PADDLE FLOWMETER KPM
KPM ï¼è±æï¼
KPM ï¼è±æï¼
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
KROHNE 03/2008 <strong>KPM</strong><br />
<strong>PADDLE</strong> <strong>FLOWMETER</strong><br />
<strong>KPM</strong><br />
Paddle flowmeters<br />
Variable area flowmeters<br />
Flow controllers<br />
Electromagnetic flowmeters<br />
Level measuring instruments<br />
Communications technology<br />
Engineering system & solutionns<br />
Temp meters<br />
Pressure meters
Measuring principle<br />
If a medium flows with sufficient velocity through the horizontally<br />
or vertically arranged measuring chamber. If the <strong>KPM</strong> fitting, the<br />
paddle will swivel around the axie until the force of the medium<br />
and the opposing force of the paddle surface plus the spring<br />
tension establish equilibrium. The angular position or the position<br />
of equilibrium of the paddle in the measuring chamber is the<br />
measure for the flow. The encapsulated ring-type permanent<br />
magnet at the end of the paddle axis then transmits this position<br />
to the scale and the optional electronic evaluators through the<br />
magnet tracking indicator system.This happens safely and without<br />
packing glands. The flow rates shown on the scale only apply to<br />
the calibrated medium or to a medium with the same physical<br />
characteristics.<br />
Introduction<br />
<strong>KPM</strong> flowmeter is suitable for measurement of liquid in pipes.<br />
The special advantage is that it can be used for all directions<br />
2. Paddle 3. Paddle axis with torsion spring<br />
4. Pointer<br />
of flow. It can show the current flow rate in volume or mass per<br />
unit in time.<br />
Applications: flow measurement, dosing, monitoring, adjusting<br />
and control of liquid products. The meter’s design makes it<br />
ideal for processes under difficult and adverse operating<br />
conditions.<br />
1. Fitting<br />
The devices are available with additional electrical equipment<br />
for process monitoring and control.<br />
6. Scale panel<br />
Approvals:<br />
• ISO9001<br />
• ERP Pass Financial Certificates<br />
• Membership of the Sinopec Resource Market<br />
• Membership of the first order supplying the network of the<br />
PetroChina<br />
• CMC:JIZHI 08000115
Features:<br />
• Tube Size:DN50-DN300;Pressure Rating :PN10-PN40;Temp:< 200℃<br />
• Measurement of the liquid<br />
• Liquid waste<br />
• All directions of flow<br />
• Reliable Capability, Steady Measure<br />
• Output:Current Signal、Local Display 、HART,PROFIBUS<br />
• Corrosive Fields and Volatile Fields<br />
• Ex“ia”<br />
Main technical Parameters<br />
Type<br />
<strong>KPM</strong><br />
Messuring ranage(100%) 水 :20℃ 2-600m 3 /h<br />
Accuracy 2.5<br />
Scale<br />
Meter Size<br />
Actually flow<br />
DN50-DN300<br />
PN40(DN50-DN80)<br />
Pressure class<br />
PN16(DN100-DN200)<br />
PN10(DN250-DN300)<br />
Connect flange size<br />
DN50-DN300<br />
Fluid Temp - 20℃ ~+200 ℃<br />
Ambient Temp<br />
With switches<br />
With signal output<br />
- 20℃ ~+80℃<br />
Power : 8V DC<br />
Ambient Temp: -20℃~+60℃<br />
Analog Signals : 4-20mA(2-wires)<br />
Power: 24VDC±10~20%<br />
Ambient Temp: -20℃~+60℃
Model instructions<br />
<strong>KPM</strong> Series :<br />
∕□ ∕□ ∕□ ∕□ ∕□ ∕□ ∕□ ∕□<br />
1 2 3 4 5 6 7 8<br />
1 05S DN50 SANDWICH 05F DN50 FLANGE F-STNDARD: DIN2501,HG,GB,ANSI. ETC<br />
08S DN80 SANDWICH 08F DN80 FLANGE F-STNDARD: DIN2501,HG,GB,ANSI. ETC<br />
10S DN100 SANDWICH 10F DN100 FLANGE F-STNDARD: DIN2501,HG,GB,ANSI. ETC<br />
12S DN125 SANDWICH 12F DN125 FLANGE F-STNDARD: DIN2501,HG,GB,ANSI. ETC<br />
15S DN150 SANDWICH 15F DN150 FLANGE F-STNDARD: DIN2501,HG,GB,ANSI. ETC<br />
20S DN200 SANDWICH 20F DN200 FLANGE F-STNDARD: DIN2501,HG,GB,ANSI. ETC<br />
25S DN250 SANDWICH 25F DN250 FLANGE F-STNDARD: DIN2501,HG,GB,ANSI. ETC<br />
30S DN300 SANDWICH 30F DN300 FLANGE F-STNDARD: DIN2501,HG,GB,ANSI. ETC<br />
2 U Vertically top to bottom<br />
D Vertically bottom to top<br />
R Horizontally right to left<br />
L Horizontally left to right<br />
