Part 2 - Switchboards and Associated Equipment<br />

202.1.2 Custom-built Assembly Type “CT”<br />

The following details shall apply to Custom-built Assemblies Type “CT”:<br />

(a) A Type “CT” assembly shall be a stationary “cubicle-type assembly” as defined in<br />

AS/NZS 3439.1:2002.<br />

(b) A Type “CT” assembly shall comply with AS/NZS 3439.1:2002 as defined by the<br />

following <strong>requirement</strong>s:<br />

(i) Form of separation shall be Form 1.<br />

(ii) The degree of protection after installation in accordance with the<br />

manufacturer’s instructions shall be IP51 for indoor installation and IP56 for<br />

outdoor installation.<br />

(iii) Assemblies shall be front access with top and/or bottom cable entry.<br />

(iv) Assemblies shall be floor mounted or wall mounted. Wall mounting is<br />

acceptable only if the frontal area of the assembly has an area less than 2<br />

square metres.<br />

(v) For outdoor switchboards containing busbars, pollution degree 3 shall apply<br />

at locations further than 1km in a direct line from the coast or at altitudes<br />

below 1000 metres. Otherwise, pollution degree 4 shall apply.<br />

For indoor switchboards, pollution degree 3 shall apply.<br />

(vi) The following safety measures against direct contact shall apply:<br />

• Requirement of a key or tool to gain entry into the switchboard. (Meet<br />

clause 7.4.2.2.3 a) of AS/NZS 3439.1:2002.)<br />

• Shielding all live parts in such a manner that they cannot be<br />

unintentionally touched when the door is opened or the cover is removed.<br />

(Meet clause 7.4.2.2.3 c) of AS/NZS 3439.1:2002.)<br />

(vii) Assemblies shall be Partially Type Tested Assemblies or Type Tested<br />

Assemblies with type test certificates or satisfactory test reports for the type<br />

tests listed in clause 8 of AS/NZS 3439.1:2002. Documentation shall be<br />

available to demonstrate that the results of type tests were satisfactory. The<br />

testing facility shall be accredited by NATA or registered with the Association<br />

of Short-Circuit Testing Authorities.<br />

(viii) The standard Internal Arcing-Fault Test specified in Annex ZD of AS/NZS<br />

3439.1:2002 (limited arc, initiated on the load side of a protective device<br />

within the functional unit being tested) shall be met and a test certificate<br />

demonstrating that the results of the type tests were satisfactory shall be<br />

available. The testing facility shall be accredited by NATA or registered with<br />

the Association of Short-Circuit Testing Authorities.<br />

202.1.3 Custom-built Assembly Type “CU”<br />

The following details shall apply to Custom-built Assemblies Type “CU”:<br />

Note that type test certificates or satisfactory test reports for the type tests listed in<br />

clause 8 of AS/NZS 3439.1:2002 are not required.<br />

(a) A Type “CU” assembly shall be a stationary “cubicle-type assembly” as defined in<br />

AS/NZS 3439.1:2002.<br />

(b) A Type “CU” assembly shall comply with AS/NZS 3439.1:2002 as defined by the<br />

following <strong>requirement</strong>s:<br />

(i) Form of separation shall be Form 1.<br />

(ii) The degree of protection after installation in accordance with the<br />

manufacturer’s instructions shall be IP51 for indoor installation and IP56 for<br />

outdoor installation.<br />

Page 28 MEW E101