Modbus Protocol for ION 7500, ION 7600 and ION 8000 series
Modbus Protocol for ION 7500, ION 7600 and ION 8000 series
Modbus Protocol for ION 7500, ION 7600 and ION 8000 series
- No tags were found...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Appendix B: <strong>Modbus</strong> Slave Module Factory Default <strong>Modbus</strong> Register Map<strong>Modbus</strong> Slave Module: kWh/kVArhThe kWh/kVArh Module applies to the <strong>ION</strong> <strong>8000</strong> <strong>series</strong> meter, v240 <strong>and</strong> beyond.Format: Signed 32 bitBase Address: 40230Scaling: NoInput <strong>Modbus</strong> Registers ParameterSource #1 40230 kWh delSource #2 40232 kWh recSource #3 40234 kVARh delSource #4 40236 kVARh recSource #5 40238 kVAhSource #6 40240Source #7 40242Source #8 40244Source #9 40246Source #10 40248Source #11 40250Source #12 40252Source #13 40254Source #14 40256Source #15 40258Source#16 40260Page 44