29.11.2012 Views

electrical services minimum requirement - NSW Public Works

electrical services minimum requirement - NSW Public Works

electrical services minimum requirement - NSW Public Works

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Part 2 - Switchboards and Associated Equipment<br />

equipment shall be suitable for the actual fault let through energy and peak cut-off<br />

current of the protective device corresponding to the indicated fault level.<br />

Equipment shall not be used at a higher fault level than that for which it has been tested,<br />

irrespective of fault duration.<br />

203.2 Fault Current Limiting<br />

Fault current limiting, either by fuses or suitable circuit breaker combinations shall only be<br />

used where indicated and shall be of the form indicated.<br />

Selection of fault current limiting equipment shall be in accordance with a selection table<br />

accepted by the relevant Supply Authority.<br />

203.3 Short Circuit Co-ordination<br />

Type 2 short circuit co-ordination in accordance with AS 60947.4.1 is required for the<br />

short circuit protective device, the motor contactor and the overload device if either of the<br />

following conditions apply:<br />

(a) Main busbar fault level of 31.5kA or greater at 415Volts has been specified.<br />

(b) Starter size is greater than 37kW when direct on line started.<br />

(c) Starter size is greater than 45kW when reduced voltage started.<br />

Type 1 short circuit co-ordination in accordance with AS 60947.4.1 is required for the<br />

short circuit protective device, the motor contactor and the overload device in all cases<br />

other than (a), (b), and (c) above, except for the following condition:<br />

Where ventilation fans are installed to provide a safe environment for personnel, Total<br />

Co-ordination for the short circuit protective device, the motor contactor and the overload<br />

in accordance with AS 60947.6.2 is required.<br />

204 BUSBARS<br />

204.1 Generally<br />

204.2 Material<br />

204.3 Sizes<br />

Busbars for Proprietary Assemblies may be of the manufacturer's standard.<br />

Multi-pole proprietary busbar assemblies for circuit breakers shall be of an accepted type.<br />

When busbar systems have been verified by type testing, such arrangements are<br />

acceptable in lieu of the methods specified below.<br />

Busbars shall be arranged to ensure that the phase sequence at all switchboard<br />

equipment terminals is red, white and blue from left to right and from top to bottom, when<br />

viewed from the front of the switchboard.<br />

Busbars shall be hard-drawn high-conductivity copper. Square-edged busbars shall not<br />

be used.<br />

Busbar sizes in relation to current ratings shall be to AS 3000, assuming the<br />

switchboards are of magnetic materials, located indoors in a well ventilated room and the<br />

appropriate enclosure rating shall apply. However, smaller busbars may be used in<br />

accordance with an approved Testing Authority Temperature Rise Test Certificate for a<br />

switchboard with a similar internal physical configuration.<br />

For purposes of withstanding thermal stresses due to fault currents, active busbars shall<br />

be sized in accordance with AS 3439.1, unless smaller busbars can be substantiated with<br />

Page 34 MEW E101

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!