<strong>DET</strong> <strong>NORSKE</strong> <strong>VERITAS</strong>TYPE APPROVAL CERTIFICATECERTIFICATE NO. E-11721This is to certify that theLow Voltage Cablewith type designation(s)BFOU (i) S3 & (c) S4 250 V, BFOU (i) S3/S7 & (c) S4/S8 250 VManufactured byB.V. Twentsche KabelfabriekHAAKSBERGEN, Netherlandsis found to comply withDet Norske Veritas' Rules for Classification of Ships, High Speed & Light Craft and Det Norske Veritas' Offshore StandardsIEC 60092-376 (2003-05)IEC 60331-1/2 (2009-05)IEC 60331-21 (1999-04)IEC 60332-3-22 (2009-02)IEC 60754-1/2 (2011-11)IEC61034-1/2 (2005-04/2005-04)NEK TS 606 (2009-05)ApplicationGeneral power and lighting. Control.Fire resistant. Flame retardant in bunch Cat. A. Halogen free. Low smoke.Cold bend -40°C. Cold impact -35°C.Mud resistant.Type Voltage class (V) Temp. class (°C)BFOU (i) S3 & (c) S4 250 V 250 90BFOU (i) S3/S7 & (c) S4/S8 250 V 250 90Høvik, 2012-07-03for Det Norske Veritas ASThis Certificate is valid until2016-06-30Marit LaumannHead of SectionDNV local office:RotterdamIvar BullSurveyorThis Certificate is subject to terms and conditions overleaf. Any significant change in design or construction may render this Certificate invalid.The validity date relates to the Type Approval Certificate and not to the approval of equipment/systems installed.If any person suffers loss or damage which is proved to have been caused by any negligent act or omission of Det Norske Veritas, then Det Norske Veritas shall pay compensation to suchperson for his proved direct loss or damage. However, the compensation shall not exceed an amount equal to ten times the fee charged for the service in question, provided that the maximumcompensation shall never exceed USD 2 million. In this provision "Det Norske Veritas" shall mean the Foundation Det Norske Veritas as well as all its subsidiaries, directors, officers,employees, agents and any other acting on behalf of Det Norske Veritas.<strong>DET</strong> <strong>NORSKE</strong> <strong>VERITAS</strong> AS, Veritasveien 1, NO-1322 Høvik, Norway, Tel.: +47 67 57 99 00, Fax: +47 67 57 99 11, Org.No. NO 945 748 931 MVA www.dnv.comForm No.: TA 1411a Issue: October 2009 Page 1 of 4


Certificate No.: E-11721File No.: 827.20Job Id.: 262.1-012873-1Product descriptionType: BFOU (i) S3 & (c) S4 250 V & BFOU (i) S3/S7 & (c) S4/S8 250 VConstruction:Conductors: Tinned, stranded copper class 2 or class 5Core insulation: Mica tape + HF HEPRScreen:Copper/polyester tape w/tinned copper drain wireInner covering: Halogen free compoundMetal covering: Tinned copper wire braidSheath:SHF 2 or SHF MudNumber ofCores xconductorcross-sectionOverall Overalldiameter diameterNominal Nominal(c+i) (c)mm 2 mm mm1 x 2 x 0,75 8,1 7,72 x 2 x 0,75 12,7 12,13 x 2 x 0,75 13,4 12,74 x 2 x 0,75 15,2 14,45 x 2 x 0,75 16,6 15,56 x 2 x 0,75 17,9 16,97 x 2 x 0,75 