04.12.2012 Views

Flowin 2 Natural Gas Flowmeter - Spirax Sarco

Flowin 2 Natural Gas Flowmeter - Spirax Sarco

Flowin 2 Natural Gas Flowmeter - Spirax Sarco

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

3309850/1<br />

<strong>Flowin</strong> 2<br />

<strong>Natural</strong> <strong>Gas</strong> <strong>Flowmeter</strong><br />

Installation and Maintenance Instructions<br />

1. Safety information<br />

2. Product information<br />

& specifications<br />

3. Installation, mechanical<br />

& electrical<br />

4. Operating &<br />

commissioning instructions<br />

5. Maintenance<br />

6. Spare parts<br />

7. Fault finding<br />

8. Settings table<br />

IM-P330-73<br />

MI Issue 1<br />

IM-P330-73 Printed in the MI UK Issue 1 © Copyright 2009 1


Safe operation of this unit can only be guaranteed if it is properly installed,<br />

commissioned, used and maintained by qualified personnel (see Section 1.11) in<br />

compliance with the operating instructions. General installation and safety instructions<br />

for pipeline and plant construction, as well as the proper use of tools and safety<br />

equipment must also be complied with.<br />

Manufacturer:-<br />

<strong>Spirax</strong> <strong>Sarco</strong> Ltd<br />

Charlton House<br />

Charlton Kings<br />

Cheltenham<br />

Glos.<br />

GL53 8ER<br />

The product is designed and constructed to withstand the forces encountered during<br />

normal use. Use of the product for any other purpose, or failure to install the product<br />

in accordance with these Installation and Maintenance Instructions, could cause<br />

damage to the product, will invalidate the marking, and may cause injury or fatality<br />

to personnel.<br />

This product complies with the requirements of Electromagnetic Compatibility<br />

Directive 2004 / 108 / EC by meeting the standards of:<br />

Safety requirements of electrical equipment for<br />

EN 61010-1-2001 measurement, control and laboratory use<br />

- Part 1 general requirements<br />

Electrical equipment for measurement, control<br />

EN 61326-1: 2006 and laboratory use EMC requirements<br />

- All relevant parts<br />

ISO 23550 2004<br />

EN 61000-4-29 2000<br />

2<br />

1. Safety information<br />

Safety & control devices for gas burning appliances<br />

Section 8 - Assessment criteria 1 and 2 met where stated<br />

dc supply voltage dips, short interruptions and variations,<br />

including additional test.<br />

Cautions: - The following conditions should be avoided as they may create<br />

interference above the limits specified in EN 61326 if:<br />

- The product or its wiring is located near a radio transmitter.<br />

- Cellular telephones and mobile radio transmitters may cause interference if used<br />

within approximately 1 metre (39") of the product or its wiring. The actual separation<br />

distance necessary will vary according to the surroundings of the installation and<br />

the power of the transmitter.<br />

If this product is not used in the manner specified by this document, particularly<br />

with regard to earthing arrangements, then the EMC protection provided may be<br />

impaired, and damage to the flowmeter could occur.<br />

IM-P330-73 MI Issue 1


1.1 Intended use<br />

Referring to these Installation and Maintenance Instructions, name-plate and<br />

Technical Information Sheet, check that the product is suitable for the intended<br />

use / application. The product listed complies with the requirements of the European<br />

Pressure Equipment Directive 97 / 23 / EC, and carries the mark when so required.<br />

The product falls within the following Pressure Equipment Directive categories:<br />

Product<br />

Group 1<br />

<strong>Gas</strong>es<br />

Group 2<br />

<strong>Gas</strong>es<br />

Group 1<br />

Liquids<br />

Group 2<br />

Liquids<br />

<strong>Flowin</strong> 2 <strong>Natural</strong> <strong>Gas</strong> <strong>Flowmeter</strong> 1 SEP - -<br />

i) The product has been specifically designed for use on <strong>Natural</strong> <strong>Gas</strong>. It may be<br />

possible to use the <strong>Flowin</strong> 2 on other gases, (excluding Hydrogen or Oxygen), but if<br />

this is contemplated, <strong>Spirax</strong> <strong>Sarco</strong> must be contacted, and written confirmation<br />

obtained. Note: Suitable values of gas reference density, molecular weight, and<br />

nominal compressibility must be programmed into the flowmeter to ensure<br />

accurate measurements of gases other than 13A (Japanese) natural gas.<br />

ii) Check material suitability, pressure and temperature and their maximum and<br />

minimum values. If the maximum operating limits of the product are lower than<br />

those of the system in which it is being fitted, or if malfunction of the product<br />

could result in a dangerous overpressure or overtemperature occurrence, ensure<br />

a safety device is included in the system to prevent such over - limit situations.<br />

iii) Determine the correct installation situation and direction of gas flow.<br />

iv) The <strong>Flowin</strong> 2 gas flowmeter is not intended to withstand external stresses that<br />

may be induced by any system to which they are fitted other than those stipulated<br />

in ISO 23550:2004 Section 7.3 ( <strong>Flowin</strong> 2 being considered as a group 2 control). It<br />

is the responsibility of the installer to consider loadings in excess of this standard<br />

and take adequate precautions to eliminate them.<br />

v) Remove protection covers from all connections and protective film from all<br />

name - plates, where appropriate, before installation.<br />

1.2 Access<br />

Ensure safe access and if necessary a safe working platform (suitably guarded)<br />

before attempting to work on the product. Arrange suitable lifting gear if required.<br />

1.3 Lighting<br />

Ensure adequate lighting, particularly where detailed or intricate work is required.<br />

1.4 Hazardous liquids or gases in the pipeline<br />

Consider what is in the pipeline or what may have been in the pipeline at some<br />

previous time. Consider: flammable materials, substances hazardous to health,<br />

and extremes of temperature.<br />

IM-P330-73 MI Issue 1 3


1.5 Hazardous environment around the product<br />

Consider: explosion risk areas, lack of oxygen (e.g. tanks, pits), dangerous gases,<br />

extremes of temperature, hot surfaces, fire hazard (e.g. during welding), excessive<br />

noise and moving machinery.<br />

1.6 The system<br />

Consider the effect on the complete system of the work proposed. Will any proposed<br />

action (e.g. closing isolation valves, electrical isolation) put any other part of the<br />

system or any personnel at risk?<br />

Dangers might include isolation of vents or protective devices or the rendering<br />

ineffective of controls or alarms. Ensure isolation valves are turned on and off in a<br />

gradual way to avoid system shocks.<br />

1.7 Pressure systems<br />

Ensure that any pressure is isolated and safely vented to atmospheric pressure.<br />

Consider double isolation (double block and bleed) and the locking or labelling of<br />

closed valves. Do not assume that the system has depressurised even when the<br />

pressure gauge indicates zero.<br />

1.8 Temperature<br />

Allow time for temperature to normalise after isolation to avoid the danger of burns<br />

and consider whether protective clothing (including safety glasses) is required.<br />

1.9 Tools and consumables<br />

Before starting work ensure that you have suitable tools and / or consumables<br />

available. Use only genuine <strong>Spirax</strong> <strong>Sarco</strong> replacement parts.<br />

1.10 Protective clothing<br />

Consider whether you and /or others in the vicinity require any protective clothing<br />

to protect against the hazards of, for example, chemicals, high / low temperature,<br />

radiation, noise, falling objects, and dangers to eyes and face.<br />

1.11 Permits to work<br />

All work must be carried out or be supervised by a suitably competent person.<br />

Installation and operating personnel should be trained in the correct use of the product<br />

according to the Installation and Maintenance Instructions.<br />

Where a formal 'permit to work' system is in force it must be complied with. Where<br />

there is no such system, it is recommended that a responsible person should know<br />

what work is taking place and, where necessary, arrange to have an assistant whose<br />

primary responsibility is safety. Post 'warning notices' if necessary.<br />

1.12 Handling<br />

Manual handling of large and /or heavy products may present a risk of injury. Lifting,<br />

pushing, pulling, carrying or supporting a load by bodily force can cause injury<br />

particularly to the back. You are advised to assess the risks taking into account the<br />

task, the individual, the load and the working environment and use the appropriate<br />

handling method depending on the circumstances of the work being done.<br />

4<br />

IM-P330-73 MI Issue 1


1.13 Residual hazards<br />

<strong>Flowin</strong> 2 is not self-venting. Take due care when removing the <strong>Flowin</strong> 2 from an<br />

installation or dismantling, taking all relevant precautions necessary for working with<br />

flammable gas equipment (refer to 'Maintenance instructions').<br />

1.14 Freezing<br />

Provision must be made to protect products from frost damage where they may be<br />

exposed to temperatures below freezing point.<br />

1.15 Disposal<br />

Unless otherwise stated in the Installation and Maintenance Instructions, this<br />

product is recyclable and no ecological hazard is anticipated with its disposal<br />

providing due care is taken.<br />

1.16 Returning products<br />

Customers and stockists are reminded that under EC Health, Safety and Environment<br />

