<strong>NX</strong>W REVERSIBLE CHILLER INSTALLATION MANUAL<br />

Operating Parameters<br />

Heating Mode<br />

Entering<br />

Load Temp (°F)<br />

60<br />

80<br />

100<br />

120<br />

Entering<br />

Source Temp (°F)<br />

Suction<br />

Pressure (psig)<br />

Discharge<br />

Pressure (psig)<br />

Superheat<br />

(°F)<br />

Subcooling<br />

(°F)<br />

30 75-100 200-215 10-12 10-13<br />

50 100-125 200-215 12-14 8-12<br />

70 125-150 215-230 14-18 8-12<br />

90 150-165 230-255 25-30 8-12<br />

30 75-100 285-300 10-12 10-13<br />

50 100-125 300-315 12-14 8-12<br />

70 125-150 315-330 14-18 8-12<br />

90 150-165 330-345 25-30 8-12<br />

30 85-110 365-380 10-12 7-11<br />

50 110-135 385-400 12-14 7-11<br />

70 135-165 400-415 14-18 3-7<br />

50 110-135 485-500 12-14 7-11<br />

70 135-165 500-515 14-18 3-7<br />

NOTE: Operating data based on normal conditions with 3 gpm/ton for the load and source.<br />

1/15/10<br />

Cooling Mode<br />

Entering<br />

Load Temp (°F)<br />

50<br />

70<br />

90<br />

110<br />

Entering<br />

Source Temp (°F)<br />

Suction<br />

Pressure (psig)<br />

Discharge<br />

Pressure (psig)<br />

Superheat<br />

(°F)<br />

Subcooling<br />

(°F)<br />

30 80-90 140-175 15-20 3-6<br />

50 90-100 200-235 11-15 6-9<br />

70 100-110 250-285 11-15 9-12<br />

90 100-120 330-365 8-12 12-14<br />

110 110-130 430-465 8-12 14-19<br />

30 80-90 150-185 15-20 3-6<br />

50 90-100 210-245 11-15 6-9<br />

70 100-110 260-295 11-15 9-12<br />

90 110-120 340-375 8-12 12-14<br />

110 110-140 440-485 8-12 14-19<br />

30 80-90 150-185 15-20 3-6<br />

50 90-100 210-245 11-15 6-9<br />

70 100-110 260-295 11-15 9-12<br />

90 110-120 340-375 8-12 12-14<br />

30 90-100 160-195 40-45 3-6<br />

50 110-130 220-255 30-40 6-9<br />

NOTE: Operating data based on normal conditions with 3 gpm/ton for the load and source.<br />

1/15/10<br />

Compressor Resistance<br />

Model 208-230 460 575<br />

096 0.610 2.330 4.060<br />

108 0.610 2.330 4.060<br />

120 0.562 2.270 3.560<br />

140 0.422 2.200 3.289<br />

180 0.320 1.298 1.999<br />

210 0.320 1.298 1.999<br />

240 0.330 1.110 1.710<br />

360 0.226 0.833 1.268<br />

540 n/a 0.450 0.701<br />

1/15/10<br />