Engineering Data & Dimensions<br />
3 M.P.T.<br />
DRAIN<br />
10<br />
30-3/8"<br />
(2)ACCESS<br />
DOOR<br />
57"<br />
(2)4 FLUID IN<br />
(2)4 FLUID OUT<br />
9' 9-3/4"<br />
2 M.P.T.<br />
MAKE-UP<br />
3 F.P.T.<br />
OVERFLOW<br />
A<br />
3-1/2"<br />
4-5/8"<br />
8'-5 1/2"<br />
17 L<br />
17<br />
H<br />
17<br />
L<br />
26<br />
LSWA 116A TO 116D<br />
LSWA 174A TO 174D<br />
LSWA 232A TO 232D<br />
LSWA 348A TO 348D<br />
26 L<br />
21<br />
L<br />
NOTE: The number of<br />
coil connections doubles<br />
when flow rate exceeds<br />
900 GPM on Models<br />
116A thru 174D and<br />
1800 GPM on Models<br />
232A thru 348D.<br />
Model<br />
Weights Fans Spray Pump ■ Remote Sump<br />
Dimensions<br />
Number Shipping Operating Heaviest Section† HP* CFM HP GPM Gallons Req'd ** Conn. Size Coil Volume Gallons Height Length A<br />
LSWA 116A 13790 21520 8530 40 75800 5 685 410<br />
10" 314 12' 6 1/4" 11' 11 3/4" 22 1/4"<br />
116B 16000 24570 10740 40 74400 5 685 410<br />
10" 418 13' 2 3/4" 11' 11 3/4" 30 3/4"<br />
116C 18210 27610 12940 40 72200 5 685 410<br />
10" 522 13 11 1/4" 11' 11 3/4" 39 1/4"<br />
116D 20420 30650 15150 40 70800 5 685 410<br />
10" 626 14' 7 3/4" 11' 11 3/4" 47 3/4"<br />
LSWA 174A 20370 31680 12380 (2) 25 107200 7 1/2 1030 600<br />
12" 468 12' 6 1/4" 18' 1/4" 22 1/4"<br />
174B 23740 36270 15500 (2) 30 112200 7 1/2 1030 600<br />
12" 624 13' 2 3/4" 18' 1/4" 30 3/4"<br />
174C 27040 40820 18680 (2) 30 108700 7 1/2 1030 600<br />
12" 780 13 11 1/4" 18' 1/4" 39 1/4"<br />
174D 30350 45380 21870 (2) 30 106200 7 1/2 1030 600<br />
12" 936 14' 7 3/4" 18' 1/4" 47 3/4"<br />
LSWA 232A 26770 41920 9710 (2) 40 151600 (2) 5 1370 820<br />
12" 628 12' 6 1/4" 24' 3/4" 22 1/4"<br />
232B 31110 47900 10740 (2) 40 148800 (2) 5 1370 820<br />
12" 836 13' 2 3/4" 24' 3/4" 30 3/4"<br />
232C 35440 53870 12940 (2) 40 144400 (2) 5 1370 820<br />
12" 1044 13 11 1/4" 24' 3/4" 39 1/4"<br />
232D 39770 59840 15150 (2) 40 141600 (2) 5 1370 820<br />
12" 1252 14' 7 3/4" 24' 3/4" 47 3/4"<br />
LSWA 348A 40140 62890 14450†† (4) 25 214400 (2) 7 1/2 2060 1500<br />
14" 936 12' 6 1/4" 36' 2" 22 1/4"<br />
348B 46880 72060 15500 (4) 30 224400 (2) 7 1/2 2060 1500<br />
14" 1248 13' 2 3/4" 36' 2" 30 3/4"<br />
348C 53490 81170 18680 (4) 30 217400 (2) 7 1/2 2060 1500<br />
14" 1560 13 11 1/4" 36' 2" 39 1/4"<br />
348D 60100 90280 21870 (4) 30 212400 (2) 7 1/2 2060 1500<br />
14" 1872 14' 7 3/4" 36' 2" 47 3/4"<br />
†Heaviest section is the coil section<br />
†† Heaviest section is the pan section<br />
* For external static pressure up to 1/2", use next larger size fan motor<br />
* For dry operation, use next larger size fan motor<br />
LSWA 116A to 116D LSWA 174A to 174D<br />
LSWA 232A to 232D LSWA 348A to 348D<br />
Coil connections are available as beveled for welding, MPT and flanged.<br />
■ Remote Sump Configuration<br />
When a remote sump arrangement is selected, the spray pump, suction strainer and associated piping<br />
are omitted; the unit is provided with an oversized outlet to facilitate drainage to the remote sump.<br />
** Gallons shown is water in suspension in unit and piping. Allow for additional water in bottom of remote sump to cover pump suction and strainer during<br />
operation (12" would normally be sufficient).<br />
Unit dimensions may vary slightly from catalog. See factory certified prints for exact dimensions.