Law, when returning products to <strong>Spirax</strong> <strong>Sarco</strong> they must provide information on<br />

any hazards and the precautions to be taken due to contamination residues or<br />

mechanical damage which may present a health, safety or environmental risk.<br />

This information must be provided in writing including Health and Safety data<br />

sheets relating to any substances identified as hazardous or potentially hazardous.<br />

1.17 Product specific warning<br />

<strong>Flowin</strong> 2 contains powerful magnets. Care should be taken when using tools or<br />

equipment containing iron near <strong>Flowin</strong>, as these items may undergo magnetic<br />

attraction. Similarly, electronic devices such as pacemakers, watches, floppy discs<br />

etc. may also be affected, and should not be placed or used close to <strong>Flowin</strong> 2.<br />

IM-P330-73 MI Issue 1 5


6<br />

2. Product information & specifications<br />

2.1 Product description<br />

Fig. 1<br />

The <strong>Spirax</strong> <strong>Sarco</strong> <strong>Flowin</strong> 2 flowmeter is designed for accurate flow measurement of dry<br />

natural gas. The unit is a 4 - 20 mA loop powered device and requires no other equipment<br />

such as temperature probes or pressure sensors to calculate a normalised (temperature<br />

and pressure compensated) flowrate.<br />

Two versions are available<br />

See Section 2.5.2 for performance data.<br />

Range 1 - standard<br />

Range 2 - low pressure drop<br />

<strong>Flowin</strong> 2 has a indexable, built in LCD display, which can show 10 digits of totalised flow.<br />

This total is resettable and is stored internally every 8 minutes to protect against data loss.<br />

Instantaneous flowrate, gas pressure and gas temperature can be displayed, in either metric<br />

or imperial units - See Section 4.2.4 for actual units available. In addition to this, <strong>Flowin</strong> 2<br />

transmits the instantaneous flowrate via the 4 - 20 mA supply, and has a user definable pulse<br />

output connection, for use with a pulse counter or similar equipment. It is also possible for<br />

a PC to communicate with the <strong>Flowin</strong> 2 via its EIA 232C (RS232) communications port. This<br />

requires an RJ11 connector and communication software (contact <strong>Spirax</strong> <strong>Sarco</strong> for further<br />

details).<br />

IM-P330-73 MI Issue 1


2.2 Principle of operation<br />

<strong>Flowin</strong> 2 operates by detecting the angular displacement of a flap caused by the momentum of<br />

the flowing gas. This angle is combined with measurements of gas temperature and pressure,<br />

and the software calculates the normalised gas flow in accordance with the (user modifiable)<br />

gas properties stored in its memory.<br />

This method of flow measurement results in very small 'overrun' errors, which can occur<br />

with other types of flowmeter under the 'start-stop' conditions often experienced with gas<br />

boiler / burner controls.<br />

2.3 Equipment delivery and handling<br />

Prior to shipment, the <strong>Spirax</strong> <strong>Sarco</strong> <strong>Flowin</strong> 2 flowmeter is built, calibrated tested and<br />

inspected to exacting standards to ensure safe and proper operation in service.<br />

At the receipt of each shipment, each carton should be inspected at the time of delivery<br />

for possible external damage. Any visible damage should be recorded immediately on the<br />

carrier's copy of the delivery slip.<br />

Each carton should be unpacked carefully and its contents checked for transit damage. If<br />

it is found that some items have been damaged or if some are missing, notify <strong>Spirax</strong> <strong>Sarco</strong><br />

immediately and provide full details. In addition, damage must be reported to the carrier with<br />

a request for their on-site inspection of the damaged item and its shipping carton.<br />

The shipping carton for the <strong>Flowin</strong> 2 should contain the following items:<br />

- The <strong>Flowin</strong> 2 gas flowmeter.<br />

- A copy of the Installation and Maintenance Instructions, (this document).<br />

- An envelope containing calibration data sheets and Declaration of Conformity.<br />

- A self-seal polythene bag containing the following items:<br />

- 1 off spare cable gland (for use when pulse output connection is required).<br />

- 4 off (blue) fork terminals, plus a spare (for wiring to loop and pulse outputs).<br />

- 2 off (uninsulated) female Lucar connectors, plus a spare (for connecting<br />

shielded cable to earth tags inside the enclosure).<br />

- 2 off braided cable assemblies (for connecting earthing points on flanges of the<br />

flowmeter to adjacent flanges in the pipework).<br />

- 2 off 'banjo' type earth tags (for alternative method of earthing to external pipework).<br />

- 4 off M6 bolts, 2 off M6 nuts and 2 off M6 shakeproof washers (for making<br />

secure earth connections to external pipework).<br />

- 1 off length of earth sleeving (for protecting the cable shielding to the earth tag inside<br />

the enclosure) - cut as required.<br />

Storage note:<br />

If <strong>Flowin</strong> 2 is to be stored for a period prior to installation, the environmental storage<br />

conditions must be at a temperature between 0°C and 60°C, and between 10% and 95%<br />

relative humidity (non-condensing).<br />

IM-P330-73 MI Issue 1 7


2.4 <strong>Flowin</strong> 2 main parts identification and recommended<br />

tightening torques<br />

8<br />

Main parts (referring to Figure 2)<br />

Recommended<br />

tightening torques<br />

(where applicable)<br />

1 <strong>Flowmeter</strong> body Refer to Section 3.3.1<br />

2 Flap assembly X<br />

3 Display PCB housing n/a<br />

4 Display PCB retaining screws (4 off) 0.6 N m<br />

5 Display PCB housing vent X<br />

6 Loop power supply and pulse output terminals 0.6 N m<br />

7 Screened cable earthing tags (2 off) See item 9<br />

8 Blanking plug 3.5 N m<br />

9 Securing nut (glands, blanking plugs and earth tags) 3.5 N m<br />

10 Gland external nut 2.0 N m<br />

11 Flange earthing tappings (2 off) 5.0 N m<br />

12 Pressure sensor X<br />

13 Sensor PCB X<br />

WARNING - Items identified with an X must not be disturbed, otherwise a malfunction<br />

or gas leak may occur.<br />

IM-P330-73 MI Issue 1


View inside the display housing<br />

3<br />

5<br />

10<br />

9<br />

7<br />

12<br />

11<br />

1<br />

11<br />

Fig. 2<br />

IM-P330-73 MI Issue 1 9<br />

6<br />

2<br />

View on arrow A<br />

A<br />

4<br />

13<br />

(below cover)<br />

8


2.5 Specifications - Performance<br />

2.5.1 Limiting conditions<br />

10<br />

PMA Maximum allowable pressure 700 kPa<br />

TMA Maximum allowable temperature 60°C<br />

PMO Maximum operating pressure *300 kPa<br />

TMO Maximum operating temperature 40°C<br />

<strong>Flowin</strong> 2 - All models<br />

Minimum allowable pressure 0.5 kPa (5mbar) abs.<br />

Minimum operating pressure *50 kPa<br />

Minimum allowable temperature 0°C<br />

Minimum operating temperature 5°C<br />

Maximum humidity level 95% RH **<br />

Notes:<br />

100 kPa = 1 bar.<br />

* <strong>Flowmeter</strong> will operate safely at pressures between 30 kPa to 600 kPa,<br />

but accuracy is not guaranteed for pressures outside this range.<br />

** Non-condensing.<br />

2.5.2 Performance data<br />

Standard model<br />

(Range 1)<br />

Low pressure drop<br />

model (Range 2)<br />

Rated capacity 350 Nm³/h † 150 Nm³/h †<br />

Turndown ratio (at 150 kPa, 20°C) 22:1 9:1<br />

Maximum pressure drop across the<br />

flowmeter<br />

22 kPa 7 kPa<br />

System accuracy ±2% FSD ±2% FSD<br />

Notes:<br />

†<br />

Normalised to Japanese reference conditions 0°C at 1 bar absolute.<br />

2.5.3 Units of measurement<br />

For details of units of measurement used, refer to Section 4.2.4.<br />

IM-P330-73 MI Issue 1


2.6 Specifications - Mechanical<br />

2.6.1 Physical data for the <strong>Flowin</strong> 2 - All models<br />

Weight of flowmeter 3.0 kg<br />

IP rating 65<br />

Materials<br />

Body<br />

Internals<br />

Aluminium alloy - aerospace grade<br />

Stainless steel, titanium, tungsten, samarium cobalt.<br />

Polymer bearing material.<br />

Finish<br />

Flange<br />

Body<br />

Faces and bore - Alocrom 1200<br />

Powder coat paint 'Gentian Blue' RAL5010.<br />

Dimensions (approximate) in mm<br />

Fig. 3<br />

88<br />

176<br />

IM-P330-73 MI Issue 1 11<br />

183<br />

69<br />

113<br />

69<br />

106<br />

70<br />

206 (min access)


