12.07.2015 Views

Type A - EN44, EN88 Installation Instructions - Dodge Engineering ...

Type A - EN44, EN88 Installation Instructions - Dodge Engineering ...

Type A - EN44, EN88 Installation Instructions - Dodge Engineering ...

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>Dodge</strong> <strong>Engineering</strong> & Controls, Inc.Toll Free (877) 334-2875 Fax: (978) 244-1422<strong>Installation</strong><strong>EN44</strong> and <strong>EN88</strong> Non-Spring Return Electronic Actuators<strong>EN44</strong>B2/<strong>EN88</strong>B2Modulating Control (24 VAC)(0-10 V or 0-20 mA *)EA0284R18M129Figure 18.AS1S2 S3BS4S5 S6Warning:Do not use tandem mount 0-20 mAactuators.* Add 500 ohm resister across pins 2 and 8 toaccept input signal of 0-20 mA.StandardSymbolTable 2. Modulating Control 24 VAC.Function1 (+) Red2 Com Black8 0 to 10 V input signal or0 to 20 mA9 Output for 0 to 10 VDCposition indicationGrayPinkS1 Switch A Common BlackS2 Switch A N.C. BlackS3 Switch A N.O. BlackS4 Switch B Common BlackS5 Switch B N.C. BlackS6 Switch B N.O. BlackColorPlenum129-271 EAI/EN4-9 DEI, Inc. Rev. 10/04Rev. 4, October, 2004