , ° or<br />

blank<br />

° , ° or<br />

blank<br />

<br />

(Alm1<br />

only = )<br />

<br />

<br />

<br />

<br />

if<br />

alarm 1<br />

active<br />

Alarm Indication<br />

The Active Alarm Status screen <strong>in</strong>dicates any active alarms. In addition, <strong>the</strong><br />

associated Alarm LED flashes.<br />

For latch<strong>in</strong>g alarm outputs, <strong>the</strong> LED flashes when <strong>the</strong> alarm condition exists,<br />

and goes <strong>to</strong> ON when <strong>the</strong> alarm condition is no longer present if <strong>the</strong> output has not<br />

yet been reset.<br />

*Resett<strong>in</strong>g Latched Alarm Outputs<br />

Any latched outputs can be reset whilst <strong>the</strong> Process variable or Alarm Status<br />

screens are displayed, by press<strong>in</strong>g <strong>the</strong> or key, via <strong>the</strong> Digital Input (if fitted)<br />

or with a communications command via <strong>the</strong> RS485 module (if fitted).<br />

Note: Outputs will only reset if <strong>the</strong>ir alarm condition is no longer present.<br />

Caution: A reset will affect ALL latched outputs.<br />

Additional 1 / 8 D<strong>in</strong> Indica<strong>to</strong>r Units Display and LED’s<br />

In Opera<strong>to</strong>r Mode, a Units display shows ° or ° when temperature values are<br />

shown. This display is also used <strong>in</strong> o<strong>the</strong>r modes as a confirmation of <strong>the</strong> parameter<br />

type currently shown <strong>in</strong> <strong>the</strong> ma<strong>in</strong> display. The SET LED <strong>in</strong>dica<strong>to</strong>r is off <strong>in</strong><br />

Opera<strong>to</strong>r Mode, Flash<strong>in</strong>g <strong>in</strong> Configuration Mode and ON <strong>in</strong> Set-up mode.<br />

MIN and MAX LED’s light when <strong>the</strong>se s<strong>to</strong>red values are shown.<br />

Multi-Po<strong>in</strong>t Scal<strong>in</strong>g<br />

When enabled (Mm<br />

= ),<br />

up <strong>to</strong> 9 breakpo<strong>in</strong>ts can be set <strong>to</strong><br />

compensate for non-l<strong>in</strong>ear <strong>in</strong>put<br />

signals.<br />

For each breakpo<strong>in</strong>t, <strong>the</strong> <strong>in</strong>put<br />

scale value (#<br />

#n) is entered<br />

<strong>in</strong> % of <strong>in</strong>put span, followed by<br />

<strong>the</strong> value <strong>to</strong> be shown (<br />

n)<br />

<strong>in</strong> display units.<br />

Each breakpo<strong>in</strong>t’s <strong>in</strong>put scale<br />

value must be higher than <strong>the</strong><br />

previous value, but <strong>the</strong> display<br />

values can be higher or lower.<br />

Any scale value set <strong>to</strong> 100%<br />

becomes <strong>the</strong> last <strong>in</strong> <strong>the</strong> series.<br />

Tare Feature<br />

When Tare is enabled (<br />

= ), it can be used <strong>to</strong> set <strong>the</strong> displayed value <strong>to</strong><br />

zero au<strong>to</strong>matically, by mak<strong>in</strong>g <strong>the</strong> PV Offset parameter equal, but opposite <strong>to</strong>, <strong>the</strong><br />

current process variable value. Tare can be <strong>in</strong>itiated via <strong>the</strong> Digital Input (if fitted),<br />

with a communications command via <strong>the</strong> RS485 module (if fitted) or by us<strong>in</strong>g <strong>the</strong><br />

follow<strong>in</strong>g key press sequence:<br />

Press until <strong>the</strong> process variable is displayed.<br />

Hold down and <strong>to</strong>ge<strong>the</strong>r for three seconds until <strong>the</strong> display shows /$<br />

Release both keys and press with<strong>in</strong> 3 seconds <strong>to</strong> confirm <strong>the</strong> request.<br />

The display should read briefly, <strong>the</strong>n beg<strong>in</strong> respond<strong>in</strong>g <strong>to</strong> <strong>in</strong>put signal changes.<br />

Note: Tare request is aborted if this sequence is not followed exactly.<br />

7. PRODUCT INFORMATION MODE<br />

First select Product <strong>in</strong><strong>format</strong>ion mode from Select mode (refer <strong>to</strong> section 2).<br />

