<strong>Specification</strong> - Indoor UnitsSystemDVM PLUS IV HP COMPACT MODULEMODULEMODULEIMAGE MODEL CAPACITY 62 64 66 68 70 72 74 76 78 80SystemRD080*8 HPRD100* 10 HP 1 1RD120* 12 HP 1 2 1 1 1 1 1COMPACTMODULERD140* 14 HP 1 1 1RD160* 16 HP 1 1 1RD180* 18 HP 1 1 1RD200* 20 HP 2 2 2 2 2 3 1 3 3 3 4* If you wish to install outdoor unit module with capacity over 60 HP, please contact local Samsung Dealer.1562012 SAMSUNGSystem Air Conditioner<strong>Specification</strong> - Outdoor Units• High Efficiency• Large Capacity• Advanced and Reliable Protection• Easy Installation & Maintenance• Eco-friendly• Comfortable Operation• Premium Quality Control Heat RecoveryDVM PLUS IV HP COMPACT MODULEDVM PLUS IV HP RD620* RD640*Model NameDVM PLUS IV HP RD620* RD640*Power Supply , #, V, Hz 3, 4, 380~415, 50 3, 4, 380~415, 50Mode - Heat Pump Heat PumpPerformancePowerHP HP 62 64Capacity(Nominal)CoolingHeatingkW 173.6 179.2Btu/h 592400 611500kW 195.3 201.6Btu/h 666400 687900Power InputCooling50.24 52.4kW(Nominal)Heating 44.39 46Current InputCooling98.6 105.6A(Nominal)Heating 89.3 95Circuit Breaker (MCCB+ELB / ELCB) A 175 175Nominal Cooling - 3.46 3.42COPNominal Heating - 4.4 4.38Fan Air Flow Rate CMM (173) x 1 + (210) x 1 + (275) x 2 (210) x 2 + (275) x 2PipingConnectionsLiquid Pipe , mm 22.23 22.23Gas Pipe , mm 44.45 44.45Discharge Gas Pipe (DVM PLUS IV HR) , mm 38.1 38.1Oil Equalizing Pipe , mm 6.35 6.35InstallationMax. Length m 200 200LimitationMax. Height m 110 (40)* 110 (40)*Type - R410a R410aRefrigerantFactory Charging kg 27 27Sound Sound Pressure dB(A) - -ExternalDimensionOperatingTemp. RangeNet WeightDVM PLUS IV HP(237) x 1 + (240) x 1 + (349) x 2 (240) x 2 + (349) x 2kgDVM PLUS IV HR (252) x 1 + (255) x 1 + (370) x 2 (255) x 2 + (370) x 2Shipping WeightDVM PLUS IV HP(880 x 1695 x 765) x 2 + (1295 x 1695 x 765) x 2 (880 x 1695 x 765) x 2 + (1295 x 1695 x 765) x 2kgDVM PLUS IV HR (948 x 1912 x 832) x 2 + (1363 x 1912 x 832) x 2 (948 x 1912 x 832) x 2 + (1363 x 1912 x 832) x 2Net Dimensions (WxHxD) mm -5 ~ 48 -5 ~ 48Shipping Dimensions (WxHxD) mm -20 ~ 24 -20 ~ 24Cooling °C -5 ~ 48 -5 ~ 48Heating °C -20 ~ 24 -20 ~ 24* Product <strong>Specification</strong>s in the Publication can be changed without a prior notice. Because there is always an ongoing improvement on our product.* If you wish to install an outdoor unit module with a capacity of over 60 HP, then please contact your local Samsung Dealer.* The maximum height of installation limitation for piping connections is only allowable when using PDM kits.1572012 SAMSUNGSystem Air Conditioner
<strong>Specification</strong> - Outdoor UnitsSystem1582012 SAMSUNGSystem Air ConditionerDVM PLUS IV HP COMPACT MODULEDVM PLUS IV HP RD660* RD680* RD700* RD720* RD740*Model NameDVM PLUS IV HP RD660* RD680* RD700* RD720* RD740*Power Supply , #, V, Hz 3, 4, 380~415, 50 3, 4, 380~415, 50 3, 4, 380~415, 50 3, 4, 380~415, 50 3, 4, 380~415, 50Mode - Heat Pump Heat Pump Heat Pump Heat Pump Heat PumpPerformancePowerDVM PLUS IV HP RD760* RD780* RD800*Model NameDVM PLUS IV HP RD760* RD780* RD800*Power Supply , #, V, Hz 3, 4, 380~415, 50 3, 4, 380~415, 50 3, 4, 380~415, 50Mode - Heat Pump Heat Pump Heat PumpPerformancePowerHP HP 76 78 80Capacity(Nominal)CoolingHeatingkW 212.8 218.4 224Btu/h 726200 745300 764400kW 239.4 245.7 252Btu/h 816900 838400 859900Power InputCooling63 66.7 68kW(Nominal)Heating 54.8 56.4 58Current InputCooling120.4 129.7 131.2A(Nominal)Heating 114.5 114 116.4Circuit Breaker (MCCB+ELB / ELCB) A 200 200 200Nominal Cooling - 3.38 3.27 3.29COPNominal Heating - 4.37 4.36 4.34Fan Air Flow Rate CMM (250) x 1 + (275) x 3 (270) x 1 + (275) x 3 (275) x 