briefcase series ups 1000brx/drc1000brx
briefcase series ups 1000brx/drc1000brx
briefcase series ups 1000brx/drc1000brx
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Portable, Lightweight 1 kVA Global UPS Systems<br />
BRIEFCASE SERIES UPS 1000BRX/DRC1000BRX<br />
Global input power capabilities of the Briefcase Series<br />
true on-line Uninterruptible Power Supply (UPS) enables<br />
transportable computer and communications systems to be<br />
used worldwide. The lightweight and compact design of the<br />
1000BRX provides self-contained system protection in an<br />
easy-to-carry, “fl yaway” confi guration.<br />
The Briefcase Series UPS provides maximum fl exibility in<br />
a transportable environment. Built using DRS Universal<br />
Power Systems’ patented Intelligent Voltage Selection<br />
(IVS) circuit combined with a matching isolation transformer,<br />
the 1000BRX confi gures and conditions nominal<br />
100/120/220/240 VAC inputs permitting operations from<br />
domestic, international, and fi eld generator power sources.<br />
The 1000BRX also features a comprehensive status and<br />
diagnostic liquid crystal display (LCD), which provides visual<br />
alarms, load percentage, and battery capacity.
HIGHLIGHTS<br />
• Global Input Power<br />
• True on-line uninterruptible power suplly (UPS)<br />
• Lightweight and rugged design<br />
• User-configurable communications<br />
• Liquid crystal display (LCD)<br />
• Input isolation transformer<br />
• Input power factor correction<br />
• Automatic bypass<br />
• Auxiliary output for printers<br />
• Single-point ground<br />
• MIL-STD-810-F<br />
SPECIFICATIONS<br />
ELECTRICAL<br />
Input voltage<br />
100/120/220/240 VAC (automatically sensed and selected)<br />
Input frequency 40 - 65Hz range; 50/60 Hz auto selection; ±3% Hz sync. range window<br />
Max input current 10 A (at 120 VAC )<br />
Input power factor 0.97 typical<br />
Output rating<br />
1000 VA / 700 W<br />
Output voltage<br />
120 VAC ±2% true sinewave, max 5% total harmonic distortion (THD) fullnon-linear load. (The<br />
UPS output rating should be reduced by 10% for the output voltage setting of 100 VAC)<br />
Output frequency 50 or 60 Hz (fi xed selectable; or synchronized to input)<br />
Transfer time to battery uninterrupted (none)<br />
BATTERY<br />
Reserve time<br />
6 minutes at full load<br />
Recharge time 4 hours to 90%<br />
Quantity and type (3) 12 V / 7.2 ampere hours (Ah), valve regulated, non-spillable, lead acid<br />
ENVIRONMENTAL<br />
Ambient temperature<br />
above sea level,<br />
Relative humidity<br />
Operating altitude<br />
Audible noise<br />
MECHANICAL<br />
Dimensions (H x W x D)<br />
Weight without case<br />
with optional case<br />
Input power cord<br />
Output receptacles<br />
0ºC to 40ºC / 32ºF to 104ºF operating for altitudes 0-3,000 m / 0-10,000 feet<br />
-15ºC to 50ºC / 5ºF to 122ºF non-operating<br />
5% to 95% non-condensing<br />
up to 3,000 m / 10,000 feet at 40ºC / 104ºF, 15,000 m / 50,000 feet non-operating<br />
< 56 dBA at 1 m / 3.3 feet<br />
127 mm x 445 mm x 381 mm / 5 inches x 17.5 inches x 15 inches (without case)<br />
21.8 kg / 48 lbs.<br />
30.4 kg / 67 lbs.<br />
1.8 m / 6 feet, with 5-15P plug<br />
(4) 5-15R (UPS), two (2) 5-15R Aux<br />
Specifi cations subject to change without notice.<br />
DRS Universal Power Systems<br />
4230 Lafayette Center Drive, Suite G, Chantilly, VA 20151 Tel 703.378.6100 www.drs.com | information@<strong>ups</strong>i.com 04.09