12.07.2015 Views

Modbus Protocol for ION 7500, ION 7600 and ION 8000 series

Modbus Protocol for ION 7500, ION 7600 and ION 8000 series

Modbus Protocol for ION 7500, ION 7600 and ION 8000 series

SHOW MORE
SHOW LESS
  • No tags were found...

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>Modbus</strong> Register MapAppendix B: <strong>Modbus</strong> Slave Module Factory Default<strong>Modbus</strong> Slave Module #2Format: Signed 32 bitBase Address: 40027Scaling: YesIn Zero, In Full: -214748364, +214748364Out Zero, Out Full: -2147483640, +2147483640Input <strong>Modbus</strong> Registers ParameterSource #1 40027 to 40028 kW aSource #2 40029 to 40030 kW bSource #3 40031 to 40032 kW cSource #4 40033 to 40034 kW totSource #5 40035 to 40036 kVAR aSource #6 40037 to 40038 kVAR bSource #7 40039 to 40040 kVAR cSource #8 40041 to 40042 kVAR totSource #9 40043 to 40044 kVA aSource #10 40045 to 40046 kVA bSource #11 40047 to 40048 kVA cSource #12 40049 to 40050 kVA totSource #13 40051 to 40052 pf sign aSource #14 40053 to 40054 pf sign bSource #15 40055 to 40056 pf sign cSource #16 40057 to 40058 pf sign totPage 27