The peeling length l corresponds to the length of the<br />

peeling blades.<br />

For pipes of diameter d = 16 mm, chamfer about 2 mm<br />

of the pipe end at an angle of 15 °. Prepare about 15 mm<br />

of the pipe end with a scraper. Mark off the jointing<br />

length of 13 mm on the pipe.<br />

Thoroughly clean the fitting socket with absorbent paper<br />

and cleaning fluid (e. g. Tangit cleaner). Use fresh paper<br />

each time.<br />

Mark the required position on both the pipe and the<br />

fitting before jointing.<br />

Fusion jointing procedure<br />

Heating<br />

Quickly push first the fitting onto the heating spigot to the<br />

correct depth and then the pipe into the heating bush<br />

axially, without twisting, and hold firmly. The heating<br />

times in the table below are measured from this point on.<br />

Fusion joints should not be used for pipes whose walls<br />

are thinner than those listed in the table.<br />