Hybrid Technique<br />
Transition Joint Type CHMP(3Pb)<br />
for three-core single lead sheath cables to polymeric cables from 24 up to 36 kV<br />
Application<br />
Transition joint<br />
– Type CHMP(3Pb)3-1 for connecting three single-core polymeric cables<br />
– Type CHMP(3Pb)3 for connecting one three-core polymeric cable<br />
are designed to cover three-core single lead sheath cables from 24 up to 36 kV.<br />
For paper cables with small conductors an adapter kit is available.<br />
Features<br />
• Quick, easy and safe installation due to the combination of slip-on and heat-shrink components<br />
• Reliable stress control for all operating conditions due to flexible silicone stress control elements<br />
• Wide cross section range suitable for all types of connectors with oil barrier<br />
• Applicable for all types of polymeric cables<br />
• Unlimited shelf life and immediate operation after installation<br />
Design<br />
A kit of a joint consists of the following main components:<br />
• Silicone stress control elements<br />
• Blue filling tape with stress control and oil resisting features<br />
• Oil-resisiting heat-shrink tube<br />
• Conductive heat-shrink tubes and spreader cap<br />
• Insulating thick-wall heat-shrink tubes<br />
• Copper braid sleeve<br />
• Thick-wall heat-shrink tubes with hot melting adhesive as an outer protection<br />
Delivery<br />
One kit for three phases without connector.<br />
Required connectors can be ordered separately.<br />
Three-core single lead sheath cable<br />
1 Carbon or metallized paper<br />
2 Impregnated paper insulation<br />
3 Impregnated carbon paper<br />
4 Stranded conductor<br />
5 Lead alloy sheath<br />
6 Impregnated paper<br />
7 Filler<br />
8 Compounded synthetic tape<br />
9 Steel armour<br />
10 Outer sheath<br />
| 32 | D529•0504