17,9 16,98 x 2 x 0,75 20,0 18,79 x 2 x 0,75 21,5 20,310 x 2 x 0,75 22,6 21,011 x 2 x 0,75 22,6 21,012 x 2 x 0,75 23,3 21,713 x 2 x 0,75 24,3 22,914 x 2 x 0,75 24,3 22,915 x 2 x 0,75 25,8 24,016 x 2 x 0,75 25,8 24,017 x 2 x 0,75 27,1 25,418 x 2 x 0,75 27,1 25,419 x 2 x 0,75 27,1 25,420 x 2 x 0,75 28,7 26,721 x 2 x 0,75 28,7 26,722 x 2 x 0,75 30,3 28,223 x 2 x 0,75 30,3 28,224 x 2 x 0,75 31,7 29,525 x 2 x 0,75 31,7 29,526 x 2 x 0,75 31,7 29,527 x 2 x 0,75 32,4 30,330 x 2 x 0,75 33,7 31,332 x 2 x 0,75 34,9 32,537 x 2 x 0,75 36,9 33,91 x 2 x 1,5 9,3 9,42 x 2 x 1,5 15,6 14,73 x 2 x 1,5 16,6 15,54 x 2 x 1,5 18,0 17,05 x 2 x 1,5 19,7 18,46 x 2 x 1,5 21,3 20,1Number ofCores xconductorcross-sectionOverall Overalldiameter diameterNominal Nominal(c+i) (c)mm 2 mm mm7 x 2 x 1,5 21,3 20,18 x 2 x 1,5 23,9 22,59 x 2 x 1,5 26,0 24,210 x 2 x 1,5 27,1 25,411 x 2 x 1,5 27,1 25,412 x 2 x 1,5 28,1 26,213 x 2 x 1,5 29,4 27,614 x 2 x 1,5 29,4 27,615 x 2 x 1,5 31,2 29,016 x 2 x 1,5 31,2 29,017 x 2 x 1,5 33,0 30,718 x 2 x 1,5 33,0 30,719 x 2 x 1,5 33,0 30,720 x 2 x 1,5 34,8 32,321 x 2 x 1,5 34,8 32,322 x 2 x 1,5 37,3 34,223 x 2 x 1,5 37,3 34,724 x 2 x 1,5 39,2 36,525 x 2 x 1,5 39,2 36,526 x 2 x 1,5 39,2 36,527 x 2 x 1,5 40,0 37,330 x 2 x 1,5 41,6 38,732 x 2 x 1,5 43,2 40,237 x 2 x 1,5 45,0 40,61 x 2 x 2,5 10,1 10,12 x 2 x 2,5 17,2 16,13 x 2 x 2,5 18,2 17,14 x 2 x 2,5 19,9 18,65 x 2 x 2,5 21,6 20,46 x 2 x 2,5 23,7 22,27 x 2 x 2,5 23,7 22,28 x 2 x 2,5 26,6 24,99 x 2 x 2,5 28,9 26,910 x 2 x 2,5 30,3 28,211 x 2 x 2,5 30,3 28,212 x 2 x 2,5 31,3 29,1Number ofCores xconductorcross-sectionOverall Overalldiameter diameterNominal Nominal(c+i) (c)mm 2 mm mm13 x 2 x 2,5 33,0 30,714 x 2 x 2,5 33,0 30,715 x 2 x 2,5 34,7 32,316 x 2 x 2,5 34,7 32,317 x 2 x 2,5 37,3 34,218 x 2 x 2,5 37,3 34,219 x 2 x 2,5 37,3 34,720 x 2 x 2,5 39,5 36,721 x 2 x 2,5 39,5 36,722 x 2 x 2,5 41,7 38,823 x 2 x 2,5 41,7 38,824 x 2 x 2,5 43,9 40,925 x 2 x 2,5 43,9 40,926 x 2 x 2,5 43,9 40,927 x 2 x 2,5 44,8 41,730 x 2 x 2,5 46,6 43,132 x 2 x 2,5 48,7 45,037 x 2 x 2,5 50,8 45,61 x 3 x 0,75 8,9 8,52 x 3 x 0,75 14,7 13,23 x 3 x 0,75 15,5 14,74 x 3 x 0,75 16,9 15,85 x 3 x 0,75 18,3 17,36 x 3 x 0,75 20,0 18,77 x 3 x 0,75 20,0 18,78 x 3 x 0,75 22,4 20,99 x 3 x 0,75 24,1 22,710 x 3 x 0,75 25,3 23,611 x 3 x 0,75 25,3 23,612 x 3 x 0,75 26,0 24,313 x 3 x 0,75 27,5 25,714 x 3 x 0,75 27,5 25,715 x 3 x 0,75 28,9 27,016 x 3 x 0,75 28,9 27,017 x 3 x 0,75 30,5 28,518 x 3 x 0,75 30,5 28,5<strong>DET</strong> <strong>NORSKE</strong> <strong>VERITAS</strong> AS, Veritasveien 1, NO-1322 Høvik, Norway, Tel.: +47 67 57 99 00, Fax: +47 67 57 99 11, Org.No. NO 945 748 931 MVA www.dnv.comForm No.: TA 1411a Issue: October 2009 Page 2 of 4