2.6.2 Sizes and pipe connections<br />

<strong>Flowin</strong> 2 - All models<br />

Body size DN40<br />

JIS B2241 10K *<br />

Flange specification<br />

(Japanese Aluminium flange standard)<br />

* Although direct physical connection to a pipeline with other flange specifications is<br />

possible, <strong>Spirax</strong> <strong>Sarco</strong> recommends the use of adaptor pieces between the flowmeter and<br />

the pipeline. Please consult <strong>Spirax</strong> <strong>Sarco</strong> for further details.<br />

2.7 Specifications - Electrical<br />

2.7.1 Electrical data<br />

12<br />

Power supply<br />

Maximum current drain 22 mA<br />

<strong>Flowin</strong> 2 - All models<br />

9 - 28 volts dc<br />

4 - 20 mA current proportional to maximum rated<br />

capacity.<br />

Output 1*<br />

i.e. 4 mA = zero flow, 20 mA = maximum rated flow<br />

(user re-rangeable)<br />

Pulsed output Vmax 28 Vdc Rmin 10 kΩ<br />

User modifiable parameters<br />

Output 2*<br />

Volume per pulse 0.1, 1, 10, 100 or 1.000 Nm³<br />

Pulse width 0.02 s to 0.2 s in 0.01 s increments<br />

Error signal (programmable) 3.8 mA (LOW) or 22 mA (HIGH)<br />

EIA 232C (RS232C) via RJ11 connector<br />

Communications port<br />

(Contact <strong>Spirax</strong> <strong>Sarco</strong> for further details)<br />

Recommended specification<br />

of loop power supply and pulse<br />

output cables<br />

Permissible earth resistance<br />

(impedance)<br />

Screened, 7 strand, twisted pair with a cross<br />

sectional area of 0.5 mm². Screen to be earthed at<br />

<strong>Flowin</strong> end of cable only. Maximum cable length<br />

approximately 300 m, but in practice is governed by<br />

the number of loop devices, cable capacitance and<br />

total network resistance. See power supply<br />

0.1 Ω maximum between inside (yellow) faces of<br />

enclosure and true earth point on installation.<br />

0.1 Ω maximum between remote end of shielded<br />

cables and true earth point on installation.<br />

* To avoid measurement inaccuracies <strong>Spirax</strong> <strong>Sarco</strong> does not recommend using both Output 1<br />

and Output 2 at the same time.<br />

V (volts)<br />

28<br />

FLOWIN 2 operating range<br />

9<br />

v = 0.022 R + 6<br />

9 v < v < 28 v<br />

0<br />

0<br />

R (ohms)<br />

1000<br />

IM-P330-73 MI Issue 1


3. Installation mechanical & electrical<br />

WARNING - To avoid the risk of injury, or damage to plant and equipment, please read<br />

and apply the safety information given in Section 1 before attempting any installation<br />

work.<br />

Caution - Failure to follow the installation and commissioning instructions given in this<br />

document could result in inaccurate meter readings and/or permanent damage to the<br />

performance of the flowmeter.<br />

3.1 Installation - General<br />

<strong>Flowin</strong> 2 is a precision instrument - do not hit it or apply excessive force on any parts as this<br />

may affect its safety and accuracy.<br />

Do not attempt to remove or adjust any parts other than those specified in these<br />

instructions, as risk of gas leak or measurement inaccuracy may occur.<br />

Take extra care when working inside the enclosure as excessive strain on the internal<br />

cable assemblies and damage to the PCB's may cause the flowmeter to malfunction.<br />

The flowmeter should be installed in an environment that minimises the effects of heat,<br />

vibration, shock and electrical interference.<br />

The flowmeter should be installed at least 300 mm away from external magnetic fields,<br />

such as those generated by transformers and electric motors.<br />

Avoid installing the <strong>Flowin</strong> 2 where it is subject to sudden changes in working pressure<br />

and flowrate, as this may affect the flowmeter accuracy. If necessary, vent excessive<br />

pressure using a suitable downstream relief valve.<br />

On installation, be sure to allow sufficient clearance for:<br />

- Removal of display PCB housing.<br />

- Installation of conduit / wiring.<br />

- Viewing of the display.<br />

<strong>Flowin</strong> 2 is designed for use outdoors without additional weather protection.<br />

Do not immerse the flowmeter or allow high-pressure fluids to impact on it (e.g. water sprays<br />

that are more severe than 12.5 litres / minute through a Ø6.3 nozzle at a distance of 2.5 m).<br />

Do not apply paint to the display PCB housing vent as this may affect the accuracy of the<br />

flowmeter.<br />

IM-P330-73 MI Issue 1 13


3.2 Installation - Recommended tools and parts (not supplied)<br />

3.2.1 Recommended tools<br />

14<br />

Tool Purpose<br />

Personal grounding cord ESD protection of flowmeter during installation<br />

24 mm A/F socket and<br />

24 mm A/F spanner<br />

19 mm A/F deep socket and<br />

24 mm A/F open ended spanner<br />

19 mm A/F crows foot<br />

10 mm A/F socket and<br />

10 mm A/F spanner<br />

Tightening of flange bolts<br />

Tightening of blanking plug, securing nut, gland<br />

and gland nut<br />

For tightening of earthing points fasteners<br />

0 - 5 N m Torque wrench<br />

For torque tightening of earthing fasteners, gland<br />

fasteners and PCB cover screws<br />

0 - 160 N m Torque wrench For torque tightening of flange bolts<br />

Wire strippers<br />

For stripping of external and internal insulation of<br />

power supply and output cables<br />

Lucar crimping tools<br />

(ensure correct sizes are used)<br />

For crimping of electrical connectors inside<br />

enclosure<br />

Soldering iron For earth connectors inside enclosure<br />

Long nose pliers For fitting of earth connectors inside enclosure<br />

Electrical multimeter<br />

For checking earth resistance and general<br />

problem solving<br />

Drill, tapping drill M6 tap and wrench<br />

Proprietary pressure decay leak<br />

For alternative flange earth connection method<br />

detection equipment, electronic<br />

leak detector or proprietary leak<br />

detection fluid<br />

To verify that installation is leak free<br />

3.2.2 Recommended ancillary parts<br />

(refer to text for specifications where appropriate)<br />

Part Purpose<br />

Flange gaskets (2 off) To prevent gas leakage from flange joints<br />

Proprietary gasket sealant To prevent gas leakage from flange joints<br />

Flange bolts and nuts (8 off) To assemble flange connections<br />

DN40 filter assembly (1 off) To prevent contamination of flowmeter<br />

DN40 check valve (1 off) To prevent reverse flow through flowmeter<br />

DN40 coalescer To remove water vapour from gas<br />

Shielded electrical cable<br />

To connect flowmeter to the power supply and<br />

(as required)<br />

output devices<br />

Trunking (as required) To protect installation cabling<br />

Pipe supports (as required) To ensure pipework rigidity<br />

IM-P330-73 MI Issue 1


3.3 Installation - Mechanical<br />

3.3.1 Orientation of flowmeter<br />

The direction of flow for the <strong>Flowin</strong> 2 gas flowmeter is shown on a cast face of the flowmeter<br />

body, and also on the flowmeter data label - See Figure 4.<br />

Caution - Ensure the flowmeter is fitted the correct way round in the pipeline, otherwise<br />

damage to the flowmeter may result.<br />

The flowmeter may be installed in a horizontal or vertical pipeline, with flow either upwards or<br />

downwards. The preferred orientation for a <strong>Flowin</strong> 2 gas flowmeter is in a horizontal pipeline,<br />

with the flowmeter display facing upwards or downwards as illustrated in Figure 4.<br />

Caution: Maximum permissible flange bolt tightening torque is 160 N m<br />

Fig. 4<br />

Filter 250 micron<br />

D = Nominal bore of the pipe<br />

6'D'<br />

Upstream distance<br />

Location of<br />

flowmeter data label<br />

Location of cast flow<br />

arrow<br />

Check valve<br />

3'D'<br />

Downstream distance<br />

IM-P330-73 MI Issue 1 15


3.3.2 Upstream / downstream pipe lengths<br />

In order to provide optimum flowmetering accuracy, the minimum lengths of straight pipe<br />

required upstream and downstream of the <strong>Flowin</strong> 2 gas flowmeter are 6'D' upstream and 3'D'<br />

downstream - Where 'D' is the nominal bore of the pipe.<br />

In an installation where there are two 90° bends connected together in two perpendicular planes,<br />

the straight pipe lengths must be increased to 12'D'.<br />

Caution - Do not install the flowmeter in close proximity to a pressure reducing valve or other<br />

active equipment as this may cause inaccuracies and /or transducer damage. If this cannot be<br />

avoided then the minimum recommended lengths of straight pipe should be increased to at<br />

least 25'D' upstream of the <strong>Flowin</strong> 2 and 20'D' downstream.<br />

