PLH_KKK_32_85.QXP 25.05.2007 10:11 Uhr Seite 64EXAMPLES FOR THE PUMP SELECTION IN THE CONDENSER CIRCUITThe selected pump is the Wilo-TOP-S 50/43-PN 6/10.Cavitation can be ruled out since this is a closedcircuit. For protection, the condenser circuitshould have its own safety valve <strong>and</strong> beequipped with its own diaphragm extensionvessel for a volume expansion of 2 to 5 %.Delivery head H [m]5,04,54,03,53,02,52,01,511,00,50 5min2max10 15 20 25 30Flow Q [m³/h]Note!The pump must constantly circulate the requiredwater volume when the refrigerating machine isin operation. This is to be ensured by a hydraulicswitch, heat exchanger, differential pressurevalves or bypasses.Operating data specificationsFlow 8.62 m 3 /hDelivery head4.09 mPumped fluidWaterFluid temperature 70 °CDensity 0.9777 kg/dm 3Kinematic viscosity 0.4084 mm 2 /sVapor pressure0.3121 barHydraulic data (duty point)Flow 8.88 m 3 /hDelivery head4.3 mPower consumption P1 0.295 kWSpeed2600 rpmThe necessary <strong>cooling</strong> towers are to be designedwith their own pump, as described before. Whenantifreeze is added, system separation with heatexchangers is recommended.64 Subject to change without prior notice 02/2007 WILO AG