Mechanical<br />
Weight: 9kg<br />
Mains Cable Access:<br />
12 x 25.5mm and 1 x 38mm knockouts<br />
Control Cable Access: 1 x 25mm knockouts<br />
Climate Range:<br />
Temperature: +2ºC to +40ºC<br />
Humidity: +5 to 95% non condensing<br />
Control Inputs:<br />
Two sets of terminals for the iCANnet TM network<br />
One RJ12 socket for the programming iCANnet TM network<br />
Suitable for Belden 1502<br />
One set of terminals for the panic/fire alarm input<br />
One set of terminals for the Audio Visual Port, RS485<br />
Optional: DMX512 input card (add X to the end of the part<br />
number)<br />
Dimensions<br />
Electrical<br />
Maximum Load: 40 Amp three phase @ 40ºc<br />
Maximum Channel Current: 10 Amp<br />
Supply: 415/230 volts -/+ 10% 50/60 Hz (optionally, 220/127 volt 60 Hz)<br />
Protection: 10 amp MCBs Type C, 6KA rated<br />
Options<br />
SCH1210S - Single pole with isolator<br />
SCH1210N - Neutral disconnect with isolator<br />
SCH1210D - Double Pole, no isolator<br />
SCH1210RCBO - RCBO Breakers with isolator<br />
SCH1210RCBOX - 12 x SP MCBs with isolator (For field fit of RCBOs)<br />
Load Types:<br />
1-10 volts HF Fluorescent, 100 per channel, 1200 per unit.<br />
Tridonic DSI HF Fluorescent Ballast, 64 per channel, 128 per unit.<br />
Broadcast DALI HF Fluorescent Ballast, 64 per channel, 128 per unit.<br />
0-10 volt Iris control (20K 0hm input)<br />
1-10 volt Multi-Load transformers 1000 (Control only)<br />
Dimmed Outputs:<br />
12 x 1-10 volts at 0.1 Amp sink current per channel<br />
12 x Tridonic DSI outputs (uses electronic power switching in<br />
ballasts)<br />
12 x DALI outputs (uses electronic power switching in ballasts)<br />
The output types above are selectable within iCANedit for each<br />
circuit<br />
Switched Outputs:<br />
12 x 230v 10 Amp (inductive or resistive)<br />
Terminal Sizes:<br />
Incoming supply, max’ cable size: 10mm 2<br />
Ballast output, max’ cable size: 12 pairs x 2.5mm 2<br />
Loads, max’ cable size: 1 x 4mm 2 or 2 x 2.5mm 2 per circuit<br />
iCANnet TM network cable size: 5 x 1mm 2<br />
Audio Visual Port: RS485 2 x 1mm 2<br />
Panic/fire alarm input: 2 x 1mm 2<br />
Memory:<br />
FLASH memory to be able to upgrade firmware<br />
EEPROM for 128 scene memory<br />
Fade Times: 0.1 seconds to 60 minutes<br />
Other HF Ballast Controllers: SCH0410, SCH1220, SCMH0410 and<br />
the SCH1200T<br />
SCH1210 D version - 690x220x155mm.<br />
RCBO & RCBOX version - 550x255x155mm<br />
Typical Schematic<br />
Contact your local Eaton office<br />
20 Greenhill Crescent, Watford Business Park,<br />
Watford, Herts, WD18 8JA. UK<br />
T: +44 (0)1923 495496 F: +44 (0)1923 228796<br />
E: enquiries@<strong>iLight</strong>.co.uk www.<strong>iLight</strong>.co.uk<br />
Eaton Industries Manufacturing GmbH<br />
Electrical Sector EMEA<br />
Route de la Longeraie<br />
71110 Morges, Switzerland<br />
Eaton.eu<br />
© 2015 Eaton<br />
All Rights Reserved<br />
Document No: SCH1210 Rev5 1214<br />
Changes to the products, to the information<br />
contained in this document, and to prices are<br />
reserved; so are errors and omissions.<br />
Eaton is a registered trademark.<br />
All other trademarks are property<br />
of their respective owners.