Do not install the flowmeter downstream of a partially open stop valve.<br />

3.3.3 General pipework considerations<br />

Ensure all pipework is clean, (i.e. free of rust and scale or other irregularities), adequately<br />

supported, properly aligned, and that during assembly, gaskets do not protrude into the line.<br />

Ensure axis of the flowmeter is aligned with the centreline of the pipework.<br />

Select flange bolts of a suitable length to avoid fouling of the flowmeter body. <strong>Flowin</strong> 2 is designed<br />

to have a maximum of 5 mm of thread protruding from the flange nuts when assembled into the<br />

gas line. Washers are not required.<br />

During assembly, ensure that the heads of the flange bolt fasteners are correctly positioned in<br />

the spotfaces in the back of the flanges otherwise uneven loading may occur.<br />

Note – Maximum permissible flange bolt tightening torque is 160 N m.<br />

3.3.4 Additional gas train components<br />

To provide protection to the <strong>Flowin</strong> 2 from contaminants, a suitably rated filter must be fitted<br />

upstream of the flowmeter as shown in Figure 4, Section 3.3.1.<br />

To provide protection for the <strong>Flowin</strong> 2 from reverse flow conditions, it is recommended to fit a<br />

suitable check valve downstream of the flowmeter as shown in Figure 4, Section 3.3.1.<br />

If it is suspected that the incoming gas contains significant amounts of moisture, then it is<br />

recommended to fit a coalescer, or similar equipment to remove all entrained moisture, upstream<br />

of the <strong>Flowin</strong> 2.<br />

16<br />

IM-P330-73 MI Issue 1


3.3.5 Final check of mechanical installation work<br />

Check tightness of all mechanical fasteners, and rigidity of installation pipework.<br />

When introducing gas into the installation for the first time, perform a leak test. This may be<br />

achieved either by using pressure decay measuring equipment, a proprietary leak detection<br />

fluid, or a suitable electronic gas leak detector.<br />

Perform any remedial work before proceeding with any electrical installation or<br />

commissioning.<br />

3.4 Installation - Electrical<br />

Caution - proper ESD (electrostatic discharge) precautions must be in place to prevent damage<br />

to the electronics of the <strong>Flowin</strong> 2 occurring whilst performing any installation /maintenance<br />

operation. As a minimum, the instrumentation engineer carrying out the work must wear an<br />

electrostatic grounding cord.<br />

Caution - The <strong>Flowin</strong> 2 must be wired in accordance with this Section, particularly with regard to<br />

earthing arrangements in order to achieve the EMC standards specified in Section 1, to prevent<br />

equipment damage or interference.<br />

WARNING - All local regulations for electrical wiring installations must be adhered to.<br />

Where conflicts occur with these installation instructions, consult <strong>Spirax</strong> <strong>Sarco</strong> for<br />

guidance.<br />

3.4.1 Electrical wiring requirements<br />

Before commencing work, study the instructions and photographs carefully to understand the<br />

connections that are required. Determine the final orientation of the display housing (0°, 90°,<br />

180° or 270°) before deciding the most suitable cable entry positions, and if appropriate, vary<br />

the instructions below to give the least amount of excess cable inside the enclosure possible.<br />

Ensure the finished workmanship is to the standard shown in the photographs by using the<br />

correct crimping tools and making the soldered connections as shown.<br />

The <strong>Flowin</strong> 2 is a loop-powered device and a nominal 24 Vdc is required to power the<br />

flowmeter. However, <strong>Flowin</strong> 2 will operate correctly as long as it is in the range shown in<br />

Section 2.7.1 / power supply. The graph shows the range of power supply voltages and loop<br />

resistances over which the <strong>Flowin</strong> 2 is capable of operating. The loop resistance includes all<br />

the wiring.<br />

A single, stand-alone, power supply may be installed in a control room or near the installed<br />

flowmeter, but not more than one power supply or <strong>Flowin</strong> 2 gas flowmeter can be on the same<br />

4 - 20 mA loop. Follow the power supply manufacturer's recommendations with regards to<br />

mounting and environmental considerations.<br />

The power supply and pulse output cable used must be in accordance with the specification<br />

listed in Section 2.7.1.<br />

IM-P330-73 MI Issue 1 17


3.4.2 Method of wiring the <strong>Flowin</strong> 2, loop supply<br />

To gain access to the loop power supply and pulse output connections, remove the 4 screws<br />

(Figure 5) that retain the display PCB housing, and carefully remove the housing from the<br />

enclosure.<br />

Caution - Do not strain the cables inside the flowmeter as this may cause the <strong>Flowin</strong> 2 to<br />

malfunction.<br />

Fig. 5<br />

Caution - Do not touch or move the small PCB which is beneth the protective cover (Figure 6)<br />

as this may invalidate the calibration of the <strong>Flowin</strong> 2, or cause it to malfunction.<br />

Fig. 6<br />

18<br />

Protective cover<br />

IM-P330-73 MI Issue 1


Loosen the outer nut on the gland (Figure 7) to release the protective red cap, which will no<br />

longer be required.<br />

Fig. 7<br />

Prepare the loop cable as shown in the following photographs:<br />

Strip off approximately 65 mm of the outer insulation, part the RF braiding and pull out the two<br />

wires using a suitable tool, see Figure 8.<br />

Fig. 8<br />

IM-P330-73 MI Issue 1 19


After separating the wires from the braiding, gather the braiding together neatly, and then strip<br />

approximately 5 mm of insulation from the two inner wires see Figure 9.<br />

Fig. 9<br />

Carefully feed the loop cable through the appropriate gland in the enclosure, and using the<br />

correct tool, crimp the blue fork connectors (supplied) onto the end of both of the two wires<br />

- Figure 10.<br />

Fig. 10<br />

20<br />

IM-P330-73 MI Issue 1


After the loop connections have been crimped, gather together the braiding from the power<br />

supply cable, and using the correct tool, crimp it onto one of the uninsulated female Lucar<br />

connectors (supplied) - Figure 11.<br />

Fig. 11<br />

Ensure all the braiding is included and that the crimp connection is properly made as shown<br />

in Figure 12.<br />

Fig. 12<br />

IM-P330-73 MI Issue 1 21


After crimping, apply solder to this joint to ensure good electrical continuity - Figure 13.<br />

Fig. 13<br />

Figure 14 - Loosen the loop +ve and loop -ve terminals on the PCB using a suitable<br />

screwdriver, and noting the correct polarity, position the blue fork connectors as shown. Tighten<br />

the screws until the connectors are secure. Refer to Section 2.4 for the recommended<br />

tightening torques.<br />

Fig. 14<br />

22<br />

IM-P330-73 MI Issue 1


Cut and slide a suitable length of earth sleeving (supplied) over the previously soldered female<br />

Lucar connector to protect the loop cable braiding from any possible short circuit. Fit the Lucar<br />

connector onto the earth tag behind the gland-securing nut as shown in Figure 15.<br />

Note the connector is a tight fit to ensure good continuity, so it is advised that pliers are used<br />

as shown below to ensure the connector is pushed fully home.<br />

Caution - Check the security of this connection before proceeding, as failure of this connection<br />

may result in serious damage to the <strong>Flowin</strong> 2.<br />

Fig. 15<br />

Caution the <strong>Flowin</strong> end of the shielded cable MUST be adequately grounded to earth otherwise<br />

EMC performance of the <strong>Flowin</strong> 2 will be impaired and serious damage may occur.<br />

Refer to Section 2.7 for the permissible earth resistance value.<br />

Refer to the wiring diagrams in Figures 17 and 18.<br />

IM-P330-73 MI Issue 1 23


Position the loop cable within the gland such that when the PCB housing is replaced in the<br />

orientation desired (0°, 90°, 180° or 270°), no crushing load is imposed on the components<br />

inside the enclosure.<br />

Using a 19 mm A / F spanner or 19 mm A / F 'Crows foot' and torque wrench, tighten the<br />

external gland nut to secure the loop cable in position (Figure 16) - Refer to Section 2.4 for the<br />

recommended tightening torque.<br />

Fig. 16<br />

Caution - If the loop cable gland nut or securing nut is not tightened correctly, the enclosure<br />

