Outdoor-<strong>VRp</strong>-<strong>ILc</strong>-15000/30000-5339 ~ 15/30kVA, 400 vac delta,230/400 vac wye<br />

Outdoor<br />

<strong>VRp</strong>-<strong>ILc</strong><br />

Outdoor <strong>VRp</strong>-<strong>ILc</strong><br />

models<br />

15000-5339<br />

15 kVA<br />

15 kW<br />

input<br />

400Vdelta<br />

output<br />

230/400V wye<br />

three phase<br />

30000-5339<br />

30 kVA<br />

30 kW<br />

input<br />

400Vdelta<br />

output<br />

230/400V wye<br />

three phase<br />

Power with a<br />

Precision Attitude<br />

TSi Power Corporation<br />

1103 West Pierce Ave<br />

Antigo, WI 54409 USA<br />

800 874 3160 (USA only)<br />

Phone +1 715 623 0636<br />

Fax +1 715 623 2426<br />

sales@tsipower.com<br />

www.tsipower.com<br />

Copyright © 2007 TSi<br />

TSi Power’s Outdoor <strong>VRp</strong>-<strong>ILc</strong> automatic<br />

precision voltage regulator with built-in<br />

low-impedance isolation transformer<br />

allows trouble-free operation of electronic<br />

equipment over a very wide mains ac<br />

voltage range of 400V+/-20% found in<br />

many developing countries.<br />

There is no switching of taps nor any break<br />

in the power path thanks to continuous<br />

pulse width modulation (PWM) switching of<br />

a buck-boost transformer primary winding.<br />

Typical applications<br />

Designed for applications where absolutely<br />

safe and precisely regulated ac power is<br />

required, such as radio base stations (RBS),<br />

telecommunication transmission sites for<br />

backhaul (including microwave links), TV/<br />

radio broadcasting, industrial equipment and<br />

end-of-line utility equipment.<br />

Outdoor <strong>VRp</strong>-<strong>ILc</strong> Series<br />

Precision Voltage Regulator + Isolation Transformer<br />

International Precision voltage regulator Isolation transformer<br />

Precision PWM Automatic Voltage<br />

Regulator with Isolation Transformer,<br />

Automatic Bypass and Automatic Cutoff<br />

Key Outdoor <strong>VRp</strong>-<strong>ILc</strong> features<br />

• Outstanding voltage regulation<br />

performance:<br />

output is within 230/400vac+/-3%<br />

under a normal input range<br />

of 400vac +/-20%<br />

• No switching of power path and<br />

unit always starts up on sine wave<br />

zero crossing<br />

• Over-voltage cutoff, with automatic<br />

restart when ac mains voltage<br />

returns to normal (safe) condition<br />

• Failsafe: automatic bypass (even<br />

during bypass, the over-voltage<br />

protection is active)<br />

• Lightweight design<br />

<strong>VRp</strong>-<strong>ILc</strong><br />

provides<br />

continuous,<br />

fast, no-break<br />

voltage regulation<br />

• A three phase low-impedance<br />

isolation transformer is used<br />

for maximum reliability<br />

• Coordinated surge protection<br />

per IEC61312<br />

• Advanced noise and interference<br />

filter reduces dV/dt from<br />

6kV/µs to less than 10V/µs<br />

• Pedestal-mountable cabinet<br />

• Common-mode noise elimination<br />

• IP23 outer enclosure with sensitive<br />

components housed in an IP55<br />

inner case (overall equivalent to<br />

IP44/NEMA-3R)<br />

• Two year warranty<br />

203


204 Outdoor <strong>VRp</strong>-<strong>ILc</strong> Series<br />

Outdoor-<strong>VRp</strong>-<strong>ILc</strong>-15000/30000-5339<br />

Outdoor<br />

<strong>VRp</strong>-<strong>ILc</strong><br />

Outdoor rated<br />

precision PWM<br />

voltage regulator<br />

with isolation<br />

transformer<br />

Power with a<br />

Precision Attitude<br />

Key Outdoor <strong>VRp</strong>-<strong>ILc</strong> benefits<br />

The lightweight, high efficiency Outdoor <strong>VRp</strong>-<strong>ILc</strong> is easy to install in outdoor<br />

environments. The unit comes in a specially designed outdoor rated enclosure<br />

with multiple air exhaust fans. To maximize cooling, the isolation transformer is<br />

housed in an IP23 outer enclosure. Sensitive components are housed in an IP55<br />

inner case. Overall equivalent is to an IP44(NEMA-3R) enclosure.<br />

The automatic bypass assures that connected equipment will not shut down,<br />

even if <strong>VRp</strong>-<strong>ILc</strong> fails. <strong>VRp</strong>-<strong>ILc</strong> is compatible with all loads as it does not switch<br />

