7.2. Double-float <strong>Buchholz</strong> relays with flanged connection (round)<br />

Type<br />

Internal description<br />

DIN description<br />

05<br />

(BF 25/6)<br />

(-)<br />

06<br />

(BF 25/10)<br />

(DR 25)<br />

23<br />

(BF 25/10 S)<br />

(-)<br />

07<br />

(BF 50/6)<br />

(-)<br />

08<br />

(BF 50/10)<br />

(DR 50)<br />

09<br />

(BF 80/10)<br />

(-)<br />

09-26.<br />

(BF80/10/8)<br />

(DR 80)<br />

24<br />

(BF 80/6)<br />

(-)<br />

Type of connection<br />

Pipe<br />

diameter<br />

DN (mm)<br />

Flange dimensions<br />

(mm)<br />

Device dimensions<br />

(mm) Weight<br />

(kg)<br />

d1 d2 d3 d4 d5 f l h1 h2<br />

Suited for<br />

transformer<br />

ratings of<br />

Flange<br />

4-hole 25 100 75 60 12 12 185 235 90 4,4 ≤5000 KVA<br />

Flange<br />

4-hole 25 115 85 68 14 18 200 235 90 4,8 ≤5000 KVA<br />

Flange<br />

4-hole 25 115 85 68 14 18 200 235 90 4,4 ≤5000 KVA<br />

Flange<br />

4-hole 50 140 110 90 14 12 185 235 80 4,6<br />

Flange<br />

4-hole 50 165 125 102 18 16 195 250 80 5,9<br />

≥5000 KVA<br />

≤10000 KVA<br />

≥5000 KVA<br />

≤10000 KVA<br />

Flange<br />

4-hole 80 200 160 138 18 15 195 265 80 6,2 ≥10000 KVA<br />

Flange<br />

8-hole 80 200 160 138<br />

18<br />

M16<br />

15 195 265 80 6,2 ≥10000 KVA<br />

Flange<br />

4-hole 80 190 150 130 18 15 195 260 80 6,0 ≥10000 KVA<br />