<strong>NX</strong>W REVERSIBLE CHILLER INSTALLATION MANUAL<br />
Field Connected Water Piping<br />
General<br />
System piping should be kept as simple as possible to<br />
minimize the pressure drop, but hand valves should be field<br />
installed to facilitate unit servicing. The piping installation<br />
should provide service personnel with the ability to measure<br />
and/or monitor water temperatures and pressures.<br />
Source and load fluid connections are provided with 2-inch<br />
[50.8mm] Victaulic grooved nipples (see Figure 4). Each<br />
nipple will also have a PT port installed for test and balance<br />
purposes. It will be the installing contractor’s responsibility<br />
to adequately support incoming piping to avoid damage to<br />
the unit’s piping or heat exchangers. The water lines should<br />
be routed so as not to interfere with access to the unit.<br />
For any installation where the transmission of vibration<br />
through the piping connections could cause unacceptable<br />
noise levels in occupied spaces it is important to provide<br />
adequate vibration damping. One method is to use the<br />
optional Adapter Hose Kit (kit number TKC16S-4). This Kit<br />
consists of four pieces of a braided stainless steel flexible<br />
hose with a 2” Victaulic connection on one end and a 2”<br />
MPT connection with pipe union on the other. Overall length<br />
of each piece is 18”.<br />
NOTE: Units are factory run-tested using propylene glycol.<br />
Prior to connecting piping to unit, thoroughly flush heat<br />
exchangers.<br />
Figure 4: Water Connections (<strong>NX</strong>W360 shown)<br />
Figure 5: <strong>Chiller</strong> Back View (<strong>NX</strong>W360 shown)<br />
Brazed Plate Heat Exchanger<br />
P/T Plug<br />
2” Victaulic<br />
Grooved<br />
Nipples<br />
Optional Connection Kit<br />
CKV160FL (Includes four<br />
of each)<br />
Out<br />
In<br />
Water<br />
Connection<br />
Ports<br />
In<br />
TKC16S-4<br />
(1 of 4)<br />
Out<br />
CAUTION: Remove the plastic protective caps in the ends of each of the four water pipes on the heat<br />
exchangers prior to piping connection. Failure to remove the caps will result in serious damage and could void<br />
the warranty.<br />
10