IP rating may be compromised, and damage due to water ingress may occur.<br />

24<br />

IM-P330-73 MI Issue 1


PULSE LOOP<br />

+ - - +<br />

Fig. 17 Wiring diagram for an externally powered 4 - 20 mA loop<br />

Caution - All installation cables must conform to the specifications given in Section 2.7.1.<br />

The RF braiding of all such cables must be grounded at the <strong>Flowin</strong> end.<br />

PULSE LOOP<br />

+ - - +<br />

Fig. 18 Wiring diagram for installation using an M750 display unit<br />

M750<br />

Display<br />

Unit<br />

IM-P330-73 MI Issue 1 25<br />

+<br />

-<br />

+<br />

-<br />

1<br />

2<br />

3<br />

4<br />

5 +<br />

PSU<br />

Loop<br />

powered<br />

4-20 mA<br />

display<br />

unit or<br />

chart<br />

recorder<br />

Caution - All installation cables must conform to the specifications given in Section 2.7.1.<br />

The RF braiding of all such cables must be grounded at the <strong>Flowin</strong> end.<br />

-


3.4.3 Wiring pulse output<br />

If a pulse output is required, a second cable has to be wired into the enclosure. To achieve this,<br />

remove the enclosure blanking plug and exchange it for a spare gland (supplied). To remove<br />

the blanking plug, loosen the securing nut on the inside of the enclosure using a 24 mm open<br />

ended spanner as shown in Figure 19. Retain the earthing tag and securing nut.<br />

Fig. 19<br />

Remove the outer nut from the spare gland, fit the spare gland, re-using the securing nut and<br />

earthing tag. Tighten the securing nut to the recommended tightening torque, Section 2.4.<br />

Ensure the orientation of the earthing tag is as shown in Figure 20.<br />

Fig. 20<br />

26<br />

Orientation<br />

of earthing tag<br />

IM-P330-73 MI Issue 1


Caution - If the securing nut is not tightened correctly the earth resistance may be too high,<br />

consequently the EMC performance of the <strong>Flowin</strong> 2 may be impaired and serious damage may<br />

be caused to the flowmeter.<br />

Caution - If the pulse output gland nut is not tightened correctly, the enclosure IP rating may<br />

be compromised, and damage due to water ingress may occur.<br />

Refit the outer cap loosely (Figure 21), until the pulse cable is fitted.<br />

Fig. 21<br />

IM-P330-73 MI Issue 1 27


Prepare the pulse cable in the same way as described in Section 3.4.2 (the loop power cable).<br />

Carefully feed the pulse cable through the newly assembled gland in the enclosure as shown in<br />

Figure 22, and using the correct tool, crimp the blue fork connectors (supplied) onto the ends<br />

of the 2 wires.<br />

Fig. 22<br />

After the pulse output connections have been crimped, gather together the braiding from the<br />

pulse output cable, crimp and then solder it to one of the female Lucar connectors (supplied)<br />

in the same way as described for the loop cable (Section 3.4.2).<br />

Loosen the pulse +ve and pulse -ve terminals on the PCB using a suitable screwdriver, and noting<br />

the correct polarity, position the blue fork connectors in a similar way to the loop connections.<br />

Tighten the screws . Refer to Section 2.4 for the recommended tightening torque.<br />

Cut and slide a suitable length of earth sleeving (supplied) over the previously soldered female<br />

Lucar connector to protect the pulse cable braiding from any possible short circuit. Assemble<br />

the Lucar connector onto the earth tag behind the gland-securing nut as shown in Section 3.4.2.<br />

Note the connector is a tight fit to ensure good continuity, so it is advised that pliers are used<br />

to ensure the connector is pushed fully home.<br />

Caution - Check the security of this connection before proceeding, as failure of the connection<br />

may result in serious damage to the <strong>Flowin</strong> 2. Ensure that only the <strong>Flowin</strong> end of the shielded<br />

cable is grounded in this way.<br />

28<br />

IM-P330-73 MI Issue 1


Position the pulse output cable in the enclosure (Figure 23) such that when the PCB housing is<br />

replaced in the orientation desired 0°, 90°, 180° or 270°, no bending or crushing load is imposed<br />

to the components inside the enclosure.<br />

Tighten the external gland nut to secure the pulse output cable - Refer to Section 2.4 for the<br />

recommended tightening torque.<br />

Caution - If the pulse cable gland nut is not tightened sufficiently, the enclosure IP rating may<br />

be compromised.<br />

Fig. 23<br />

The completed wiring assembly should look like Figure 24.<br />

Fig. 24<br />

IM-P330-73 MI Issue 1 29


Temporarily refit the display housing while completing the flange earth connections in Section<br />

3.3.4, then perform all final checks in Section 3.3.5 before finally fitting the display PCB<br />

housing.<br />

Remote<br />

NPN<br />

Input<br />

Remote<br />

NPN<br />

Input<br />

Fig. 25 Wiring diagram for pulse output<br />

Caution - All installation cables must conform to the specifications given in Section 2.7.1. The<br />

RF braiding of all such cables must be grounded at the <strong>Flowin</strong> end.<br />

30<br />

Power<br />

0 Volts<br />

OR<br />

Power<br />

0 Volts<br />

R<br />

R<br />

3.3.4 Wiring the flange earth connections<br />

The <strong>Flowin</strong> 2 must be earthed to the installation pipework, using the braided cables, shakeproof<br />

washers, and the hexagon screws supplied.<br />

Fig. 26<br />

PULSE LOOP<br />

+ - - +<br />

IM-P330-73 MI Issue 1


The preferred method of earthing the <strong>Flowin</strong> 2 into the installation pipework is to fit the<br />

braided earthing cable between a 'banjo' type earth tag (supplied), which has been installed<br />

under the head of a flange fastener, and the 'pre-tapped' hole in the flange of the <strong>Flowin</strong> 2 -<br />

See Figure 27 for details.<br />

'Shakeproof' washer<br />

fitted between the<br />

end of the braided<br />

cable and flange.<br />

Fig. 27<br />

Screw fitted into pre-tapped<br />

hole in the flange of the<br />

<strong>Flowin</strong> 2.<br />

Braided<br />

earthing<br />

cable.<br />

'Banjo' type<br />

earth tag.<br />

The maximum torque to be applied to the earth screws attached directly to the flowmeter body<br />

is specified in Section 2.4.<br />

Caution - To ensure good electrical continuity, and prevent damage to the meter due to poor<br />

earthing, a shakeproof washer must be fitted between the end of the braided earth lead and<br />

the flange tapping of the <strong>Flowin</strong> 2.<br />

IM-P330-73 MI Issue 1 31


Alternatively, it is permissible to drill and tap an M6 thread in each of the adjacent flanges of<br />

the <strong>Flowin</strong> 2 installation in order to fit the earthing cables in the manner shown in Figure 28.<br />

The pre-tapped holes in the flanges of the <strong>Flowin</strong> 2 already have the paint removed locally to<br />

ensure good electrical continuity at this connection.<br />

It is essential to remove any paint or corrosion found within a radius of 6 mm of the centre of any<br />

new tapping made in the adjacent flanges to ensure adequate earthing continuity at that point.<br />

Fig. 28<br />

Note: In order to achieve the earth resistance specified in Section 2.7.1 it may be necessary<br />

to fit extra earth cables in other areas of the installation.<br />

Caution - Serious damage to the <strong>Flowin</strong> 2 may occur if earthing to the installation pipework<br />

is omitted, or if the earth resistance exceeds the value specified in Section 2.7.1.<br />

3.3.5 Final check of electrical installation work<br />

Before powering up the <strong>Flowin</strong> 2 for the first time, complete the following checklist:<br />

1. Are all required connections made?<br />

(a) Loop?<br />

(b) Pulse? (if required)<br />

(c) Grounding to earth of RF braiding at the <strong>Flowin</strong> end (only) of the loop and pulse cables?<br />

(d) Flange earth connections?<br />

2. Are all the connections secure?<br />

3. Is the polarity of all connections correct?<br />

4. Check Earth resistance is in accordance with the specifications listed in Section 2.7.1.<br />

5. Ensure there is no possibility of short circuit occurring when the PCB housing is refitted.<br />

6. Refit the PCB housing to the flowmeter body in the orientation desired before 'powering<br />

up' the flowmeter.<br />

Caution - Do not operate the <strong>Flowin</strong> 2 with the display PCB housing removed from the flowmeter,<br />

as there is a conductive path between these items that is essential for its EMC performance.<br />

32<br />

IM-P330-73 MI Issue 1


4. Operating & commissioning instructions<br />

The <strong>Flowin</strong> 2 user interface consists of an LCD display, with a 5 button keypad below it<br />

