Pellet Boiler/Burner Technical Introduction - Maine Energy Systems
Pellet Boiler/Burner Technical Introduction - Maine Energy Systems
Pellet Boiler/Burner Technical Introduction - Maine Energy Systems
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Chimney Design Criteria (1)• Draft Influencing Factors:– height of chimney– flue gas temperature– boiler output– flue gas resistance in boiler• Chimney diameter must be at least 6” (150 mm)• Vent diameter less than 6” (150 mm) diameter: requires exhaust fan, or chimney heightover 35 ft (10 m).• Combustion chamber draft values:– Full fire ≥ .04 Inch WC. (Required for good combustion & proper burner operation)- Low fire ≥ .02 Inch WC.• Installation of barometric damper is required in ALL cases.Training documentation Slide Nr. 30: 11/2007