any components in the power path. <strong>VRp</strong>-<strong>ILc</strong>’s ultra-low impedance assures<br />

stability even with the most demanding loads.<br />

The automatic over-voltage cutoff with automatic restart ensures that operation<br />

is off-line during serious over-voltage situations that could damage the system<br />

and/or load, and then restarts without intervention when the ac mains voltage<br />

returns to the normal operating range.<br />

The <strong>ILc</strong> isolation line conditioner components provide maximum equipment<br />

protection against surges, spikes and transients, for higher equipment reliability<br />

and maximum equipment operating life. In addition, the <strong>VRp</strong>-<strong>ILc</strong> offers<br />

improved repeatability, fewer reboots or system lock-ups. A reduction in<br />

equipment down time and service costs can also be expected.<br />

How the Outdoor <strong>VRp</strong>-<strong>ILc</strong> works<br />

The high frequency insulated gate bi-polar transistor (IGBT) driven converter<br />

takes the incoming ac power, measures against the nominal voltage and adds<br />

or subtracts voltage, 20,000 times per second, to achieve precisely regulated<br />

230/400 vac three phase output.<br />

The Automatic Bypass will be activated when there is a fault condition.<br />

A green LED indicates normal regulated protected mode operation.<br />

The over-voltage cutoff is activated whenever the ac mains voltage becomes<br />

dangerously high (over 475vac). It automatically restarts whenever ac mains<br />

voltage is restored to a safe level.<br />

At extremely low ac input conditions it can be operated at limited duty cycle.<br />

A low-impedance isolation transformer provides complete isolation between the<br />

primary and secondary, and permits bonding between output neutral to ground,<br />

which completely eliminates all disturbances between neutral and ground.<br />

The leakage inductance of the isolation transformer, in combination with<br />

capacitive elements and metal oxide varistors (MOVs), provide superb noise<br />

filtering, as well as coordinated multi-stage surge protection in accordance with<br />

the principles of IEC-61312. Multiple cooling fans control the unit’s internal<br />

temperature, with intakes at the bottom of the unit and exhaust through the top<br />

