3. Technical Radar-Füllstandsmesssysteme<br />

versionsDurchflussmesser (MID)<br />

Type A Type B<br />

Cable structure shielded, twisted-<strong>pa</strong>ir one or several twisted cables with common shielding<br />

Cross-sectional area 0.8 mm2 , AWG 18 0.322 mm, AWG 22<br />

Loop resistance (DC) 44 Ohm/km 112 Ohm/km<br />

Impedance at 31.25 kHz 100 Ohm +/- 20% 100 Ohm +/- 30%<br />

Damping at 39 kHz 3 dBlkm 5 dBlkm<br />

Ca<strong>pa</strong>citive unbalance 2 nF/km 2 nF/km<br />

Percentage coverage <strong>of</strong> the shield 90% -<br />

Max. cable length 1900 m 1200 m<br />

Available fieldbus cables<br />

We recommend using two-core twisted and shielded cables, e.g. the following types:<br />

Manufacturer/ Cable type Surge No. <strong>of</strong> Core cross- Loop Effective Damping Shielding Remarks<br />

Marketed by impedance cores section resistance ca<strong>pa</strong>citance<br />

Siemens AG SINEC 100Ω ±20Ω 1 x 2 0.75 mm 2 Cu 44 Ω/km