Table 602<br />
Table 602 specifies the fire-resistance rating requirements of exterior walls based on fire-separation<br />
distance as well as type of construction <strong>and</strong> occupancy groups.<br />
It is important to compare ratings required in Table 601 <strong>and</strong> table 602<br />
Fire separation distance –defined in section 702<br />
“The distance measured from the building face to the closest interior lot line, to the<br />
centerline of a street, alley or public way, or to an imaginary line between two buildings on the<br />
lot. The distance shall be measured at right angles to the wall”<br />
The fire-resistive requirements decrease with increasing distance between buildings.<br />
they also decrease in relation to decreasing construction type requirements.<br />
Table 602 also builds in assumptions about the hazard of occupancies relative to fire<br />
separation distances – the principle is that increased distances offset the hazards presented by<br />
various occupancies.<br />
The amount of openings allowed in exterior walls is governed in section 7 under Table 704.8