VRp-ILc - Westek Electronics
VRp-ILc - Westek Electronics
VRp-ILc - Westek Electronics
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Outdoor-<strong>VRp</strong>-<strong>ILc</strong>-15000/30000-5339 ~ 15/30kVA, 400 vac delta,230/400 vac wye<br />
Outdoor<br />
<strong>VRp</strong>-<strong>ILc</strong><br />
Outdoor <strong>VRp</strong>-<strong>ILc</strong><br />
models<br />
15000-5339<br />
15 kVA<br />
15 kW<br />
input<br />
400Vdelta<br />
output<br />
230/400V wye<br />
three phase<br />
30000-5339<br />
30 kVA<br />
30 kW<br />
input<br />
400Vdelta<br />
output<br />
230/400V wye<br />
three phase<br />
Power with a<br />
Precision Attitude<br />
TSi Power Corporation<br />
1103 West Pierce Ave<br />
Antigo, WI 54409 USA<br />
800 874 3160 (USA only)<br />
Phone +1 715 623 0636<br />
Fax +1 715 623 2426<br />
sales@tsipower.com<br />
www.tsipower.com<br />
Copyright © 2007 TSi<br />
TSi Power’s Outdoor <strong>VRp</strong>-<strong>ILc</strong> automatic<br />
precision voltage regulator with built-in<br />
low-impedance isolation transformer<br />
allows trouble-free operation of electronic<br />
equipment over a very wide mains ac<br />
voltage range of 400V+/-20% found in<br />
many developing countries.<br />
There is no switching of taps nor any break<br />
in the power path thanks to continuous<br />
pulse width modulation (PWM) switching of<br />
a buck-boost transformer primary winding.<br />
Typical applications<br />
Designed for applications where absolutely<br />
safe and precisely regulated ac power is<br />
required, such as radio base stations (RBS),<br />
telecommunication transmission sites for<br />
backhaul (including microwave links), TV/<br />
radio broadcasting, industrial equipment and<br />
end-of-line utility equipment.<br />
Outdoor <strong>VRp</strong>-<strong>ILc</strong> Series<br />
Precision Voltage Regulator + Isolation Transformer<br />
International Precision voltage regulator Isolation transformer<br />
Precision PWM Automatic Voltage<br />
Regulator with Isolation Transformer,<br />
Automatic Bypass and Automatic Cutoff<br />
Key Outdoor <strong>VRp</strong>-<strong>ILc</strong> features<br />
• Outstanding voltage regulation<br />
performance:<br />
output is within 230/400vac+/-3%<br />
under a normal input range<br />
of 400vac +/-20%<br />
• No switching of power path and<br />
unit always starts up on sine wave<br />
zero crossing<br />
• Over-voltage cutoff, with automatic<br />
restart when ac mains voltage<br />
returns to normal (safe) condition<br />
• Failsafe: automatic bypass (even<br />
during bypass, the over-voltage<br />
protection is active)<br />
• Lightweight design<br />
<strong>VRp</strong>-<strong>ILc</strong><br />
provides<br />
continuous,<br />
fast, no-break<br />
voltage regulation<br />
• A three phase low-impedance<br />
isolation transformer is used<br />
for maximum reliability<br />
• Coordinated surge protection<br />
per IEC61312<br />
• Advanced noise and interference<br />
filter reduces dV/dt from<br />
6kV/µs to less than 10V/µs<br />
• Pedestal-mountable cabinet<br />
• Common-mode noise elimination<br />
• IP23 outer enclosure with sensitive<br />
components housed in an IP55<br />
inner case (overall equivalent to<br />
IP44/NEMA-3R)<br />
• Two year warranty<br />
203
204 Outdoor <strong>VRp</strong>-<strong>ILc</strong> Series<br />
Outdoor-<strong>VRp</strong>-<strong>ILc</strong>-15000/30000-5339<br />
Outdoor<br />
<strong>VRp</strong>-<strong>ILc</strong><br />
Outdoor rated<br />
precision PWM<br />
voltage regulator<br />
with isolation<br />
transformer<br />
Power with a<br />
Precision Attitude<br />
Key Outdoor <strong>VRp</strong>-<strong>ILc</strong> benefits<br />
The lightweight, high efficiency Outdoor <strong>VRp</strong>-<strong>ILc</strong> is easy to install in outdoor<br />
environments. The unit comes in a specially designed outdoor rated enclosure<br />
with multiple air exhaust fans. To maximize cooling, the isolation transformer is<br />
housed in an IP23 outer enclosure. Sensitive components are housed in an IP55<br />
inner case. Overall equivalent is to an IP44(NEMA-3R) enclosure.<br />
The automatic bypass assures that connected equipment will not shut down,<br />
even if <strong>VRp</strong>-<strong>ILc</strong> fails. <strong>VRp</strong>-<strong>ILc</strong> is compatible with all loads as it does not switch<br />
