Specifications continued-Table 5: Water Heater PerformanceMODELHot WaterAvailability(Minutes)Coil HeatTransfer Area(Sq Ft)Pressure Drop atRated HeatSource Flow Rate(Feet of Head)40-Gal. 6.8 14.2 2.450-Gal. 8.6 14.2 2.465-Gal. 10.8 14.2 2.480-Gal. 13.5 14.2 2.4NOTICEIf the boiler takes longer to heat up from a cold startthan the water availability as noted above, hot watershortage may occur.Hot water availability is based on drawing 80% of theheated tank volume at 4 gallons per minute flow rate.The maximum heat transfer through the coil (heatinput) of the water heater at 240°F boiler water supplytemperature and 210°F potable water temperature is23,500 Btu/hr. Potable water temperature is limited tobelow 210 °F and nominal water-containing capacityis below 120 gallons for all indirect-fired models.Accordingly, per Part HLW-101.2, Section IV of theASME Boiler and Pressure Vessel Code, all indirectfiredproducts listed are exempted from compliancewith the code.10