10. CONNECTING MAGNASTARTS IN PARALLELThe maximum <strong>Magnastart</strong> rating is 370kW, but it may be desired to start a higher ratedmotor. In this case it is sometimes possible to connect 2 or more M350 <strong>Magnastart</strong>s inparallel to achieve a larger combined rating. This should only be considered for ratingsabove 370kW, it is normally more reliable (and more economic) to use a single, correctlysized <strong>Magnastart</strong> for lower ratings.In case <strong>Magnastart</strong>s are connected in parallel the following criteria MUST be applied.i) The <strong>Magnastart</strong>s are all tapped identically, andii) The Cut-outs on all units are wired in series, so that if any unit overheats, thesystem trips.iii) The system is de-rated by 10% to allow for mismatch of individual units.iv) The rotor voltage must not exceed the <strong>Magnastart</strong> rating.It will be obvious that operating in parallel will reduce the combined maximum impedance,so this arrangement functions best with lower voltage rotors. If this is problematic, then aseries/parallel combination could be considered, and must be designed specifically for theapplication by a competent Electrical Engineer.Since the success of this use is very dependant on the motor and system design, IRISPOWERdoes not guarantee that parallel operation will be successful in all cases, and theuser must satisfy themselves that the application is appropriate.Page 16 V1.3

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!