30.01.2015 Views

Triple IR (IR3) Flame Detector - LGM Products Ltd

Triple IR (IR3) Flame Detector - LGM Products Ltd

Triple IR (IR3) Flame Detector - LGM Products Ltd

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>Triple</strong> <strong>IR</strong> (<strong>IR</strong>3)<br />

<strong>Flame</strong> <strong>Detector</strong><br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

Discriminates between flames and other sources of heat<br />

Detects invisible flames from fuels such as hydrogen<br />

Impervious to oil, dust or ice on the lens<br />

LPCB certified to EN54 part10<br />

Selectable response speed<br />

Optical self test<br />

Low power consumption<br />

© 2013 <strong>LGM</strong> <strong>Products</strong> <strong>Ltd</strong>. (v11.4)<br />

<strong>LGM</strong> <strong>Products</strong> <strong>Ltd</strong>, Unit 15 Riverside Industrial Park, Farnham, Surrey, GU9 7UG, United Kingdom.<br />

Tel: +44(0)1252 725257 Fax: +44(0)1252 727627 Email: sales@lgmproducts.com Web: www.lgmproducts.com


<strong>Triple</strong> <strong>IR</strong> (<strong>IR</strong>3)<br />

<strong>Flame</strong> <strong>Detector</strong><br />

Part number 016589<br />

Supply voltage<br />

Quiescent current<br />

Selectable output options<br />

Alarm current<br />

Operating temperature<br />

Humidity<br />

IP rating<br />

Field of view<br />

Range of view<br />

Sensitivity<br />

Spectral response<br />

Reset time<br />

Reset voltage<br />

Power up time<br />

Housing material<br />

Dimensions<br />

<strong>Detector</strong> weight<br />

Approvals<br />

14 to 30 Vdc<br />

8mA, fault relay energised<br />

3mA, fault relay de-energised<br />

4mA, current loop fault relay de-energised<br />

Conventional 2 wire 4-20mA<br />

Latching or Non-latching<br />

Pre-alarm Fire and Fault volt free relay contacts<br />

28mA, fire & fault relays energised<br />

20mA, current loops, fire & fault relays off<br />

9mA, fire relay energised<br />

-10°c to +55°c<br />

95%, non-condensing<br />

IP65<br />

90° cone<br />

0.1m² n-heptane at 25m<br />

Class 1 (EN54-10)<br />

0.75 to 2.7μm<br />

1 second<br />

6V<br />

2 seconds<br />

Die Cast Zinc Alloy (ZA12), Blue<br />

142mm height x 108mm wide x 82mm depth<br />

2kg<br />

LPCB, AFNOR, NF-SSI, CPD<br />

Dimensions (mm)<br />

Also Available: <strong>Flame</strong>proof (Exd) housings for hazardous areas. ATEX & IECEx approved.<br />

<strong>Flame</strong>proof, <strong>IR</strong>3 flame sensor<br />

<strong>Flame</strong>proof, <strong>IR</strong>3 flame sensor<br />

for high ambient temperatures<br />

Stainless Steel <strong>Flame</strong>proof,<br />

<strong>IR</strong>3 flame sensor<br />

© 2013 <strong>LGM</strong> <strong>Products</strong> <strong>Ltd</strong>. (v11.4)<br />

<strong>LGM</strong> <strong>Products</strong> <strong>Ltd</strong>, Unit 15 Riverside Industrial Park, Farnham, Surrey, GU9 7UG, United Kingdom.<br />

Tel: +44(0)1252 725257 Fax: +44(0)1252 727627 Email: sales@lgmproducts.com Web: www.lgmproducts.com

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!