29.09.2015 Views

Protection relay software models in interaction with power system simulators

Protection relay software models in interaction with power system ...

Protection relay software models in interaction with power system ...

SHOW MORE
SHOW LESS
  • No tags were found...

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

VII. RELAY LIBRARIES<br />

As shawn <strong>in</strong> Figure 6, several <strong>models</strong> of earth-fault<br />

<strong>relay</strong>s are modelled and stored <strong>in</strong> <strong>relay</strong> library.<br />

Modelled earth-fault <strong>relay</strong>s are: overcurrent (51N),<br />

directional voltage or current polarised directional (67N,<br />

32U or 32I), directional sensitive or wattmetric/warmetric<br />

(67Ns, 32W) and admittance earth-fault <strong>relay</strong>.<br />

Figure 6: Earth-fault <strong>relay</strong> <strong>models</strong> library<br />

Def<strong>in</strong>ite time earth-fault overcurrent <strong>relay</strong> is nondirectional<br />

<strong>relay</strong> which compares measured or from phase<br />

currents derived earth-fault current <strong>with</strong> set constant<br />

value.<br />

Inputs for traditional directional current polarised <strong>relay</strong><br />

are 3I 0 and I pol , where I pol is polaris<strong>in</strong>g current obta<strong>in</strong>ed<br />

from neutral po<strong>in</strong>t ground conductor [6]. So, this <strong>relay</strong> is<br />

only suitable for solidly or low impedance grounded<br />

distribution networks. It calculates torque (term derived<br />

from electro-mechanical <strong>relay</strong><strong>in</strong>g) based on magnitudes<br />

and relative angle of analog <strong>in</strong>put quantities, Equation 1.<br />

Relay compares the result of calculated torque aga<strong>in</strong>st set<br />

thresholds. If torque is positive and above the positive<br />

threshold, then <strong>relay</strong> determ<strong>in</strong>es a forward earth-fault. If<br />

torque is negative and below the negative threshold, then<br />

<strong>relay</strong> determ<strong>in</strong>es a reverse earth-fault.<br />

where:<br />

I pol : Polaris<strong>in</strong>g current<br />

3I 0 : = I A +I B +I C<br />

| | | | ( - ) (1)<br />

Directional voltage polarised <strong>relay</strong> makes directional<br />

decision accord<strong>in</strong>g to Equation 2. The <strong>relay</strong> compares<br />

calculated Z0 aga<strong>in</strong>st Z0F and Z0R thresholds to<br />

determ<strong>in</strong>e the direction of the ground fault.<br />

[ ]<br />

| |<br />

(2)<br />

where (* - complex conjugate):<br />

3V 0 : = V A +V B +V C<br />

3I 0 : = I A +I B +I C<br />

Θ L0 : L<strong>in</strong>e zero-sequence impedance angle<br />

Directional wattmetric <strong>relay</strong> makes directional<br />

decision accord<strong>in</strong>g to Equation 3. The <strong>relay</strong> compares<br />

calculated W aga<strong>in</strong>st -w and +w thresholds to determ<strong>in</strong>e<br />

the direction of the ground fault. W < -w <strong>in</strong>dicates a<br />

forward fault and W > +w <strong>in</strong>dicates a reverse fault.<br />

[ ⃗⃗⃗ ⃗⃗ ] (3)<br />

Earth-fault admittance <strong>relay</strong> algorithm is centralised<br />

and it simultaneously uses zero currents from all galvanic<br />

connected feeders (on the same busbar) and common zero<br />

voltage. It calculates zero asymmetry admittance for each<br />

feeder. Asymmetries occur as a consequence of<br />

asymmetries of feeder capacitances to the earth or of an<br />

earth-fault. Advantage is that it also calculates asymmetry<br />

admittance change dY. This algorithm has two thresholds,<br />

an absolute Y as_max and the sensitive one dY as_max .<br />

VIII. CONCLUSION<br />

In this paper methodology for <strong>power</strong> <strong>system</strong> and <strong>relay</strong><br />

modell<strong>in</strong>g is described <strong>in</strong> accordance to the relevant<br />

literature. A distribution <strong>system</strong> and several earth-fault<br />

<strong>relay</strong> <strong>models</strong> are developed us<strong>in</strong>g user friendly open<br />

