Part 2 - Switchboards and Associated Equipment<br />

207.12.3 Reduced Voltage Starters<br />

Reduced voltage starters shall be of the electromagnetically operated type complying with<br />

AS 1202 Parts 2 and 3, offering overload protection in each phase of the supply or motor<br />

circuit and incorporating the following features.<br />

(a) Star Delta Starter<br />

Star-delta starters shall include:<br />

(i) One (1) main line contactor or equivalent.<br />

(ii) Star and Delta contactors mechanically and <strong>electrical</strong>ly interlocked to<br />

prevent simultaneous operation.<br />

(iii) One (1) triple pole overload relay, fitted to the line contactor. Where the<br />

star-delta starter configuration is such that the overload is connected into the<br />

motor phase winding circuit, a nameplate shall be fixed to the starter stating<br />

the full load current of the motor phase wind, i.e. 58% of the full load line<br />

current of the motor.<br />

(iv) One (1) time delay relay with nominal 0-30 second adjustable time delay<br />

period to control the star to delta switching contactors.<br />

(v) Where closed transition type starters are indicated, suitably rated stainless<br />

steel resistor banks, transition contactor and time delay relay shall be<br />

provided.<br />

(b) Auto-Transformer Starters<br />

207.12.4 Reversing Starters<br />

Auto-transformer starters shall be parallel, closed transition (Korndorfer<br />

connections) type in accordance with Diagram B1, Appendix G of AS 1202, Part 3,<br />

utilising three poles of the star contactor ("K1"), Mechanical and <strong>electrical</strong><br />

interlocking shall be employed between the star contactor ("K1") and the run<br />

contactor ("K3") to prevent simultaneous closing.<br />

Each auto-transformer starter shall include:<br />

(i) One (1) three core auto-transformer tapped at 50%, 65% and 80% and rated<br />

for enclosed operation. Provide Auto-transformers with insulation class 155<br />

to AS 2768. Provide Auto-transformers suitable for a <strong>minimum</strong> of 12 starts<br />

per hour. House each auto-transformer in its own segregated compartment.<br />

(ii) One (1) triple pole thermal overload relay.<br />

(iii) Star, auto-transformer and run contactors (K1, K2 and K3).<br />

(iv) One (1) set of three embedded thermistors, complete with manual reset,<br />

operating relays and indicators, to protect the auto-transformer.<br />

(v) One (1) time delay relay with nominal 0 to 30 second adjustable time delay<br />

period to control the start and run contactors.<br />

Reversing starters shall generally comply with Clause 207.12.1 and shall include:<br />

(i) Two (2) main line contactors, mechanically and <strong>electrical</strong>ly interlocked to prevent<br />

simultaneous closure.<br />

(ii) One (1) triple pole overload relay.<br />

(iii) One (1) time delay relay with nominal 0 to 30 second adjustable time delay period,<br />

to prevent plugging of the motor.<br />

Page 48 MEW E101