The <strong>3UF5</strong>0 Basic Unit2.5.4 Thermistor <strong>Motor</strong> <strong>Protection</strong>Description of functionsOperationA Thermistor-detector circuit can be connected to versions <strong>3UF5</strong>0.1 to 3A...for direct temperature detection. Thermistor <strong>Motor</strong> <strong>Protection</strong> is an alternativeto external Earth Fault Detection.If the resistance values are exceeded (PTC) or fall below a certain value(NTC), the <strong>SIMOCODE</strong>-<strong>DP</strong> reacts either• by turning off the Contactor <strong>Control</strong>s QE1 / QE2 / QE3 or• with a warning,depending on the setting you have entered.NoteThermistor <strong>Motor</strong> <strong>Protection</strong> is an alternative to the external Earth FaultDetection function (version of unit).Types of detectorThree types of detector can be evaluated:Type Behaviour Characteristic Comments1 PTCBinaryRWarning or shutdown can be set.2 PTCAnalogKTY3 NTCAnalog1 2 υTable 7: Types of detector for Thermistor <strong>Motor</strong> <strong>Protection</strong>RR1 2υυTwo thresholds can be evaluated.1. Warning <strong>and</strong>2. ShutdownTwo thresholds can be evaluated.1. Warning <strong>and</strong>2. ShutdownGWA 4NEB 631 4286-02a 2-19