Circuit-breakers, switch-disconnectors<br />
up to 1600 A<br />
160 Technical data<br />
Fieldbus connection<br />
Dielectric strength<br />
Rating of the air and<br />
EN 50178, UL 508, CSA C22.2, No. 142<br />
creepage distance<br />
Dielectric strength EN 50178<br />
<strong>Moeller</strong> SK1230-1157GB-INT<br />
EASY221-CO EASY222-DN NZM-XDMI-DPV1<br />
Power supply<br />
Rated operational voltage Ue V 24 (-15/+20 %) 24 (-15/+20 %) 24 (-15/+20 %)<br />
Admissible range V DC 20.4 – 28.8 20.4 – 28.8 20.4 – 28.8<br />
Residual ripple % < 5 < 5 < 5<br />
At 24 V DC mA Averaged 200 Averaged 200 Averaged 200<br />
Voltage dips (IEC/EN 61131-2) ms 10 10 10<br />
Heat dissipation at 24 V DC W 4.8 4.8 4.8<br />
Protection against polarity reversal<br />
Power supply Yes Yes Yes<br />
LED displays<br />
Power supply LED RUN (RUN): green LED module status (MS): green LED power (POW): green<br />
LED display LED ERROR (ERR): red LED network status (NS):<br />
red/green<br />
LED-PROFIBUS-DP (BUS): red<br />
Network<br />
Connection types RJ45 5-pole, twin-level terminal block –<br />
Potential isolation Bus to power supply (simple,<br />
bus and power supply to EASY<br />
base unit (safe isolation)<br />
Bus to power supply (simple,<br />
bus and power supply to EASY<br />
base unit (safe isolation)<br />
Function CANopen slave DeviceNet slave –<br />
Interface CAN CAN –<br />
Bus protocol CANopen DeviceNet –<br />
Baud rates Automatic detection up to 1<br />
MBitxs<br />
Bus termination resistors Separate, external bus connection<br />
necessary (120 O)<br />
Bus addresses 1 – 127 via EASY base unit with<br />
display or EASY-SOFT addressable<br />
Automatic detection up to 500<br />
kBitxs<br />
Separate, external bus connection<br />
necessary (120 O)<br />
0 – 63 via EASY base unit with<br />
display or EASY-SOFT addressable<br />
Services –<br />
Cyclic All data R1 – R16, S1 – S8 All data R1 – R16, S1 – S8 –<br />
Acyclic Readxwrite, time, day,<br />
summer-xwinter time, all<br />
parameters of the EASY function<br />
Readxwrite, time, day,<br />
summer-xwinter time, all<br />
parameters of the EASY function<br />
PROFIBUS-DP<br />
Connection types – – Sub-D 9 pole, socket<br />
Potential isolation – – Bus to power supply (simple),<br />
bus and power supply to DMI base<br />
unit (safe isolation)<br />
Function – – PROFIBUS-DP slave<br />
Interface – – RS 485<br />
Bus protocol – – PROFIBUS-DP<br />
Baud rates – – Automatic detection up to<br />
12 MBitxs<br />
Bus termination resistors – – Switch-in via connector<br />
Bus addresses – – 1 – 126 via DMI<br />
For Immediate Delivery call KM<strong>Parts</strong>.com at (866) 595-9616<br />
–<br />
–<br />
–<br />
–<br />
–