14. Other protection devices<br />

Monitoring relay for tap changers ÜRF 25, ÜRF 25/10, ÜRF 25/10-26<br />

The monitoring relay for tap changers, also known as the protection relay for<br />

tap changers or oil flow relay, is a monitoring device for insulating liquid-filled<br />

tap changers with conservator. It protects the tap changer and the transformer<br />

from damage. The monitoring relay responds to excessive oil flow in the<br />

direction of the conservator and generates a signal disconnecting the tap<br />

changer and the transformer immediately from voltage supply.<br />

Pipe diameter DN: 25 mm (1“)<br />

Type of connection: threaded or flanged<br />

Oil flow indicator SG 25, SF 25, SF 25/10<br />

The oil flow indicator is a protective relay monitoring the circulating oil lubrication<br />

or circulating oil cooling of machines and equipment. It indicates faults<br />

in circulating oil systems or shuts down the machine or equipment, thus preventing<br />

damage. The flow indicator operates at a very low service pressure,<br />

so it can be installed in an oil return pipe where the oil flow is ensured by the<br />

sloping pipe.<br />

Pipe diameter DN: 25 mm (1“)<br />

Type of connection: threaded or flanged<br />

For further information, please ask for special reference material.<br />