INVERTER HEAT PUMP MODEL (High COP)<br />
SRF-ZJX<br />
Floor type<br />
A<br />
CLASS<br />
Standard equipment<br />
SRC25ZJX-S, SRC35ZJX-S<br />
SRC50ZIX-S<br />
SRF25ZJX-S, SRF35ZJX-S, SRF50ZJX-S<br />
All SRF-ZJX series can be selected for use as indoor units in<br />
the combination with SCM Multi system outdoor unit.<br />
Our experience, research and development efforts with the floor standing<br />
series have realized the highest COP level in the industry and all models<br />
clear A class level by wide margin. Indoor units are totally new design with<br />
optimum balance of air outlet direction and sufficient air flow volume.<br />
FUNCTION<br />
Self Clean<br />
Operation<br />
Enzyme<br />
Filter<br />
SUN<br />
Filter<br />
Comfortable Functions<br />
Convenient & Economy Functions<br />
Economy<br />
OFF Timer Sleep<br />
On Timer<br />
DRY<br />
24h Timer<br />
Comfortable <strong>Air</strong> Flow Functions<br />
Auto Flap Memory UP/DOWN <strong>Air</strong> outlet<br />
selection<br />
Maintenance & Prevention Functions<br />
Self Detachable<br />
MC Diagnostic<br />
EER in Cooling<br />
5.0<br />
4.5<br />
4.0<br />
3.5<br />
3.0<br />
2.5<br />
4.8<br />
A<br />
CLASS<br />
3.9 3.2<br />
3.6<br />
SRF25ZJX-S SRF35ZJX-S SRF50ZJX-S<br />
Refrigerant pipe length<br />
COP in Heating<br />
A<br />
CLASS<br />
5.0 4.7<br />
4.5<br />
4.0<br />
3.5<br />
3.0<br />
2.5<br />
4.0<br />
3.9<br />
SRF25ZJX-S SRF35ZJX-S SRF50ZJX-S<br />
3.6<br />
22<br />
Others<br />
Back-up<br />
Switch<br />
Auto<br />
Restart<br />
Luminous<br />
SPECIFICATIONS<br />
Item<br />
Power supply<br />
Cooling capacity<br />
Heating capacity<br />
Cooling input<br />
Heating input<br />
Cooling energy label<br />
Heating energy label<br />
EER (In cooling)<br />
COP (In heating)<br />
Running current<br />
Sound power level<br />
*<br />
Sound pressure level<br />
<strong>Air</strong> flow<br />
Exterior dimensions<br />
(HXWXD)<br />
Net weight<br />
Refrigerant piping<br />
Refrigerant<br />
Clean filter<br />
*<br />
Model (Indoor unit/Outdoor unit)<br />
ISO-T1(JIS)<br />
ISO-T1(JIS)<br />
at 230V<br />
at 230V<br />
Cooling<br />
Heating<br />
Cooling(Indoor/Outdoor)<br />
Heating(Indoor/Outdoor)<br />
Cooling(Indoor)<br />
Heating(Indoor)<br />
Indoor Cooling<br />
Heating<br />
Outdoor<br />
Indoor<br />
Outdoor<br />
Indoor/Outdoor<br />
O.D Liquid line<br />
Gas line<br />
Connecting method<br />
kW<br />
kW<br />
kW<br />
kW<br />
A<br />
A<br />
dB(A)<br />
dB(A)<br />
dB(A)<br />
dB(A)<br />
CMM<br />
mm<br />
mm<br />
kg<br />
mm(in)<br />
mm(in)<br />
SRF25ZJX-S<br />
SRC25ZJX-S<br />
2.5(0.9~3.2)<br />
3.4(0.9~4.7)<br />
0.521(0.19~0.82)<br />
0.723(0.23~1.20)<br />
4.80<br />
4.70<br />
2.6/2.5/2.4<br />
3.6/3.4/3.3<br />
51/60<br />
51/60<br />
Hi:40 Me:32 Lo:26<br />
Hi:40 Me:35 Lo:28<br />
Hi:9.0 Me:7.6 Lo:5.8<br />
Hi:10.5 Me:8.2 Lo:6.6<br />
Cooling:29.5 Heating:27.0<br />
Maximum pipe length<br />
15m<br />
Maximum height difference<br />
SRF25ZJX-S, SRF35ZJX-S<br />
SRF35ZJX-S<br />
SRC35ZJX-S<br />
1Phase, 220/230/240V, 50Hz<br />
3.5(0.9~4.1)<br />
4.5(0.9~5.1)<br />
0.890(0.19~1.26)<br />
1.124(0.23~1.43)<br />
A<br />
A<br />
3.93<br />
4.00<br />
4.1/3.9/3.7<br />
5.2/4.9/4.7<br />
52/63<br />
52/62<br />
Hi:41 Me:34 Lo:28<br />
Hi:41 Me:36 Lo:31<br />
Hi:9.2 Me:7.8 Lo:6.4<br />
Hi:10.7 Me:8.3 Lo:7.4<br />
Cooling:32.5 Heating:29.5<br />
600X860X238<br />
SRF50ZJX-S<br />
SRC50ZIX-S<br />
5.0(0.7~5.5)<br />
6.0(0.7~7.0)<br />
1.390(0.2~1.80)<br />
1.540(0.2~2.25)<br />
3.60<br />
3.90<br />
6.4/6.1/5.8<br />
7.1/6.8/6.5<br />
58/62<br />
58/62<br />
Hi:47 Me:39 Lo:30<br />
Hi:47 Me:39 Lo:32<br />
Hi:11.5 Me:9.6 Lo:6.6<br />
Hi:12.0 Me:10.0 Lo:7.6<br />
Cooling:36.0 Heating:33.0<br />
The data are measured under the following conditions(ISO-T1). Cooling: Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Heating: Indoor temp. of 20°CDB, and outdoor temp. of 7°CDB, 6°CWB.<br />
Indicates the value in an anechoic chamber.During operation these values are somewhat higher due to ambient conditions.<br />
*<br />
10m<br />
Maximum pipe length<br />
30m<br />
Maximum height difference<br />
20m<br />
SRF50ZJX-S<br />
595X780(+62)X290<br />
640X800(+71)X290<br />
18/38<br />
19/38<br />
19/43<br />
6.35 (1/4")<br />
9.52 (3/8")<br />
12.7(1/2'')<br />
Flare connecting<br />
R410A<br />
Natural Enzyme FilterX1 Photocatalytic Washable Deodorizing FilterX1