<strong>Local</strong> <strong>Thermal</strong> <strong>Discomfort</strong><br />
• Draught Rating Model<br />
PD = (34 – t a )(v – 0.05) 0.62 (0.37vTu + 3.14)<br />
For v < 0.5 m/s insert v = 0.05 m/s;<br />
for PD > 100%, insert PD = 100%<br />
Valid for: 20 < t a < 26˚C, v < 0.05 m/s<br />
19