<strong>system</strong> environment Matlab and Simul<strong>in</strong>k.<br />

Developed comprehensive <strong>relay</strong> <strong>models</strong> process<br />

voltage and current transient waveforms obta<strong>in</strong>ed from<br />

electromagnetic transients simulations, actual fault<br />

waveforms captured by numerical <strong>relay</strong>s, or from digital<br />

fault recorders. This way user can observe their response<br />

to these transients and reaffirm the protection behaviour<br />

dur<strong>in</strong>g network disturbances.<br />

In the future <strong>in</strong>tention is to develop <strong>relay</strong> <strong>software</strong><br />

modell<strong>in</strong>g for relevant test<strong>in</strong>g prior the build<strong>in</strong>g of a<br />

prototype <strong>relay</strong>s. This is essential <strong>in</strong> the development<br />

process because, it allows test<strong>in</strong>g of various <strong>relay</strong><strong>in</strong>g<br />

algorithms, the <strong>relay</strong> logic and to make necessary changes<br />

<strong>with</strong>out the need to make changes <strong>in</strong> hardware or <strong>software</strong><br />

modules of the actual device.<br />

REFERENCES<br />

[1] T. S. Sidhu et al, “Software <strong>models</strong> for use <strong>with</strong> Electromagnetic<br />

Transient Analysis Programs,” CIGRE WG B5.17 Report, Ref. No.<br />

295, 2006.<br />

[2] A. K. S. Chaudhary et al, “Model<strong>in</strong>g and analysis of transient<br />

performance of protection <strong>system</strong>s us<strong>in</strong>g digital programs,” IEEE<br />

WG Task Force Special Publication, 1998.<br />

[3] P: G. McLaren et al, “Software <strong>models</strong> for <strong>relay</strong>s,” IEEE<br />

Transactions on Power Delivery, Vol. 16, No. 2, pp. 238-246, 2001.<br />

[4] M. Kezunović, “ User-friendly, open-<strong>system</strong> <strong>software</strong> for teach<strong>in</strong>g<br />

protective <strong>relay</strong><strong>in</strong>g application and design concepts,” IEEE<br />

Transactions on Power Systems, Vol. 18, No. 3, pp. 986-992, 2003.<br />

[5] G. Sybille et al, “Theory and Applications of Power System<br />

Blockset, a MATLAB/Simul<strong>in</strong>k-Based Simulation Tool for Power<br />

Systems,” IEEE Power Eng<strong>in</strong>eer<strong>in</strong>g Society W<strong>in</strong>ter Meet<strong>in</strong>g,<br />

Vol.1, pp. 774-779, 2000.<br />

[6] J. Roberts, H. J. Altuve, D. Hou, “Review of ground fault<br />

protection methods for grounded, ungrounded and compensated<br />

distribution <strong>system</strong>s,” Technical paper, Schweitzer Eng<strong>in</strong>eer<strong>in</strong>g<br />

Laboratories, 2001.<br />

[7] A. Guzman, J. Roberts, D. Hou, “New ground directional elements<br />

operate reliably for chang<strong>in</strong>g <strong>system</strong> conditions,” 51 st Annual<br />

Protective Relay<strong>in</strong>g Conference, Atlanta, Georgia, 1997.<br />

[8] I. G. Kuliš, “Earth-fault detection methods <strong>in</strong> resonant grounded<br />

MV networks,” Study report for DSO, EIHP, 2006.<br />

[9] I. G. Kuliš et al, “Typ<strong>in</strong>g of solutions for the implementation of<br />

neutral po<strong>in</strong>t ground<strong>in</strong>g <strong>in</strong> MV networks,” Study report for DSO,<br />

Končar – Institut, 2010.<br />

[10] I. G. Kuliš et al, “The criteria for neutral po<strong>in</strong>t treatment selection<br />

<strong>in</strong> 20(10) kV radial networks <strong>in</strong> “Elektra” Zagreb,” 20 th<br />

International Conference on Electricity Distribution, CIRED,<br />

Prague, 2009.<br />

1070 MIPRO 2012/MEET

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!