any components in the power path. <strong>VRp</strong>-<strong>ILc</strong>’s ultra-low impedance assures<br />
stability even with the most demanding loads.<br />
The automatic over-voltage cutoff with automatic restart ensures that operation<br />
is off-line during serious over-voltage situations that could damage the system<br />
and/or load, and then restarts without intervention when the ac mains voltage<br />
returns to the normal operating range.<br />
The <strong>ILc</strong> isolation line conditioner components provide maximum equipment<br />
protection against surges, spikes and transients, for higher equipment reliability<br />
and maximum equipment operating life. In addition, the <strong>VRp</strong>-<strong>ILc</strong> offers<br />
improved repeatability, fewer reboots or system lock-ups. A reduction in<br />
equipment down time and service costs can also be expected.<br />
How the Outdoor <strong>VRp</strong>-<strong>ILc</strong> works<br />
The high frequency insulated gate bi-polar transistor (IGBT) driven converter<br />
takes the incoming ac power, measures against the nominal voltage and adds<br />
or subtracts voltage, 20,000 times per second, to achieve precisely regulated<br />
230/400 vac three phase output.<br />
The Automatic Bypass will be activated when there is a fault condition.<br />
A green LED indicates normal regulated protected mode operation.<br />
The over-voltage cutoff is activated whenever the ac mains voltage becomes<br />
dangerously high (over 475vac). It automatically restarts whenever ac mains<br />
voltage is restored to a safe level.<br />
At extremely low ac input conditions it can be operated at limited duty cycle.<br />
A low-impedance isolation transformer provides complete isolation between the<br />
primary and secondary, and permits bonding between output neutral to ground,<br />
which completely eliminates all disturbances between neutral and ground.<br />
The leakage inductance of the isolation transformer, in combination with<br />
capacitive elements and metal oxide varistors (MOVs), provide superb noise<br />
filtering, as well as coordinated multi-stage surge protection in accordance with<br />
the principles of IEC-61312. Multiple cooling fans control the unit’s internal<br />
temperature, with intakes at the bottom of the unit and exhaust through the top<br />
rear of the unit, protected with a rain guard/sunshield.<br />
TSi Power Corporation<br />
1103 West Pierce Ave<br />
Antigo, WI 54409 USA<br />
800 874 3160 (USA only)<br />
Phone +1 715 623 0636<br />
Fax +1 715 623 2426<br />
sales@tsipower.com<br />
www.tsipower.com<br />
Copyright © 2007 TSi
Outdoor<br />
<strong>VRp</strong>-<strong>ILc</strong><br />
Outdoor precision<br />
PWM voltage<br />
regulator with<br />
isolation transformer<br />
Specifications<br />
Power with a<br />
Precision Attitude<br />
TSi’s ongoing product<br />
improvement process makes<br />
specifications subject to<br />
change. Other companies<br />
product names herein are for<br />
identification purposes only,<br />
and may be trademarks of<br />
their respective companies.<br />
TSi Power Corporation<br />
1103 West Pierce Ave<br />
Antigo, WI 54409 USA<br />
800 874 3160 (USA only)<br />
Phone +1 715 623 0636<br />
Fax +1 715 623 2426<br />
sales@tsipower.com<br />
www.tsipower.com<br />
Copyright © 2007 TSi<br />
Specifications<br />
Precision Voltage Regulator + Isolation Transformer<br />
Specification 15000-5339 30000-5339<br />
Electrical<br />
Capacity in VA (watts) 15kVA (15kW) 30kVA (30kW)<br />
Regulator technology<br />
Transformer type<br />
Input<br />
Nominal voltage<br />
Normal operating range<br />
Nominal frequency<br />
High frequency IGBT driven voltage regulation converter<br />
Three phase isolation transformer used<br />
Three phase delta: 400 volts ac<br />
400 volts ac +/-25% at limited duty cycle<br />
47 to 63 Hz<br />
Input circuit breaker<br />
Input circuit breaker with limited inrush current capability.<br />
Over-voltage cutoff<br />
with auto-restart<br />
Over-voltage cutoff activated when >475vac with<br />
automatic restart when voltage returns to normal.<br />
Circuit breaker rating 40A 60A<br />
Input wire size 10mm 2 (AWG 8) 15mm 2 (AWG 6)<br />
Ac connection Terminal block (L1, L2, L3 and ground wires) provided.<br />