Figure 29.<br />

LCD display<br />

5 button keypad<br />

Fig. 29<br />

4.1 Operating instructions - 'Run Mode'<br />

4.1.1 Introduction<br />

total<br />

high low<br />

temp<br />

imp<br />

flow pres<br />

When powered up, the <strong>Flowin</strong> 2 briefly displays all the LCD elements at once, to give a visual<br />

indication that the display is working correctly, then shows information on the software<br />

version that is running, before finally entering 'run mode'. These functions /information are<br />

also accessible in the menu structure when the flowmeter is operating in the Commissioning<br />

Mode. See Section 4.2 for details.<br />

Upon entering the run mode, the display initially shows the 'high' 5 digits of the totalised<br />

flow for approximately 9 seconds and then remains showing the 'low' 5 digits until the user<br />

intervenes.<br />

A flashing symbol at the left of the display indicates normal function of the flowmeter.<br />

OK<br />

IM-P330-73 MI Issue 1 33


4.1.2 'Run mode' display options<br />

When the flowmeter is in run mode, press the or the buttons to scroll through all<br />

the display information available, in the order listed below.<br />

34<br />

Metric units Imperial unit<br />

(Default) (Optional)<br />

Total high High 5 digits of the totaliser Nm³ Nft³<br />

Total low Low 5 digits of the totaliser Nm³ Nft³<br />

Flow Current gas flow rate Nm³/h Nft³ /min<br />

Pres Current gas pressure kPa g psi g<br />

Temp Current gas temperature °C °F<br />

The quantity being displayed is indicated by a small arrow on the edge of the display, which<br />

lines up with the annotations around it, as shown in Figure 30.<br />

Fig. 30<br />

Figure 30 illustrates a totaliser reading having 1'6801 as the high 5 digits. Press once to<br />

show the low 5 digits (16'801). The total is in units of Nm³, but if the 'imp' arrow was highlighted,<br />

it would signify that the imperial units of 'Normalised cubic feet' was the units of measure.<br />

IM-P330-73 MI Issue 1


4.1.3 Error messages<br />

Any errors detected will be displayed in run mode.<br />

The error messages will alternate with the normal run mode display and are prioritised. All<br />

errors except 'sensor constant alarm' will be latched and can only be cancelled by pressing<br />

the button. (Sensor constant alarm is self-cancelling). Once the error message has been<br />

cancelled by pressing the button the display will show the next (if any) error.<br />

Any continuous error will reinstate itself 2 seconds after it has been cancelled, and will be<br />

indicated by a flashing exclamation mark (!).<br />

Depending on settings made during commissioning, certain errors can also cause the<br />

4 - 20 mA alarm signal to be initiated.<br />

The possible error messages which are displayed over two screens are:<br />

POWER<br />

OUt<br />

NO<br />

SIGNL<br />

SENSR<br />

CONSt<br />

HIGH<br />

FLOW<br />

= Power interrupted.<br />

=<br />

=<br />

No signal from sensor.<br />

(This can also activate<br />

the 4 - 20 mA alarm).<br />

Signal from sensor constant.<br />

(This can also activate<br />

the 4 - 20 mA alarm).<br />

= Flow above the maximum.<br />

IM-P330-73 MI Issue 1 35


4.2 Operating instructions - 'commissioning mode'<br />

4.2.1 Introduction<br />

The following commissioning instructions should be followed if it is necessary to change any of<br />

the default settings for the flowmeter. All commissioning changes may be carried out by using<br />

the standard display and keypad.<br />

WARNING - The <strong>Flowin</strong> 2 commissioning should only be carried out when no gas is flowing<br />

through the flowmeter, and must only be performed by a competent person.<br />

Caution - access to the commissioning menu is pass code protected. Because incorrect<br />

settings can cause serious errors in the gas flow measurement, the password should be<br />

kept confidential to those authorised to make changes to the flowmeter operation. If it is<br />

suspected that this confidentiality is compromised, then the pass code should be changed<br />

immediately.<br />

The following sections explain how to use commissioning mode to set the gas data (density,<br />

molecular weight, etc.), re-range, set and test the outputs and change the pass code.<br />

All data entry is performed via a menu and sub-menu configuration, using the keypad buttons<br />

for navigation, i.e.<br />

Press the button to go deeper into the menu.<br />

Press the button to exit from a sub menu.<br />

Press the button to scroll down a menu.<br />

Press the button to scroll up a menu.<br />

Press the button to enter data.<br />

Please note, pressing the button to exit from a sub-menu will also have the effect of<br />

dropping down a line in the higher-level menu. This is convenient for circumstances where<br />

a long list of data has to be checked, as it saves repeated use of the button followed<br />

by the button.<br />

When editing menu items, previously entered selections will flash.<br />

When entering numeric data, use button and button to select digit, and then use<br />

button and button to cycle through the numerals. When the complete number<br />

shown is as desired, press the button.<br />

Note - After a period of five minutes without any buttons being pressed the <strong>Flowin</strong> 2 will<br />

automatically return to 'run mode'.<br />

36<br />

IM-P330-73 MI Issue 1


4.2.2 Entering commissioning mode<br />

To enter the commissioning mode press and hold down the button for 3 seconds. The<br />

display will show:<br />

ENtER<br />

PASS<br />

Followed by:<br />

The leading digit will flash indicating that this is the position of the cursor.<br />

The default factory set pass code for commissioning mode is 7452. (This can be changed<br />

from within the commissioning menu structure). The pass code can be entered by using the<br />

up and down buttons to increment /decrement the flashing value and the left<br />

and right buttons to move the cursor. Pressing will enter the pass code.<br />

If an incorrect pass code is used the display will automatically return to the run mode.<br />

After the correct pass code is entered the display shows:<br />

BASIC<br />

dAtA<br />

8888<br />

Which is the first item in the commissioning menu structure. The remaining menu items and<br />

sub-menus are shown pictorially in Section 4.2.3.<br />

Use the navigation method described in Section 4.2.1 to arrive at the desired menu item.<br />

To exit from the commissioning mode at any time, repeatedly press and release the left<br />

button until the flowmeter returns to the run mode.<br />

IM-P330-73 MI Issue 1 37


4.2.3 The <strong>Flowin</strong> 2 'run mode' and 'commissioning mode' menu structure<br />

(test display) VERxx Total high<br />

38<br />

Total low<br />

Flow<br />

Pressure<br />

Temperature<br />

ENTER PASS xxxxxxxx<br />

Automatically after 9 seconds<br />

HIGH<br />

LOW<br />

OFF<br />

ON<br />

OFF<br />

xxxx<br />

xxxx<br />

ALARM<br />

OUTPUT<br />

POWER OUT<br />

ALARM<br />

SEt PASS<br />

SW VER<br />

SW VER<br />

IM-P330-73 MI Issue 1<br />

BASIC dAtA<br />

MEtER<br />

OUt PUts<br />

tESt


UNItS<br />

REF dENSE<br />

MOLWt<br />

NOM Z<br />

AtMOS PRES<br />

S/N<br />

CLEAR tOtAL<br />

4-20 mA<br />

PULSE<br />

dISP<br />

4-20 mA Out<br />

PULSE Out<br />

x.xxx<br />

xxx.xx<br />

x.xxxx<br />

x.xx<br />

xxxxx<br />

yES<br />

NO<br />

xxx xxmA<br />

ON<br />

CANCL OFF<br />

Met<br />

IMP<br />

NUM / PULSE<br />

PULSE WIDTH<br />

IM-P330-73 MI Issue 1 39<br />

xxxxx<br />

xxx mS<br />

Set 4mA<br />

Set 20mA<br />

xxxxx<br />

xxxxx<br />

CHECK 4mA OP=4mA<br />

CHECK 4mA OP=4mA


4.2.4 BASIC DATA sub-menu<br />

40<br />

BASIC dAtA<br />

UNITS<br />

Metric (MET) or imperial (IMP) units can be displayed and transmitted.<br />

A summary of the units of measurement used is detailed in the Table below.<br />

(this data is also listed in Section 4.1.2).<br />

Units setting<br />

in sub-menu<br />

UNItS<br />

REF dENSE<br />

MOLWt<br />

NOM Z<br />

AtMOS PRES<br />

Units of measurement used<br />

Volume Flowrate Pressure Temperature<br />

Metric Nm 3 Nm 3 / h kPa g °C<br />

Imperial Nft 3 Nft 3 / min psi g °F<br />

Select either 'MET' or 'IMP' and press to confirm.<br />

The default settings are listed in Section 8.<br />

x.xxx<br />

xxx.xx<br />

x.xxxx<br />

x.xx<br />

Met<br />

IMP<br />

IM-P330-73 MI Issue 1


REF DENSE<br />

This is to enter the density of the gas at reference conditions (1 atmosphere and 0°C). The unit<br />

for this value is kg /m 3 .<br />

The default settings are listed in Section 8.<br />

MOL WT<br />

This value is the molecular weight of the flowing gas.<br />

The default settings are listed in Section 8.<br />

NOM Z<br />

This value is the nominal compressibility of the gas.<br />

The default settings are listed in Section 8.<br />

ATMOS PRES<br />

This value compensates the meter calculations for atmospheric pressure. It should be used if<br />

a high degree of accuracy is required or when the meter is installed a significant height above<br />

or below sea level.<br />

Note: Values up to two decimal places can be entered.<br />

If metric units are selected pressure units are bar absolute, for imperial units psi absolute.<br />

