S-series IS Electronic Marshalling - Emerson Process Management
S-series IS Electronic Marshalling - Emerson Process Management
S-series IS Electronic Marshalling - Emerson Process Management
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
DeltaV Product Data SheetOctober 2013 – Page 20S-<strong>series</strong> <strong>IS</strong> <strong>Electronic</strong> <strong>Marshalling</strong><strong>IS</strong> Analog Output CHARMSpecifications for <strong>IS</strong> AO 4-20 mA HART CHARMSensor TypesNominal signal range (span)Full signal rangeLoad ResistanceVoltage to LoadAccuracy over temperature rangeResolution4 to 20 mA with or without HART4-20 mA, (0-20 mA optional)0 to 22 mA750 Ohm max.15 V (min) @ 20 mA0.25% of span (0 to 60 ºC)0.5% of span (-40 to 70 ºC)16 bit A/D converterCalibrationNone requiredIsolation Galvanically isolated according to EN 60079-11.Voltage peak value 375 VDC.Field Circuit (2-wire Transmitter)- Voltage Uo- Current Io- Power Po(Connect between field terminals 3+, 4-)- 27 V- 93 mA- 628 mW (linear Characteristic)CHARM power req. 56 mA max @ 24 VDC ±10%CHARM Heat DissipationHART supportHART data update rates1.1 WHART v7 pass-through for AMSHART v7 variable and device status available to control500 msSimplified Circuit and Connection Diagram for <strong>IS</strong> AO HART CHARM