5.3.4.4 Filling SpeedParameter: P26 Default value: 5000 m/hPath: OPTIMIZATION / FILLING SPEEDDescription:This parameter provides additional protection against echo loss in applications involvingvery heavy fuming during filling process. <strong>Co</strong>rrect setting increases the reliability of themeasurement during the filling. The parameter must not be smaller than the fastest possiblefilling rate of the actual technology.5.3.4.5 Background Echo ImagePath: OPTIMIZATION / BACKG.ECHO IMAGE / SAVE BACKG. IMAGEDescription:Blocking out disturbing objects. The not-moving disturbing objects inside the tank whichgenerates unwanted false reflections can be blocked out from the measurement range. Forthis purpose the instrument needs to map the totally empty tank to create a ”backgroundimage”. After this procedure the software will automatically recognise and ignore thereflections coming from the disturbing objects crossing the microwave beam(see 4.1 - Obstacles).Clear saved background imageBACKGROUND IMG.RANGE:SR BKG.:LG BKG.:[QUIT][CLEAR]SHORTNONO[SAVE]Indication of short or long background imageSaved short background imageSaved long background imageQuitSave background imagewes1404a0600p_01 ♦ 31 / 44