The default settings are listed in Section 8.<br />

IM-P330-73 MI Issue 1 41


4.2.5 METER sub-menu<br />

S/N<br />

This is the meter serial number set by the factory, and cannot be changed using the<br />

commissioning pass code.<br />

To view the serial number, press the button.<br />

CLEAR TOTAL<br />

This function allows the totalised flow to be reset to zero.<br />

To activate this function, press and hold the button for 3 seconds.<br />

4.2.6 OUTPUTS sub-menu<br />

42<br />

OUt PUts<br />

4 - 20 mA<br />

Meter S/N<br />

Clear Total<br />

PULSE yES NUM / PULSE XXXXX<br />

NO PULSE WIDTH XXX mS<br />

xxxxxx<br />

Set 4mA xxxxxx<br />

Set 4mA<br />

xxxxxx<br />

CHECK 4mA OP=4mA<br />

CHECK 20mA OP=20mA<br />

IM-P330-73 MI Issue 1


4.2.6.1 4 - 20 mA sub-menu<br />

This sub-menu provides facilities to re-range and check the 4 - 20 mA output.<br />

Set 4 mA<br />

This sets the value for the flowrate, which is equivalent to 4 mA. The minimum value that can<br />

be set as 4 mA is 0. The maximum is the 20 mA equivalent value less one. The default settings<br />

are listed in Section 8.<br />

Set 20 mA<br />

This sets the value for the flowrate, which is equivalent to 20 mA. The minimum value that<br />

can be set is the 4 mA equivalent plus one. The maximum is the meters rated maximum<br />

Normalised flow.<br />

The default settings are listed in Section 8.<br />

CHECK 4 mA<br />

This allows the 4 mA output value to be checked and re-calibrated.<br />

A calibrated digital multimeter should be connected in series with the 4 - 20 mA loop. Pressing<br />

the button will display OP = 4 mA and the <strong>Flowin</strong> 2 will attempt to output a steady 4 mA.<br />

If the multimeter does not read 4 mA the and buttons can be pressed to alter this<br />

current until 4 mA exactly is indicated.<br />

Pressing the button confirms the setting.<br />

CHECK 20 mA<br />

This allows the 20 mA output value to be checked and re-calibrated.<br />

A calibrated digital multimeter should be connected in series with the 4 - 20 mA loop.<br />

Pressing the button will display OP = 20 mA and the <strong>Flowin</strong> 2 will attempt to output a<br />

steady 20 mA.<br />

If the multimeter does not read 20 mA the and buttons can be pressed to alter<br />

this current until 20 mA exactly is indicated.<br />

Pressing the button confirms the setting.<br />

IM-P330-73 MI Issue 1 43


4.2.6.2 PULSE sub-menu<br />

This sub-menu allows customisation of the pulse output function.<br />

PULSE<br />

This selects whether the pulsed output is to be used or disabled.<br />

Select YES to enable pulse output, or NO to disable pulse output.<br />

The default settings are listed in Section 8.<br />

NUM/PULSE<br />

Allows the flow, which is represented by one pulse to be configured.<br />

Allowable values are 0.1, 1, 10, 100, or 1 000 N m³<br />

The default settings are listed in Section 8.<br />

PULSE WIDTH<br />

This allows the width of the pulse to be set.<br />

The width can be set in 0.01 second increments from 0.02 seconds to a maximum of<br />

0.2 seconds.<br />

The default settings are listed in Section 8.<br />

44<br />

IM-P330-73 MI Issue 1


4.2.7 TEST sub-menu<br />

The options on this sub-menu make it possible to manually set the <strong>Flowin</strong> 2's outputs so that<br />

diagnostic operations may be performed on the LCD display, 4 - 20 mA, and pulse output<br />

functions.<br />

DISP<br />

This allows the display to be tested. Pressing the button will cause all the segments on<br />

the display to be turned on.<br />

Pressing the button cancels the test and the menu moves down to the next option on<br />

the list.<br />

4 - 20 mA Out<br />

This allows the 4 - 20 mA output to be tested. By editing the value shown, and then pressing<br />

the button, the output is set to a specified value in mA.<br />

This output current will continue to be transmitted for five minutes or until the cancel option is<br />

chosen.<br />

PULSE OUT<br />

This allows the pulsed output to be tested. By selecting 'ON' or 'OFF' the desired test state of<br />

the pulsed output can be selected.<br />

Once the button is pressed the pulsed output will remain in the selected state for five<br />

minutes or until the cancel option is chosen.<br />

CANCEL<br />

Test Disp<br />

4 - 20mA Out<br />

xx xxmA<br />

PULSE Out ON<br />

CANCEL<br />

OFF<br />

This allows the 4 - 20 mA output or pulsed output test signal previously selected to be<br />

cancelled before the five minutes duration has expired.<br />

IM-P330-73 MI Issue 1 45


4.2.8 ALARM sub-menu<br />

This sub-menu gives access to setting the action required on the 4 - 20 mA output when an<br />

error is detected by the <strong>Flowin</strong> 2 electronics. It also allows the Power Out alarm to be turned<br />

on or off.<br />

OUTPUT ALARM<br />

This sub-menu sets the action of the 4 - 20 mA output on detection of an alarm condition.<br />

There are three possible options, the default setting being listed in Section 8.<br />

HIGH<br />

If the self-diagnostic electronics determine that the sensor output has been constant for a<br />

period of time, or is not sending a signal, it will set the 4 - 20 mA output to 22 mA.<br />

LOW<br />

If the self-diagnostic electronics determine that the sensor output has been constant for a<br />

period of time, or is not sending a signal, it will set the 4 - 20 mA output to 3.8 mA.<br />

OFF<br />

46<br />

Output<br />

Alarm<br />

Power Out<br />

Alarm<br />

This disables the 4 - 20 mA alarm function.<br />

High<br />

Low<br />

Off<br />

On<br />

Off<br />

IM-P330-73 MI Issue 1


POWER OUT ALARM<br />

This alarm indicates if there has been an interruption in the power supply to the flowmeter.<br />

This can be configured as ON or OFF.<br />

The default settings are listed in Section 8.<br />

4.2.9 SOFTWARE VERSION<br />

Press the button to view the software version.<br />

4.2.10 SET PASS CODE<br />

SW.VER<br />

Set Pass<br />

This allows the default pass code, which protects the meter from unauthorised modification of<br />

settings (i.e. commissioning mode) to be changed to another user-defined value.<br />

The default settings are listed in Section 8.<br />

Press the button and then the and buttons to increment or decrement the<br />

pass code numerals. Press to accept the change.<br />

Caution - Ensure that if the default pass code is changed to another value, that a record<br />

is kept of the new number. The record of the new number must be kept secure to avoid<br />

unauthorised persons gaining access to the commissioning menu structure.<br />

IM-P330-73 MI Issue 1 47<br />

xxx<br />

xxx


The <strong>Flowin</strong> 2 is maintenance free, and has no user-adjustable parts. If recalibration or repair<br />

is necessary, please contact <strong>Spirax</strong> <strong>Sarco</strong>.<br />

As the <strong>Flowin</strong> 2 is designed to be maintenance free, there are no spare parts available. However<br />

should additional commissioning parts, such as glands, earth leads etc. be required, please<br />

contact <strong>Spirax</strong> <strong>Sarco</strong>.<br />

Part numbers for replacement <strong>Flowin</strong> 2 flowmeters:<br />

3309894 <strong>Flowin</strong> 2 <strong>Natural</strong> <strong>Gas</strong> <strong>Flowmeter</strong> DN40 Range 1 (350 Nm³/h)<br />

3309895 <strong>Flowin</strong> 2 <strong>Natural</strong> <strong>Gas</strong> <strong>Flowmeter</strong> DN40 Range 2 (150 Nm³/h)<br />

48<br />

5. Maintenance<br />

6. Spare parts<br />

7. Fault finding<br />

The <strong>Flowin</strong> 2 undergoes a thorough final inspection at the factory. Often, faults reported on<br />

commissioning are found to be due to inappropriate installation, incorrect wiring or setting up<br />

of the flowmeter.<br />

It is therefore recommended that thorough investigations be made if problems occur, using the<br />

following checklist as a guide. If problems remain, please contact <strong>Spirax</strong> <strong>Sarco</strong>.<br />

