English - FOXBORO ECKARDT GmbH
English - FOXBORO ECKARDT GmbH
English - FOXBORO ECKARDT GmbH
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
PSS EVE0105 E-(en) SRD991 9<br />
Electrical classification<br />
1) 2)<br />
see Certificates of Conformity EX EVE0105 A<br />
Type of protection “Intrinsically Safe”<br />
TypeAI638.............II2GEExiaIIB/IIC,<br />
II 2 G EEx ib IIB/IIC<br />
Temperature classes<br />
Version with HART communication and "without communication":<br />
T4 with explosion protection code EA4<br />
Version with communications HART, FOUNDATION Fieldbus and<br />
PROFIBUS-PA:<br />
T4 / T6 with explosion protection code EAA<br />
Certificate of Conformity ....PTB 00 ATEX 2128<br />
For use in hazardous areas in circuits certified as intrinsically<br />
safe with the following maximum values:<br />
Input circuit: U max = 30 V, I max = 130 mA, P max = 0.9 W<br />
Li = negligible, Ci = 1.3 nF (5.3 nF to earth)<br />
Ambient temperature ranges:<br />
TemperatureclassT4: ....–40°Cto+80°C<br />
TemperatureclassT6: ....–40°Cto+55°C<br />
Explosion protection Zone 2<br />
Installation of the SRD991 in potentially explosive<br />
atmospheres for Zone 2 (explosion protection EEx nA / nL)<br />
The Intelligent Positioner SRD991, type AI 638 in protection<br />
level intrinsic safety "ia" (II 2 G EEx ib/ia IIB/IIC T6/T4 Gb)<br />
can be operated in potentially hazardous areas of Zone 2<br />
(EEx nA / nL Gc) also on a normal (not intrinsically safe)<br />
power supply, of which the voltage output is not higher than<br />
the maximum value for explosion protection intrinsic safety<br />
(according to EN 50014 / EN 50020) described in the<br />
EC-Type-Examination Certificate PTB 00 ATEX 2128.<br />
The non intrinsic safe circuit has additionally to fulfill the<br />
requirements of EN 61010-1 (IEC 1010-1), protection grade<br />
III, overvoltage category I.<br />
See our Manufacturer’s Declaration on our website.<br />
Explosion protection Zone 20<br />
Certificate of Conformity .........IBExU08 ATEX 1148<br />
EX II 1D Ex iaD 20 T 100°C. ......–40°C