Model OD-11Ceiling <strong>Swirl</strong> <strong>Diffusers</strong>Performance Data ContinuedBlade opening angle during heating and cooling operationOD-11V size 630COOLING Blade angle35° 40° 45° 50°30°∆T z0 °K-2 °K-5 °K-10 °K-15 °KExample 3 (cooling)Q = 2700m 3 /hV H1 = 0.2m/s∆T z = -10 °KH1 = 9m→ H1=9-1.8 = 7.2mRecommended size: 630V ef = Q/A ef x 3600 = 2700/0.32 x 3600V ef = 2.3m/sV H1 /V ef = 0.2/2.3 = 0.08Blade angle: 43°∆T z+15 °K+30 °K1 2 3 4 5 10 0.03 0.04 0.050.10 0.15H1 (m)V H1 /V efHEATING+10 °K +5 °K45 °50 °60 °70 °90 °10 5 4 3 2 1 2 3 4 5 10v ef (m/s)H1 (m)OD-11V size 800COOLING Blade angle35° 40° 45° 50°30°∆T z0 °K-2 °K-5 °K-10 °K-15 °K∆Tz+10°K+15°K1 2 3 4 5 10 0.03 0.04 0.050.10 0.15H1 (m)V H1 /V efHEATING+5 °K45°50°60°70°90°10 5 4 3 2 1 0.6 1 2 3 4 5 10V ef (m/s)H1 (m)44