The <strong>Flowin</strong> 2 has a built-in diagnostic features that will indicate a number of problems via the<br />

LCD display as well as the 4 - 20mA output.<br />

Error message behaviour of the <strong>Flowin</strong> 2 is explained in Section 4.1.3.<br />

IM-P330-73 MI Issue 1


Symptom Possible Causes Actions<br />

Display is blank • dc voltage is not within<br />

the range of 9 - 28 Vdc,<br />

insufficient current,<br />

or short circuit in the<br />

flowmeter power supply.<br />

• Supply connected with<br />

reverse polarity.<br />

• Electronics damaged.<br />

Display shows:-<br />

NO SIGNL<br />

Display shows: -<br />

POWER OUT<br />

Display shows: -<br />

SENSR CONST<br />

Display shows: -<br />

HIGH FLOW<br />

• Insufficient supply voltage.<br />

• Current loop resistance<br />

is greater than Rmax.<br />

(See Section 2.7.1).<br />

• Internal cable has become<br />

loose.<br />

• Electronics faulty.<br />

• Power supply interrupted<br />

(Note - this alarm can be<br />

disabled if desired, refer to<br />

Section 4.2.8).<br />

• <strong>Gas</strong> flowrate constant for<br />

6 hours.<br />

• Flap jammed.<br />

• Electronics faulty.<br />

• <strong>Flowmeter</strong> undersized.<br />

• Flap jammed in fully open<br />

position.<br />

• Check the power supply / current and<br />

connections. See Section 3.0.<br />

• Change polarity.<br />

• Contact <strong>Spirax</strong> <strong>Sarco</strong>.<br />

• Check that the supply voltage is<br />

within 9-28 Vdc.<br />

• Check the current loop resistance<br />

and reduce if necessary.<br />

• Check that the internal cables are<br />

secure.<br />

• Contact <strong>Spirax</strong> <strong>Sarco</strong>.<br />

• Ensure that power supply is secure<br />

and cancel the error using the OK<br />

button. (Note,Totals transmitted may<br />

not be accurate).<br />

• Increase or decrease the gas flowrate<br />

temporarily, error should<br />

automatically self-cancel.<br />

• Remove the unit from the line and<br />

carefully check if the flap moves freely.<br />

• Contact <strong>Spirax</strong> <strong>Sarco</strong>.<br />

• Check sizing and replace with<br />

alternative flowmeter if necessary.<br />

• Take steps to prevent sudden<br />

pulsations in the gas flow, contact<br />

<strong>Spirax</strong> <strong>Sarco</strong>.<br />

IM-P330-73 MI Issue 1 49


50<br />

Symptom Possible Causes Actions<br />

Constant 3.8 mA • Error signal set to Low. • Check display for errors and rectify<br />

as indicated.<br />

• Check current output electronics<br />

(refer to Section 4.2.7).<br />

Constant 22 mA • Error signal set to High. • Check display for errors and rectify<br />

as indicated.<br />

• Check current output electronics<br />

(refer to Section 4.2.7).<br />

Flow indicated<br />

responds to<br />

changes in<br />

actual flow but<br />

value indicated<br />

does not<br />

correspond to<br />

actual flowrate<br />

• Installation not in<br />

accordance with Section 3<br />

of this document.<br />

• Incorrect settings of the<br />

flowmeter for the specific<br />

installation.<br />

• Check installation is in accordance<br />

with Section 3 of this document.<br />

Possible causes are:<br />

• Installation environment outside<br />

specifications.<br />

• Rusty or contaminated pipework.<br />

• Dirty or wet gas.<br />

• The axis of the flowmeter bore is not<br />

concentric with the pipeline.<br />

• <strong>Gas</strong>kets faces protruding into bore.<br />

• <strong>Flowmeter</strong> too close to other pipeline<br />

components.<br />

• Flow direction incorrect.<br />

• Review the default gas properties<br />

and atmospheric pressure that are<br />

programmed into the flowmeter<br />

and modify if necessary (ref.<br />

Section 4.2.4).<br />

• <strong>Flowmeter</strong> may be damaged, contact<br />

<strong>Spirax</strong> <strong>Sarco</strong>.<br />

IM-P330-73 MI Issue 1


Symptom Possible Causes Actions<br />

A flow indicated<br />

when no actual<br />

flow is in the<br />

pipe, or there<br />

is discrepancy<br />

between LCD<br />

display and the<br />

4 - 20 mA output<br />

Pulse output<br />

not working,<br />

incorrect,<br />

or does not<br />

correspond to<br />

LCD display<br />

output<br />

<strong>Flowin</strong> noisy<br />

in operation<br />

(banging and<br />

clattering)<br />

• 4 mA retransmission set to<br />

a value higher than zero.<br />

• 20 mA retransmission set<br />

to an unsuitable value.<br />

• Mains interference.<br />

• Contamination in the<br />

pipeline preventing the flap<br />

from closing.<br />

• Pulse output disabled or<br />

incorrectly programmed.<br />

• Pulse output is overloaded.<br />

• Pulse output electronics<br />

faulty.<br />

• Upstream/ downstream<br />

installation lengths incorrect.<br />

• Severe pulsating flow<br />

conditions.<br />

• Reset 4 mA output<br />

(see Section 4.2.6).<br />

• Modify 20 mA output<br />

(see Section 4.2.6).<br />

• Check earthing.<br />

• Remove the flowmeter from the<br />

pipeline and inspect the flap<br />

assembly.<br />

• Check the programming of the pulse<br />

output, (Section 4.2.6.2) and ensure<br />

that it is compatible with the pulse<br />

counter electronics.<br />

• Check load ratings (see Section 2.7.1)<br />

• Test pulse output (see Section 4.2.7)<br />

If faulty contact <strong>Spirax</strong> <strong>Sarco</strong>.<br />

• Remove the flowmeter from the<br />

line and inspect the flap assembly<br />

for damage, Re-install following the<br />

installation guidelines (Section 3).<br />

• <strong>Flowmeter</strong> may be damaged<br />

internally - contact <strong>Spirax</strong> <strong>Sarco</strong>.<br />

IM-P330-73 MI Issue 1 51


The following settings are the default values programmed into the <strong>Flowin</strong> 2 at the factory.<br />

These settings are user modifiable in 'commissioning mode' (see Section 4.2), but should only<br />

be altered by a competent person.<br />

Caution - The functionality and accuracy of the <strong>Flowin</strong> 2 relies on the correct selection<br />

of these settings, which are pass code protected. Do not allow unauthorised persons to<br />

make changes.<br />

52<br />

Submenu<br />

Changeable settings<br />

(commissioning mode)<br />

8. Settings table<br />

Standard model<br />

(Range 1)<br />

Factory default<br />

settings<br />

Low dP model<br />

(Range 2)<br />

Factory default<br />

settings<br />

Units Metric Metric<br />

Reference density **kg/m³ 0.822 0.822<br />

Basic<br />

Data*<br />

Molecular weight 18.37 18.37<br />

Nominal compressibility (z) 0.997 0.997<br />

Atmospheric pressure 1.01 bar absolute 1.01 bar absolute<br />

4 mA setting Nm³/h 0 0<br />

20 mA setting Nm³/h 350 150<br />

Outputs Pulse No No<br />

Number of m³ per pulse 0.1 0.1<br />

Pulse width ms 0.2 0.2<br />

Alarm<br />

Output<br />

Power out<br />

High<br />

Off<br />

High<br />

Off<br />

Set pass Pass code 7452 7452<br />

*<br />

Default gas is Japanese 13A natural gas with the following composition-Methane (CH4) 89.6%,<br />

Ethane (C2H6) 5.62%, Propane (C3H8) 3.43%, n-Butane (C4H10) 1.35%, Odoriser 5mg/Nm³.<br />

** Reference conditions used are, 1 atmosphere and 0°C.<br />

IM-P330-73 MI Issue 1


User customised settings - The table below is provided for the user to record custom settings<br />

for future reference.<br />

Sub-menu<br />

Basic Data<br />

Outputs<br />

Alarm<br />

Changeable settings<br />

(commissioning mode)<br />

Units<br />

Reference density<br />

Molecular weight<br />

Nominal compressibility (z)<br />

Atmospheric pressure<br />

4 mA setting<br />

20 mA setting<br />

Pulse<br />

Number of m³ per pulse<br />

Pulse width ms<br />

Output<br />

Power out<br />

Set pass Pass code<br />

Custom 1 Custom 2<br />

IM-P330-73 MI Issue 1 53


54<br />

IM-P330-73 MI Issue 1


IM-P330-73 MI Issue 1 55


56<br />

IM-P330-73 MI Issue 1

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!