Press <strong>to</strong> view each parameter (while this key is pressed, and for 1 sec after, <strong>the</strong><br />

parameter legend is shown, followed by its value). Hold down and press <strong>to</strong><br />

return <strong>to</strong> Select mode. Note: These parameters are all read only.<br />

Parameter Legend Value Description<br />

Units<br />

for 1 sec<br />

Display<br />

followed<br />

( 1 /8 D<strong>in</strong><br />

by<br />

Only )<br />

Input type<br />

'<br />

Universal <strong>in</strong>put<br />

<br />

No option fitted<br />

/ Relay output<br />

Option 1 module<br />

SSR drive output<br />

type fitted<br />

<br />

<br />

Triac output<br />

L<strong>in</strong>ear DC voltage / current output<br />

No option fitted<br />

/ Relay output<br />

Option 2 module<br />

/Dual Relay (outputs 2 & 4)<br />

type fitted<br />

<br />

SSR drive output<br />

<br />

Triac output<br />

L<strong>in</strong>ear DC voltage / current output<br />

No option fitted<br />

/ Relay output<br />

Option 3 module<br />

/Dual Relay (outputs 3 & 5)<br />

type fitted<br />

<br />

SSR drive output<br />

<br />

L<strong>in</strong>ear DC voltage / current output<br />

#24V DC Transmitter power supply<br />

No option fitted<br />

Auxiliary Option A<br />

(RS485 communications<br />

module type fitted <br />

<br />

Digital Input<br />

Firmware type<br />

01Value displayed is firmware type number <br />

Firmware issue<br />

'$$Value displayed is firmware issue number <br />

Product Rev Level . Value displayed is Product Revision Level <br />

Manufactured Date MmMonth & year of manufacture. Format mmyy <br />

Serial number 1 First four digits of serial number<br />

<br />

Serial number 2 Middle four digits of serial number<br />

<br />

Serial number 3 Last four digits of serial number #<br />

8. SERIAL COMMUNICATIONS<br />

Refer <strong>to</strong> <strong>the</strong> full user guide (available from your supplier) for details.<br />

i<br />

Displayed Value<br />

% of Span<br />

PV Input Signal<br />

9. SPECIFICATIONS<br />

UNIVERSAL INPUT<br />

Thermocouple<br />

Calibration:<br />

PT100 Calibration:<br />

±0.1% of full range, ±1LSD (±1°C for Thermocouple CJC).<br />

BS4937, NBS125 & IEC584.<br />

±0.1% of full range, ±1LSD.<br />

BS1904 & DIN43760 (0.00385Ω/Ω/°C).<br />

±0.1% of full range, ±1LSD.<br />

4 per second.<br />

DC Calibration:<br />

Sampl<strong>in</strong>g Rate:<br />

Impedance: >10MΩ resistive, except DC mA (5Ω) and V (47kΩ ).<br />

Sensor Break Thermocouple, RTD, 4 <strong>to</strong> 20 mA, 2 <strong>to</strong> 10V and 1 <strong>to</strong> 5V ranges<br />

Detection: only. High alarms activate for <strong>the</strong>rmocouple/RTD sensor break,<br />

low alarms activate for mA/V DC sensor break.<br />

Isolation:<br />

DIGITAL INPUT<br />

Voltage Input:<br />

Volt-free Contacts:<br />

Isolation:<br />

OUTPUTS<br />

Relay<br />

Contact Type &<br />

Rat<strong>in</strong>g:<br />

Lifetime:<br />

Isolation:<br />

Dual Relay<br />

Contact Type &<br />

Rat<strong>in</strong>g:<br />

Lifetime:<br />

Isolation:<br />

SSR Driver<br />

Drive Capability:<br />

Isolation:<br />

Triac<br />

Operat<strong>in</strong>g Voltage:<br />

Current Rat<strong>in</strong>g:<br />

Isolation:<br />

Isolated from all outputs (except SSR driver).<br />

Universal <strong>in</strong>put must not be connected <strong>to</strong> opera<strong>to</strong>r accessible<br />

circuits if s<strong>in</strong>gle relay outputs are connected <strong>to</strong> a hazardous<br />

voltage source. Supplementary <strong>in</strong>sulation or <strong>in</strong>put ground<strong>in</strong>g<br />

would <strong>the</strong>n be required.<br />

Reset or Tare occurs on high (2 <strong>to</strong> 24VDC) <strong>to</strong> low 500,000 operations at rated voltage/current.<br />