rear of the unit, protected with a rain guard/sunshield.<br />

TSi Power Corporation<br />

1103 West Pierce Ave<br />

Antigo, WI 54409 USA<br />

800 874 3160 (USA only)<br />

Phone +1 715 623 0636<br />

Fax +1 715 623 2426<br />

sales@tsipower.com<br />

www.tsipower.com<br />

Copyright © 2007 TSi


Outdoor<br />

<strong>VRp</strong>-<strong>ILc</strong><br />

Outdoor precision<br />

PWM voltage<br />

regulator with<br />

isolation transformer<br />

Specifications<br />

Power with a<br />

Precision Attitude<br />

TSi’s ongoing product<br />

improvement process makes<br />

specifications subject to<br />

change. Other companies<br />

product names herein are for<br />

identification purposes only,<br />

and may be trademarks of<br />

their respective companies.<br />

TSi Power Corporation<br />

1103 West Pierce Ave<br />

Antigo, WI 54409 USA<br />

800 874 3160 (USA only)<br />

Phone +1 715 623 0636<br />

Fax +1 715 623 2426<br />

sales@tsipower.com<br />

www.tsipower.com<br />

Copyright © 2007 TSi<br />

Specifications<br />

Precision Voltage Regulator + Isolation Transformer<br />

Specification 15000-5339 30000-5339<br />

Electrical<br />

Capacity in VA (watts) 15kVA (15kW) 30kVA (30kW)<br />

Regulator technology<br />

Transformer type<br />

Input<br />

Nominal voltage<br />

Normal operating range<br />

Nominal frequency<br />

High frequency IGBT driven voltage regulation converter<br />

Three phase isolation transformer used<br />

Three phase delta: 400 volts ac<br />

400 volts ac +/-25% at limited duty cycle<br />

47 to 63 Hz<br />

Input circuit breaker<br />

Input circuit breaker with limited inrush current capability.<br />

Over-voltage cutoff<br />

with auto-restart<br />

Over-voltage cutoff activated when >475vac with<br />

automatic restart when voltage returns to normal.<br />

Circuit breaker rating 40A 60A<br />

Input wire size 10mm 2 (AWG 8) 15mm 2 (AWG 6)<br />

Ac connection Terminal block (L1, L2, L3 and ground wires) provided.<br />

Output<br />

Nominal voltage Three phase wye: 230/400 volts ac<br />

Power efficiency<br />

95% maximum<br />

Voltage regulation Better than +/-3%<br />

Automatic bypass<br />

Overload protection<br />

Surge protection<br />

System status indicator<br />

Surge test conditions<br />

Surge let-through<br />

voltages<br />

Common mode filtering<br />

Normal mode filtering<br />

Automatic bypass will be activated when there is a fault condition.<br />

Output circuit breaker provides protection against overload conditions.<br />

A three-stage surge protection system consisting of isolation<br />

transformer, capacitor and MOV is included.<br />

Green LED indicates Normal (regulating) mode operation.<br />

Class 2 and Class 3 Simulated lightning surge (Combination wave)<br />

Per ANSI/IEEE C62.41-1991, Cat. C test waveform: 6kV,3kA,8x20µs.<br />

Optional Class 1 surge arrester available for primary protection.<br />

Single pulse: L-N: 50 V, L-G: 50V, N-G: 0.5V<br />

Ring wave: L-N: 20V, L-G: 20V, N-G: 0.5V<br />

Combination wave: L-N: 250V, L-G: 250V, N-G: 0.5V<br />

Measured rate of voltage rise/fall (dV/dt) of the remnant waveform<br />

is less than 10V/µs with input test waveform dV/dt of 6kV/µs.<br />

Neutral-ground bond eliminates all noise or voltage on neutral (< 0.5V)<br />

A built-in inductor-capacitor filter attenuates EMI/RFI noise from output.<br />

Circuit breaker rating 30A 50A<br />

Output wire size 6mm 2 (AWG 10) 15mm 2 (AWG 6)<br />

Ac connection Terminal block (L1, L2, L3, neutral and ground wires) provided.<br />

Physical<br />

Dimensions 1040mm(40.9”)wide<br />

450mm(17.7”)deep<br />

1170mm(46.1”)high<br />

1150mm(45.3”)wide<br />

600mm(23.6”)deep<br />

1300mm(51.2”) high<br />

Weight 250kg (550 lbs) 450kg(990 lbs)<br />

Safety<br />

Standards Designed to meet IEC 60950 standards.<br />

Environmental<br />

Ambient temperature<br />

-20 o to +40 o C(-4 o to +104 o F).<br />

Cooling method Multiple air exhaust fans are used.<br />

Weather protection<br />

Warranty<br />

Warranty<br />

IP23 outer enclosure with sensitive components housed in<br />

an IP55 inner case (overall equivalent to IP44/NEMA-3R).<br />

Two year limited warranty, parts and labor.<br />

205


206 Outdoor <strong>VRp</strong>-<strong>ILc</strong> Series<br />

Outdoor-<strong>VRp</strong>-<strong>ILc</strong>-15000/30000-5339<br />

Outdoor<br />

<strong>VRp</strong>-<strong>ILc</strong><br />

1040mm<br />

(40.9”)<br />

450mm<br />

(17.7”)<br />

model<br />

-15000<br />

model<br />

-30000<br />

600mm<br />

(23.6”)<br />

the Outdoor <strong>VRp</strong>-<strong>ILc</strong> provides<br />

excellent protection, superior<br />

thermal management and<br />

ease of installation<br />

1150mm<br />

(45.3”)<br />

1170mm<br />

(46.1”)<br />

hot air<br />

exhaust<br />

front panel<br />

is a hinged<br />

door with locks<br />

1300mm<br />

(51.2”)<br />

ventilated<br />

base<br />

Right side rear view<br />

input/output<br />

cable glands openings<br />

Front right side view<br />

Outdoor <strong>VRp</strong>-<strong>ILc</strong> system architecture (per phase)<br />

input<br />

400vac<br />

+/-20%<br />

L1<br />

L2<br />

3 phase<br />

circuit breaker<br />

ground<br />

surge<br />

prot.<br />

and<br />

noise<br />

filter<br />

isolation transformer<br />

buck-boost<br />

transformer<br />

ac<br />

dc<br />

ground<br />

automatic bypass<br />

over-voltage<br />

cutoff<br />

microprocessor<br />

control<br />

noise<br />

filter<br />

<strong>VRp</strong>-<strong>ILc</strong><br />

output<br />

230vac<br />

+/-3%<br />

N<br />

L<br />

G<br />

TSi Power Corporation<br />

1103 West Pierce Ave<br />

Antigo, WI 54409 USA<br />

800 874 3160 (USA only)<br />

Phone +1 715 623 0636<br />

Fax +1 715 623 2426<br />

sales@tsipower.com<br />

www.tsipower.com<br />

Copyright © 2007 TSi<br />

three separate<br />

buck-boost<br />

transformers<br />

delta to wye<br />

transformer<br />

ac surge<br />

protection and<br />

filter module<br />

cold air entry<br />

through mesh<br />

Inside view<br />

hot air exhaust<br />

via multiple fans<br />

(not shown)<br />

<strong>VRp</strong> electronic<br />

module with fans<br />

ac input/output<br />

connection<br />

terminals<br />

ac input/output<br />

via cable glands<br />

Outdoor-<strong>VRp</strong>-<strong>ILc</strong>-15000-30000-5339-2007-02-15.pdf