Part 2 - Switchboards and Associated Equipment<br />

For Common Control Compartments:<br />

• Requirement of a key or tool to gain entry into the switchboard. (Meet<br />

clause 7.4.2.2.3 a) of AS/NZS 3439.1:2002.)<br />

• Shielding all live parts in such a manner that they cannot be<br />

unintentionally touched when the door is opened or the cover is removed.<br />

(Meet clause 7.4.2.2.3 c) of AS/NZS 3439.1:2002.)<br />

For Distribution Compartments with one main protective device plus a<br />

number of subcircuit protective devices:<br />

• Requirement of a key or tool to gain entry into the switchboard. (Meet<br />

clause 7.4.2.2.3 a) of AS/NZS 3439.1:2002.) for the compartment door<br />

and for the escutcheon.<br />

(vii) Assemblies shall be Partially Type Tested Assemblies or Type Tested<br />

Assemblies with type test certificates or satisfactory test reports for the type<br />

tests listed in clause 8 of AS/NZS 3439.1:2002. Documentation shall be<br />

available to demonstrate that the results of type tests were satisfactory. The<br />

testing facility shall be accredited by NATA or registered with the Association<br />

of Short-Circuit Testing Authorities.<br />

(viii) The special Internal Arcing-Fault Test (unlimited arc, initiated on the line<br />

side of the protective device within the functional unit being tested) required<br />

by Appendix ZD.6 of AS/NZS 3439.1:2002 shall be met and a test certificate<br />

demonstrating that the results of the type tests were satisfactory shall be<br />

available. The duration of the test shall be chosen by the manufacturer<br />

according to the time response of the <strong>electrical</strong> protection devices. If details<br />

of these devices are not known, a power supply duration of at least 100<br />

milliseconds shall apply. The testing facility shall be accredited by NATA or<br />

registered with the Association of Short-Circuit Testing Authorities.<br />

202.1.5 Custom-built Assembly Type “DU”<br />

The following details shall apply to Custom-built Assemblies Type “DU”:<br />

Note that type test certificates or satisfactory test reports for the type tests listed in<br />

clause 8 of AS/NZS 3439.1:2002 are not required.<br />

(a) A Type “DU” assembly shall be a stationary “cubicle-type assembly” or ‘multicubicle-type<br />

assembly” as defined in AS/NZS 3439.1:2002.<br />

(b) A Type “DU” assembly shall comply with AS/NZS 3439.1:2002 as defined by the<br />

following <strong>requirement</strong>s:<br />

(i) Form of separation shall be Form 3b or 3bi, 3bh, 3bih, 4a, 4b, 4ah, 4ai, 4aih,<br />

4bh, 4bi, 4bih.<br />

(ii) The degree of protection after installation in accordance with the<br />

manufacturer’s instructions shall be IP51 for indoor installation and IP56 for<br />

outdoor installation.<br />

(iii) Assemblies shall be front access with top and/or bottom cable entry.<br />

(iv) Assemblies shall be floor mounted.<br />

(v) For outdoor switchboards containing busbars, pollution degree 3 shall apply<br />

at locations further than 1km in a direct line from the coast or at altitudes<br />

below 1000 metres. Otherwise, pollution degree 4 shall apply.<br />

For indoor switchboards, pollution degree 3 shall apply.<br />

(vi) The following safety measures against direct contact shall apply:<br />

For Main Incoming Supply Compartments, Motor Starter Compartments and<br />

Distribution Feeder Compartments with one feeder in the Distribution Feeder<br />

Compartment:<br />

Page 30 MEW E101