FC-1010 - STI - Specified Technologies Inc
FC-1010 - STI - Specified Technologies Inc
FC-1010 - STI - Specified Technologies Inc
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
2. Through Penetrants - One metallic pipe, conduit or tube installed approximately midway between wood joists. Diam<br />
of openings hole-sawed through flooring system and through gypsum board ceiling to be nom 1/2 in. greater than the<br />
outside diam of through-penetrant. For 1 hr rated floor assemblies, through penetrant to be installed either<br />
concentrically or eccentrically within the opening with an annular space of 0 in. (point contact) to 1/2 in. For 2 hr rated<br />
floor assemblies, through penetrant to be centered in the opening. Pipe, conduit or tube to be rigidly supported on<br />
both sides of floor-ceiling assembly. The following types and sizes of metallic pipes, conduits or tubing may be used:<br />
A. Steel Pipe - Nom 4 in. diam (or smaller) Schedule 5 (or heavier) steel pipe.<br />
B. Iron Pipe - Nom 4 in. diam (or smaller) cast or ductile iron pipe.<br />
C. Conduit - Nom 4 in. diam (or smaller) steel electrical metallic tubing or steel conduit.<br />
D. Copper Pipe - Nom 4 in. diam (or smaller) Regular (or heavier) copper pipe.<br />
E. Copper Tubing - Nom 4 in. diam (or smaller) Type L (or heavier) copper tubing.<br />
The T Rating of the firestop system is dependent upon the hourly rating of the floor-ceiling assembly and type of<br />
through-penetrant used as shown in the table below:<br />
Floor Ceiling Rating Hr<br />
1<br />
1<br />
1<br />
2<br />
2<br />
2<br />
Type of Penetrant<br />
Steel or Iron Pipe<br />
Steel Conduit<br />
Copper Tube or Pipe<br />
Steel or Iron Pipe<br />
Steel Conduit<br />
Copper Tube or Pipe<br />
T Rating Hr<br />
1<br />
1<br />
3/4<br />
1-1/2<br />
1-1/2<br />
1/2<br />
3. Fill, Void or Cavity Material* - Sealant - Fill material forced into annulus to fill space to max extent possible on top<br />
surface of floor and bottom surface of ceiling. Min 3/8 in. diam bead of fill material applied at point contact location on<br />
top surface of floor and on bottom surface of gypsum board ceiling.<br />
SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant<br />
*Bearing the UL Classification Mark<br />
Reproduced courtesy of Underwriters Laboratories, <strong>Inc</strong>.<br />
Created or Revised: January 2, 2009<br />
(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:techserv@stifirestop.com Website:www.stifirestop.com<br />
R<br />
F-C-<strong>1010</strong><br />
PAGE 2 OF 2