Output<br />
Nominal voltage Three phase wye: 230/400 volts ac<br />
Power efficiency<br />
95% maximum<br />
Voltage regulation Better than +/-3%<br />
Automatic bypass<br />
Overload protection<br />
Surge protection<br />
System status indicator<br />
Surge test conditions<br />
Surge let-through<br />
voltages<br />
Common mode filtering<br />
Normal mode filtering<br />
Automatic bypass will be activated when there is a fault condition.<br />
Output circuit breaker provides protection against overload conditions.<br />
A three-stage surge protection system consisting of isolation<br />
transformer, capacitor and MOV is included.<br />
Green LED indicates Normal (regulating) mode operation.<br />
Class 2 and Class 3 Simulated lightning surge (Combination wave)<br />
Per ANSI/IEEE C62.41-1991, Cat. C test waveform: 6kV,3kA,8x20µs.<br />
Optional Class 1 surge arrester available for primary protection.<br />
Single pulse: L-N: 50 V, L-G: 50V, N-G: 0.5V<br />
Ring wave: L-N: 20V, L-G: 20V, N-G: 0.5V<br />
Combination wave: L-N: 250V, L-G: 250V, N-G: 0.5V<br />
Measured rate of voltage rise/fall (dV/dt) of the remnant waveform<br />
is less than 10V/µs with input test waveform dV/dt of 6kV/µs.<br />
Neutral-ground bond eliminates all noise or voltage on neutral (< 0.5V)<br />
A built-in inductor-capacitor filter attenuates EMI/RFI noise from output.<br />
Circuit breaker rating 30A 50A<br />
Output wire size 6mm 2 (AWG 10) 15mm 2 (AWG 6)<br />
Ac connection Terminal block (L1, L2, L3, neutral and ground wires) provided.<br />
Physical<br />
Dimensions 1040mm(40.9”)wide<br />
450mm(17.7”)deep<br />
1170mm(46.1”)high<br />
1150mm(45.3”)wide<br />
600mm(23.6”)deep<br />
1300mm(51.2”) high<br />
Weight 250kg (550 lbs) 450kg(990 lbs)<br />
Safety<br />
Standards Designed to meet IEC 60950 standards.<br />
Environmental<br />
Ambient temperature<br />
-20 o to +40 o C(-4 o to +104 o F).<br />
Cooling method Multiple air exhaust fans are used.<br />
Weather protection<br />
Warranty<br />
Warranty<br />
IP23 outer enclosure with sensitive components housed in<br />
an IP55 inner case (overall equivalent to IP44/NEMA-3R).<br />
Two year limited warranty, parts and labor.<br />
205
206 Outdoor <strong>VRp</strong>-<strong>ILc</strong> Series<br />
Outdoor-<strong>VRp</strong>-<strong>ILc</strong>-15000/30000-5339<br />
Outdoor<br />
<strong>VRp</strong>-<strong>ILc</strong><br />
1040mm<br />
(40.9”)<br />
450mm<br />
(17.7”)<br />
model<br />
-15000<br />
model<br />
-30000<br />
600mm<br />
(23.6”)<br />
the Outdoor <strong>VRp</strong>-<strong>ILc</strong> provides<br />
excellent protection, superior<br />
thermal management and<br />
ease of installation<br />
1150mm<br />
(45.3”)<br />
1170mm<br />
(46.1”)<br />
hot air<br />
exhaust<br />
front panel<br />
is a hinged<br />
door with locks<br />
1300mm<br />
(51.2”)<br />
ventilated<br />
base<br />
Right side rear view<br />
input/output<br />
cable glands openings<br />
Front right side view<br />
Outdoor <strong>VRp</strong>-<strong>ILc</strong> system architecture (per phase)<br />
input<br />
400vac<br />
+/-20%<br />
L1<br />
L2<br />
3 phase<br />
circuit breaker<br />
ground<br />
surge<br />
prot.<br />
and<br />
noise<br />
filter<br />
isolation transformer<br />
buck-boost<br />
transformer<br />
ac<br />
dc<br />
ground<br />
automatic bypass<br />
over-voltage<br />
cutoff<br />
microprocessor<br />
control<br />
noise<br />
filter<br />
<strong>VRp</strong>-<strong>ILc</strong><br />
output<br />
230vac<br />
+/-3%<br />
N<br />
L<br />
G<br />
TSi Power Corporation<br />
1103 West Pierce Ave<br />
Antigo, WI 54409 USA<br />
800 874 3160 (USA only)<br />
Phone +1 715 623 0636<br />
Fax +1 715 623 2426<br />
sales@tsipower.com<br />
www.tsipower.com<br />
Copyright © 2007 TSi<br />
three separate<br />
buck-boost<br />
transformers<br />
delta to wye<br />
transformer<br />
ac surge<br />
protection and<br />
filter module<br />
cold air entry<br />
through mesh<br />
Inside view<br />
hot air exhaust<br />
via multiple fans<br />
(not shown)<br />
<strong>VRp</strong> electronic<br />
module with fans<br />
ac input/output<br />
connection<br />
terminals<br />
ac input/output<br />
via cable glands<br />
Outdoor-<strong>VRp</strong>-<strong>ILc</strong>-15000-30000-5339-2007-02-15.pdf