PRAKAB Export Catalogue
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
HALOGEN-FREE ENERGY CABLES 0.6/1 kV<br />
FR–N1X1G1–AR<br />
Halogen-free energy cable<br />
SCHWECHATER KABELWERKE<br />
DESIGN<br />
TECHNICAL DATA<br />
Standard:<br />
NFC 32-323<br />
Rated voltage:<br />
0.6/1 kV<br />
Test voltage:<br />
4 kV/50 Hz<br />
4 3 2 1<br />
1 | Aluminium conductor, round stranded (RM),<br />
resp.sector-shaped stranded (SM)<br />
2 | Core insulation (XLPE)<br />
3 | Inner covering (halogen-free plastic tape or halogen-free<br />
polymer compound)<br />
4 | Sheath (halogen-free polymer compound, grey)<br />
APPLICATION<br />
These cables are intended for the stationary distribution of electrical<br />
energy in dry or damp premises and for fixed installations<br />
in air or concrete. Suitable for hotels, hospitals, underground<br />
railways, airports etc. to protect people and technical building<br />
equipment in the event of fire if circuit integrity is not required.<br />
Not allowed for installations underground or in water.<br />
Temperature range:<br />
laying temperature: min. –5 °C<br />
operating temperature: –50 °C up to +90 °C<br />
conductor temperature: max. +90 °C<br />
short-circuit temperature: max. +250 °C/5 s<br />
Bending radius (min.):<br />
15 x ∅ of cable<br />
Core identification:<br />
HD 308 S2<br />
Fire properties:<br />
flame retardant:<br />
EN 60332-1-2<br />
halogen-free, non-corrosive combustion gases:<br />
EN 50267-2-2<br />
reduced flame propagation:<br />
EN 60332-3-24<br />
low smoke emission:<br />
EN 61034-2<br />
Number of cores<br />
x nominal cross<br />
section<br />
(mm²)<br />
Max. conductor<br />
resistance<br />
(Ω/km)<br />
Current rating<br />
in the air 1)<br />
(A)<br />
FR–N1X1G1–AR<br />
Outer diameter<br />
(mm) ca.<br />
Total weight<br />
(kg/km) ca.<br />
Standard lengths/<br />
packing<br />
(m)<br />
1 x 25 RM 1.200 136 12.5 205 500 D, 1000 D<br />
1 x 35 RM 0.868 166 13.5 235 500 D, 1000 D<br />
1 x 50 RM 0.641 205 15.0 295 500 D, 1000 D<br />
1 x 70 RM 0.443 260 16.5 375 500 D, 1000 D<br />
1 x 95 RM 0.320 321 18.5 475 500 D, 1000 D<br />
1 x 120 RM 0.253 376 20.5 570 500 D, 1000 D<br />
1 x 150 RM 0.206 431 22.5 690 500 D, 1000 D<br />
1 x 185 RM 0.164 501 24.5 830 500 D, 1000 D<br />
1 x 240 RM 0.125 600 27.5 1,050 500 D, 1000 D<br />
1 x 300 RM 0.100 696 30.0 1,280 500 D, 1000 D<br />
11<br />
1) basic rated current acc. to NFC 32-323<br />
Subject to technical changes.<br />
SKW.AT | MEMBER OF SKB-GROUP<br />