Certificate No.: E-11721File No.: 827.20Job Id.: 262.1-012873-1Number ofCores xconductorcross-sectionOverall Overalldiameter diameterNominal Nominal(c+i) (c)mm 2 mm mm19 x 3 x 0,75 30,5 28,520 x 3 x 0,75 32,2 30,221 x 3 x 0,75 32,2 30,222 x 3 x 0,75 34,0 31,823 x 3 x 0,75 34,0 31,824 x 3 x 0,75 36,3 33,41 x 3 x 1,5 10,1 9,72 x 3 x 1,5 17,3 16,23 x 3 x 1,5 18,3 17,34 x 3 x 1,5 20,1 18,85 x 3 x 1,5 22,0 20,66 x 3 x 1,5 23,8 22,57 x 3 x 1,5 23,8 22,58 x 3 x 1,5 26,8 25,29 x 3 x 1,5 29,1 27,410 x 3 x 1,5 30,5 28,511 x 3 x 1,5 30,5 28,512 x 3 x 1,5 31,5 29,413 x 3 x 1,5 33,2 31,0Number ofCores xconductorcross-sectionOverall Overalldiameter diameterNominal Nominal(c+i) (c)mm 2 mm mm14 x 3 x 1,5 33,2 31,015 x 3 x 1,5 35,0 32,916 x 3 x 1,5 35,0 32,917 x 3 x 1,5 37,6 34,618 x 3 x 1,5 37,6 34,619 x 3 x 1,5 37,6 34,620 x 3 x 1,5 39,8 37,121 x 3 x 1,5 39,8 37,122 x 3 x 1,5 42,0 39,323 x 3 x 1,5 42,0 39,324 x 3 x 1,5 44,3 41,31 x 3 x 2,5 10,9 10,42 x 3 x 2,5 18,8 17,83 x 3 x 2,5 20,1 18,84 x 3 x 2,5 22,1 20,75 x 3 x 2,5 24,0 22,66 x 3 x 2,5 26,3 24,87 x 3 x 2,5 26,3 24,88 x 3 x 2,5 29,6 27,8Number ofCores xconductorcross-sectionOverall Overalldiameter diameterNominal Nominal(c+i) (c)mm 2 mm mm9 x 3 x 2,5 32,2 30,210 x 3 x 2,5 33,7 31,511 x 3 x 2,5 33,7 31,512 x 3 x 2,5 34,8 32,513 x 3 x 2,5 37,3 34,314 x 3 x 2,5 37,3 34,315 x 3 x 2,5 39,5 36,816 x 3 x 2,5 39,5 36,817 x 3 x 2,5 41,7 39,018 x 3 x 2,5 41,7 39,019 x 3 x 2,5 41,7 39,020 x 3 x 2,5 44,2 41,321 x 3 x 2,5 44,2 41,322 x 3 x 2,5 46,7 43,623 x 3 x 2,5 46,7 43,624 x 3 x 2,5 49,6 45,71 x 4 x 0,75 9,8 7,71 x 4 x 1,5 11,5 8,91 x 4 x 2,5 12,4 9,6Application/LimitationThis type of cable is fire resistant in accordance with IEC Publication 60331-series.The requirements of SOLAS Amendments Chapter II-1, Part D, Reg. 45, 5.2 (provision to be taken to limit Fire Propagationalong Bunches of Cables or Wires) are fulfilled without any additional measures.Type Approval documentationTests carried outStandard Issued General description LimitationIEC 60092-350 2008-02 General construction and test methods of power,control and instrumentation cables for shipboard andoffshore applicationsIEC 60092-351 2004-04 Insulating materials for shipboard and offshore units,power, control, instrumentation, telecommunicationand data cablesIEC 60092-359 1999-08 Sheathing materials for shipboard power andtelecommunication cablesIEC 60092-376 2003-05 Cables for control and instrumentation circuits150/250 V (300 V)IEC 60331-21 1999-04 Fire resistance / Circuit integrity – Test for electriccables under fire conditions-Circuit integrity – Part 21IEC 60331-1/2 2009-05 Fire resistance / Circuit integrity – Test for methodfor fire with shock at temperature of at least 830ºCfor cables rated up to and including 0,6/1 kVMinimum 90 min. test. +15 minutes cooling time<strong>DET</strong> <strong>NORSKE</strong> <strong>VERITAS</strong> AS, Veritasveien 1, NO-1322 Høvik, Norway, Tel.: +47 67 57 99 00, Fax: +47 67 57 99 11, Org.No. NO 945 748 931 MVA www.dnv.comForm No.: TA 1411a Issue: October 2009 Page 3 of 4