4PipingConnectionsLiquid Pipe , mm 22.23 22.23 22.23Gas Pipe , mm 50.8 50.8 50.8Discharge Gas Pipe (DVM PLUS IV HR) , mm 44.45 44.45 44.45Oil Equalizing Pipe , mm 6.35 6.35 6.35InstallationMax. Length m 200 200 200LimitationMax. Height m 110 (40)* 110 (40)* 110 (40)*Type - R410a R410a R410aRefrigerantFactory Charging kg 32.5 34 34Sound Sound Pressure dB(A) - - -ExternalDimensionOperatingTemp. RangeHP HP 66 68 70 72 74Capacity(Nominal)CoolingHeatingNet WeightDVM PLUS IV HP(329) x 1 + (349) x 3 (340) x 1 + (349) x 3 (349) x 4kgDVM PLUS IV HR (349) x 1 + (370) x 3 (360) x 1 + (370) x 3 (370) x 4Shipping WeightDVM PLUS IV HP(1295 x 1695 x 765) x 4 (1295 x 1695 x 765) x 4 (1295 x 1695 x 765) x 4kgDVM PLUS IV HR (1363 x 1912 x 832) x 4 (1363 x 1912 x 832) x 4 (1363 x 1912 x 832) x 4Net Dimensions (WxHxD) mm -5 ~ 48 -5 ~ 48 -5 ~ 48Shipping Dimensions (WxHxD) mm -20 ~ 24 -20 ~ 24 -20 ~ 24Cooling °C -5 ~ 48 -5 ~ 48 -5 ~ 48Heating °C -20 ~ 24 -20 ~ 24 -20 ~ 24* Product <strong>Specification</strong>s in the Publication can be changed without a prior notice. Because there is always an ongoing improvement on our product.* If you wish to install an outdoor unit module with a capacity of over 60 HP, then please contact your local Samsung Dealer.* The maximum height of installation limitation for piping connections is only allowable when using PDM kits.kW 184.8 190.4 196 201.6 207.2Btu/h 630600 649700 668800 687900 707000kW 207.9 214.2 220.5 226.8 233.1Btu/h 709400 730900 752400 773900 795400Power InputCooling53.3 55.2 58.9 60.2 61.1kW(Nominal)Heating 47.15 48.8 50.4 52 53.15Current InputCooling106.5 107.6 116.9 118.4 119.3A(Nominal)Heating 96 103.8 103.3 105.7 106.7Circuit Breaker (MCCB+ELB / ELCB) A 175 175 200 200 200Nominal Cooling - 3.47 3.45 3.33 3.35 3.39COPNominal Heating - 4.41 4.39 4.38 4.36 4.39Fan Air Flow Rate CMM (210) x 2 + (275) x 2 (210) x 1 + (250) x 1 + (275) x 2 (210) x 1 + (270) x 1 + (275) x 2 (210) x 1 + (275) x 3 (210) x 1 + (275) x 3PipingConnectionsLiquid Pipe , mm 22.23 22.23 22.23 22.23 22.23Gas Pipe , mm 50.8 50.8 50.8 50.8 50.8Discharge Gas Pipe (DVM PLUS IV HR) , mm 44.45 44.45 44.45 44.45 44.45Oil Equalizing Pipe , mm 6.35 6.35 6.35 6.35 6.35InstallationMax. Length m 200 200 200 200 200LimitationMax. Height m 110 (40)* 110 (40)* 110 (40)* 110 (40)* 110 (40)*Type - R410a R410a R410a R410a R410aRefrigerantFactory Charging kg 29 29 30.5 30.5 32.5Sound Sound Pressure dB(A) - - - - -ExternalDimensionOperatingTemp. RangeNet WeightDVM PLUS IV HP(240) x 1 + (280) x 1 + (349) x 2 (240) x 1 + (329) x 1 + (349) x 2 (240) x 1 + (340) x 1 + (349) x 2 (240) x 1 + (349) x 3 (280) x 1 + (349) x 3kgDVM PLUS IV HR (255) x 1 + (301) x 1 + (370) x 2 (255) x 1 + (349) x 1 + (370) x 2 (255) x 1 + (360) x 1 + (370) x 2 (255) x 1 + (370) x 3 (301) x 1 + (370) x 3DVM PLUS IV HP(880 x 1695 x 765) x 1 + (1295 x 1695 x 765) x 3 (880 x 1695 x 765) x 1 + (1295 x 1695 x 765) x 3 (880 x 1695 x 765) x 1 + (1295 x 1695 x 765) x 3 (880 x 1695 x 765) x 1 + (1295 x 1695 x 765) x 3 (1295 x 1695 x 765) x 4Shipping Weightkg (948 x 1912 x 832) x 1 + (1268 x 1912 x 832) x 1DVM PLUS IV HR+ (1363 x 1912 x 832) x 2(948 x 1912 x 832) x 1 + (1363 x 1912 x 832) x 3 (948 x 1912 x 832) x 1 + (1363 x 1912 x 832) x 3 (948 x 1912 x 832) x 1 + (1363 x 1912 x 832) x 3 (1268 x 1912 x 832) x 1 + (1363 x 1912 x 832) x 3Net Dimensions (WxHxD) mm -5 ~ 48 -5 ~ 48 -5 ~ 48 -5 ~ 48 -5 ~ 48Shipping Dimensions (WxHxD) mm -20 ~ 24 -20 ~ 24 -20 ~ 24 -20 ~ 24 -20 ~ 24Cooling °C -5 ~ 48 -5 ~ 48 -5 ~ 48 -5 ~ 48 -5 ~ 48Heating °C -20 ~ 24 -20 ~ 24 -20 ~ 24 -20 ~ 24 -20 ~ 24DVM PLUS IV HP COMPACT MODULESystem1592012 SAMSUNGSystem Air Conditioner