3 RR1 304 , 1Cr18Ni9Ti<br />
RR0 316Ti , 0Cr17Ni12MoTi<br />
RRL 316l , 00Cr17Ni14Mo2<br />
4 M81 M81 Aluminum indicator with local flow value<br />
M9 M9 Aluminum indicator with local flow value<br />
5 00 No Switches (Default)<br />
K1 With one 2-wires Switch<br />
K2 With two 2-wires Switch<br />
KD1 With one 3-wires Switch<br />
KD2 With two 3-wires Switch<br />
6 00 No Signal Putput (Default)<br />
ESK 4-20mA (M9)<br />
ESKZ 4-20mA Totalizer (M9)<br />
Es 4-20mA (M81)<br />
7 00 Non Ex (Default)<br />
Exi ExiaIICT3-T6<br />
Exd ExdIIbT3-T6<br />
8 HT For medium temp>100 ℃
Measuring range table<br />
Nominal<br />
size(DN)<br />
50<br />
80<br />
100<br />
125<br />
150<br />
200<br />
250<br />
300<br />
Measuring<br />
range code<br />
Measuring range----- Water 1000Kg/m 3<br />
5.1 2-10 m 3 /h<br />
5.2 5-30 m 3 /h<br />
8.1 4-25 m 3 /h<br />
8.2 6-50 m 3 /h<br />
8.3 8-70 m 3 /h<br />
10.1 6-45 m 3 /h<br />
10.2 10-80 m 3 /h<br />
10.3 15-100 m 3 /h<br />
12.1 15-100 m 3 /h<br />
12.2 20-125 m 3 /h<br />
15.1 20-150 m 3 /h<br />
15.2 25-200 m 3 /h<br />
20.1 25-200 m 3 /h<br />
20.2 40-300 m 3 /h<br />
20.3 60-450 m 3 /h<br />
25.1 40-300 m 3 /h<br />
25.2 70-400 m 3 /h<br />
25.3 80-500 m 3 /h<br />
30.1 80-400 m 3 /h<br />
30.2 120-600 m 3 /h<br />
Installation<br />
Installation conditions<br />
The <strong>KPM</strong> can be installed vertically or horizontally (according to the direction of flow indicated in the order). The nominal size of<br />
the product line to be connected must correspond to the nominal size of the <strong>KPM</strong>. The best installation position is between loose<br />
flanges。When installing the device between weld-on flanges, the flange hole pattern has to be turned so that the indicator unit is in a<br />
horizontal position if the pipe arrangement is horizontal. The nominal size of the product line to be connected must correspond to the<br />
nominal size of the <strong>KPM</strong>. Avoid fittings converging on one side directly in front of the device.<br />
The adequate distance to ferromagnetic parts must be observed. During installation, the standard inlet section must be 5 x D<br />
and the standard outlet section 3 x D.<br />
We recommend that the lateral distance between two adjacently mounted devices be 300 mm. The devices can be mounted close<br />
together if vertically offset by one device length. The minimum lateral distance for interfering steel parts should be 200 mm. In case of<br />
doubt, check the interference by moving the device back and forth in the selected distance by about 200 mm and testing whether the<br />
pointer position changes.<br />
Select the mounting location so as to enable a reliable reading of the scale values. Please take note as well of the space<br />
requirement for a possible disassembly of the device.
Installation draft:<br />
Horizontal; from the left to the right Model:<strong>KPM</strong>/L Horizontal; from the right to the left Model:<strong>KPM</strong>/R<br />
Vertical: from the top to the bottom Model:<strong>KPM</strong>/U<br />
Vertical: from the bottom to the top Model :<strong>KPM</strong>/D
Installation size<br />
Sandwich connection<br />
Flange connection<br />
The others same as sandwich
CRK<br />
Chengde Rehe-KROHNE Meters CO., LTD.<br />
Add: Chengde High-Tech Development<br />
Zone Postcode: 067000<br />
Tel: 0314-2120930 2120940 2120875<br />
Fax: 0314-2120920 2120077<br />
E-mail: llh@rehe-krohne.com<br />
Beijing Branch Office<br />
Add: Room 704-707,Fang Heng International Mansion Building B Wang Jing District Beijing<br />
Postcode: 100102<br />
Tel: 010-5875576<br />
Fax: 010-58785476<br />
E-mail: beijing@rehe-krohne.com<br />
Shanghai Office<br />
Add: No.125 Chang Ning Road, Jun Zi Lan Flat 15A, Shanghai<br />
Postcode: 200042<br />
Tel: 021-62408911<br />
Fax: 021-62516350<br />
E-mail: shanghai@rehe-krohne.com<br />
Xinjiang Office<br />
Add: Hongshiyue garden, str. 213 yangtse, Urumqi (wulumiqi)<br />
Tel: 0991-4523018<br />
Fax: 0991-4523018<br />
E-mail: yzh@rehe-krohne.com<br />
Copyright:Chengde Rehe-KROHNE Meters CO.,LTD.