Basic Isolation from universal <strong>in</strong>put and SSR outputs.<br />

S<strong>in</strong>gle pole s<strong>in</strong>gle throw (SPST), latch<strong>in</strong>g or non-latch<strong>in</strong>g<br />

action (selectable); 2A resistive at 120/240VAC.<br />

>200,000 operations at rated voltage/current.<br />

Re<strong>in</strong>forced safety isolation from <strong>in</strong>puts and o<strong>the</strong>r outputs.<br />

SSR drive voltage >10V <strong>in</strong><strong>to</strong> 500Ω m<strong>in</strong>.<br />

Not isolated from universal <strong>in</strong>put or o<strong>the</strong>r SSR driver outputs.<br />

20 <strong>to</strong> 280Vrms (47 <strong>to</strong> 63Hz).<br />

0.01 <strong>to</strong> 1A (full cycle rms on-state @ 25°C);<br />

derates l<strong>in</strong>early above 40°C <strong>to</strong> 0.5A @ 80°C.<br />

Re<strong>in</strong>forced safety isolation from <strong>in</strong>puts and o<strong>the</strong>r outputs.<br />

L<strong>in</strong>ear DC<br />

Accuracy: ±0.25% (mA @ 250, V @ 2k). Degrades l<strong>in</strong>early <strong>to</strong> ±0.5%<br />

for <strong>in</strong>creas<strong>in</strong>g burden (<strong>to</strong> specification limits).<br />

Resolution: 8 bits <strong>in</strong> 250mS (10 bits <strong>in</strong> 1s typical, >10 bits <strong>in</strong> >1s typical).<br />

Isolation: Re<strong>in</strong>forced safety isolation from <strong>in</strong>puts and o<strong>the</strong>r outputs.<br />

Transmitter PSU<br />

Power Rat<strong>in</strong>g: 24V TxPSU Module; Unregulated 20 <strong>to</strong> 28V DC <strong>in</strong><strong>to</strong> 910Ω m<strong>in</strong><br />

L<strong>in</strong>ear output Module; Regulated 0.0 <strong>to</strong> 10.0V <strong>in</strong><strong>to</strong> 500Ω m<strong>in</strong>.<br />

Isolation: Re<strong>in</strong>forced safety isolation from <strong>in</strong>puts and o<strong>the</strong>r outputs.<br />

SERIAL COMMUNICATIONS<br />

Physical: RS485, at 1200, 2400, 4800, 9600 or 19200 bps.<br />

Pro<strong>to</strong>cols: Selectable between Modbus and <strong>West</strong> ASCII.<br />

Isolation: Re<strong>in</strong>forced safety isolation from all <strong>in</strong>puts and outputs.<br />

OPERATING CONDITIONS (FOR INDOOR USE)<br />

Ambient<br />

0°C <strong>to</strong> 55°C (Operat<strong>in</strong>g), –20°C <strong>to</strong> 80°C (S<strong>to</strong>rage).<br />

Temperature:<br />

Relative Humidity: 20% <strong>to</strong> 95% non-condens<strong>in</strong>g.<br />

Supply Voltage and<br />

Power:<br />

100 <strong>to</strong> 240VAC ±10%, 50/60Hz, 7.5VA<br />

(for ma<strong>in</strong>s powered versions), or<br />

20 <strong>to</strong> 48VAC 50/60Hz 7.5VA or 22 <strong>to</strong> 65VDC 5W<br />

(for low voltage versions).<br />

ENVIRONMENTAL<br />

Standards: CE, UL & ULC<br />

EMI:<br />

Complies with EN61326 (Susceptibility & Emissions).<br />

Safety<br />

Considerations:<br />

Complies with EN61010-1 & UL3121.<br />

Pollution Degree 2, Installation Category II.<br />

Front Panel Seal<strong>in</strong>g: To IP66 (IP20 beh<strong>in</strong>d <strong>the</strong> panel).<br />

PHYSICAL<br />

Front Bezel Size:<br />

1 / 16 D<strong>in</strong> = 48 x 48mm, 1 / 8 D<strong>in</strong> = 96 x 48mm<br />

Depth Beh<strong>in</strong>d Panel: 1 / 16 D<strong>in</strong> = 110mm, 1 / 8 D<strong>in</strong> = 100mm.<br />

Weight:<br />

0.21kg maximum.<br />