threshold frequency. While the depleted hydro plants may have a thresholdfrequency in 49.0 – 49.2 Hz range, the over-flowing hydro stations may beassigned a threshold frequency <strong>of</strong> 50.5 Hz.This would lead to a frequency - based dispatch <strong>of</strong> <strong>generating</strong> stations(typically as shown in figure - 6), which can be given out by the SLDCs as thedispatch guideline or instructions for their <strong>generating</strong> stations. The underlyingapproach is that the frequency would be allowed to float, and there would beno attempt to operate the grid at a frequency very close to 50.0 Hz. Also,while the schedules would serve as the commercial datum, the entities wouldbe free to deviate from the schedules, to achieve real region - wide merit -order in generation, in an autonomous, decentralized and very cost - effectivemanner, without depending on any communication and EMS / SCADAsystem.Figure - 619