Closed Circuit Coolers - Tasman Cooling Towers
Closed Circuit Coolers - Tasman Cooling Towers
Closed Circuit Coolers - Tasman Cooling Towers
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Engineering Data & Dimensions<br />
H<br />
8<br />
5' – 1 1/8"<br />
15<br />
ACCESS<br />
DOOR<br />
1/2 F.P.T. VENT<br />
4 FLUID IN<br />
4 FLUID OUT<br />
H<br />
1 M.P.T.<br />
MAKE-UP<br />
2 F.P.T.<br />
OVERFLOW<br />
2 M.P.T. DRAIN<br />
5' – 5 1/2"<br />
3' – 7 1/2"<br />
ACCESS<br />
DOOR 2 M.P.T.<br />
OVERFLOW<br />
1 M.P.T.<br />
MAKE-UP<br />
LSWA 41A TO 41C<br />
19 1/8<br />
11' – 11 3/4"<br />
4 FLUID IN<br />
4 FLUID OUT<br />
2 M.P.T. DRAIN<br />
4' – 5/8" 19' – 1/8"<br />
1/2 F.P.T. VENT<br />
1/2 F.P.T. VENT<br />
LSWA 20AA TO 20C<br />
LSWA 20AA TO 20C<br />
LSWA 30A TO 30C<br />
LSWA 41A TO 41C<br />
13 1 / 8 5' – 11 7/8" 13 1 / 8<br />
1/2 F.P.T. VENT<br />
12 18'<br />
LSWA 61A TO 61C<br />
1/2 F.P.T. VENT<br />
1/2 F.P.T. VENT<br />
LSWA 58A TO 58D LSWA 87A TO 87D<br />
131/ 8 11' – 11 1/2" 13 1/ 8 18' – 1/8"<br />
LSWA 30A TO 30C<br />
8' – 11 1/4"<br />
LSWA 61A TO 61C<br />
LSWA 58A TO 58D<br />
LSWA 87A TO 87D<br />
NOTE: The number of<br />
coil connections doubles<br />
when flow rate exceeds<br />
450 GPM on Models<br />
20AA thru 87D<br />
Model<br />
Weights Fans Spray Pump ■ Remote Sump Dimensions<br />
Number Shipping Operating Heaviest Section† HP* CFM HP GPM Gallons Req'd ** Conn. Size Coil Volume Gallons Height Length<br />
LSWA 20AA 2250 3310 2250†† 5 12100 3/4 120 80 4" 41 6' 8 5/8" 5' 11 7/8"<br />
20A 2670 3840 1680 5 11900 3/4 120 80 4" 59 7' 4 1/8" 5' 11 7/8"<br />
20B 3030 4310 2040 5 11700 3/4 120 80 4" 77 7' 11 5/8" 5' 11 7/8"<br />
20C 3470 4870 2430 7.5 13100 3/4 120 80 4" 95 8' 7 1/8" 5' 11 7/8"<br />
LSWA 30A 3850 5610 2430 7.5 17800 1 180 120 6" 83 7' 4 1/8" 8' 11 1/4"<br />
30B 4450 6380 3000 10 19200 1 180 120 6" 109 7' 11 5/8" 8' 11 1/4"<br />
30C 5050 7160 3590 10 18800 1 180 120 6" 135 8' 7 1/8" 8' 11 1/4"<br />
LSWA 41A 4920 7370 3170 10 23800 1 1/2 245 170 6" 110 7' 4 1/8" 11' 11 3/4"<br />
41B 5770 8450 3960 15 26000 1 1/2 245 170 6" 147 7' 11 5/8" 11' 11 3/4"<br />
41C 6550 9480 4750 15 26200 1 1/2 245 170 6" 184 8' 7 1/8" 11' 11 3/4"<br />
LSWA 58A 6850 10010 4360 15 38800 1 1/2 245 170 6" 157 9' 3/4" 11' 11 1/2"<br />
58B 7960 11470 5470 15 38000 2 345 230 6" 209 9' 9 1/4" 11' 11 1/2"<br />
58C 9100 12950 6580 20 37000 2 345 230 6" 261 10' 5 3/4" 11' 11 1/2"<br />
58D 10210 14410 7700 20 36300 2 345 230 6" 313 11' 2 1/4" 11' 11 1/2"<br />
LSWA 61A 7460 10830 7460 15 35800 2 365 250 8" 164 7' 4 1/8" 18'<br />
61B 8650 12380 8650 20 38600 2 365 250 8" 218 7' 11 5/8" 18'<br />
61C 9840 13290 9840 20 37800 2 365 250 8" 272 8' 7 1/8" 18'<br />
LSWA 87A 10470 14760 6690 20 52500 3 515 340 8" 234 9' 3/4" 18' 1/8"<br />
87B 12200 16990 8330 25 55600 3 515 340 8" 312 9' 9 1/4" 18' 1/8"<br />
87C 13870 19180 9990 25 53800 3 515 340 8" 390 10' 5 3/4" 18' 1/8"<br />
87D 15590 21420 11660 30 52700 3 515 340 8" 468 11' 2 1/4" 18' 1/8"<br />
† Heaviest section is the coil section<br />
†† Model Normally Ships in One Piece<br />
* For external static pressure up to 1/2", use next larger size fan motor<br />
* For dry operation, use next larger size fan motor<br />
■ Remote Sump Configuration<br />
When a remote sump arrangement is selected, the spray pump, suction strainer and associated piping<br />
are omitted; the unit is provided with an oversized outlet to facilitate drainage to the remote sump.<br />
** Gallons shown is water in suspension in unit and piping. Allow for additional water in bottom of remote sump to cover pump suction and strainer during<br />
operation (12" would normally be sufficient).<br />
Unit dimensions may vary slightly from catalog. See factory certified prints for exact dimensions.