Certificate No.: E-11721File No.: 827.20Job Id.: 262.1-012873-1Standard Issued General description LimitationIEC 60332-3-22 2009-02 Tests on electric and optical fibre cables under fireconditions – Part 3-22: Test for vertical flame spreadof vertically-mounted bunched wires or cables –Category ABunch testCategory AIEC 60332-1-2 2006-07 Tests on eletric cables under fire conditions.Test for vertical flame propagation for a singleinsulated wire or cable.IEC 60754-1 2011-11 Test on gases evolved during combustion ofmaterials from cables – Determination of the amountof halogen acid gasIEC 60754-2 2011-11 Test on gases evolved during combustion ofmaterials from cables – Determination of the degreeof acidity of gases evolved during the combustion ofmaterials taken from electric cables by measuring pHand condctivityLow Halogen: 4,3Conductivity < 10µSIEC 60684-2 2003-05 Flexible insulating sleeving – Part 2: Methods of test. Fluorine content < 0,1%IEC 61034-1/2 2005-04 Measurement of smoke density of cablesburning under defined conditions –Test apparatus, procedure and requirementsLow smokeIEC 60092-350 2008-02 Annex E: Procedure8.9.1: Temperature requirementsNEK 606 Ed. 4 2009-05 Cables for offshore installations. Halogen-free and/ormud resistant. Technical specification.Cold bend: -40°CCold impact: -35°CMarking of product{length} <strong>TKF</strong> - BFOU(c) - S4/S8 – No of elements x pair/triple x cross sectional area - 250 V - NEK606 / IEC 60092-376 - IEC60332-3-22 – IEC 60331-1/2 {production code} {year} or{length} <strong>TKF</strong> - BFOU(i) – S3/S7 - No of elements x pair/triple x cross sectional area - 250 V - NEK606 / IEC 60092-376 - IEC60332-3-22 – IEC 60331-1/2 {production code} {year}Certificate retention surveyThe scope of the retention/renewal survey is to verify that the conditions stipulated for the Type approval is complied with andthat no alterations are made to the product design or choice of materials.The main elements of the survey are:• Inspection on factory samples, selected at random from the production line (where practicable)• Results from Production Sample Tests (PST) and Routine Tests (RT) checked• (if RT- and PST-test reports are not available, tests according to PST and RT to be carried out)• Review of type approval documentation• Review of possible change in design, materials and performance• Ensure traceability between manufacturer's product type marking and Type Approval Certificate.Survey shall be performed at least every second year.END OF CERTIFICATE<strong>DET</strong> <strong>NORSKE</strong> <strong>VERITAS</strong> AS, Veritasveien 1, NO-1322 Høvik, Norway, Tel.: +47 67 57 99 00, Fax: +47 67 57 99 11, Org.No. NO 945 748 931 MVA www.dnv.comForm No.: TA 1411a Issue: October 2009 Page 4 of 4